MELIPC MI5000 Series
User's Manual (Application)

-MI5122-VW

Summary of Contents for MELIPC MI5000 Series

Page 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...

Page 2: ......

Page 3: ...uits for conflicting operations such as forward reverse rotations or upper lower limit positioning must be configured external to the product 2 When the product detects an abnormal condition it stops the operation and all outputs are Turned off if the overcurrent or overvoltage protection of the power supply module is activated Held or turned off according to the parameter setting if the self diag...

Page 4: ... position of the main module and push in the fan module until the fan module fixing hook snaps into place Check that the fan module fixing hook is fixed to the main module securely If the fan module is not connected properly the fan may not rotate or it may cause malfunction due to rise in temperature of the main module To disconnect a fan module securely press the fan module fixing hook with your...

Page 5: ...made of nylon can be used as well If not dangling cable may swing or inadvertently be pulled resulting in damage to the module or cables or malfunction due to poor contact Check the interface type and correctly connect the cable Incorrect wiring connecting the cable to an incorrect interface may cause failure of the module and external device Tighten the terminal screws or connector screws within ...

Page 6: ...t to the rotating fan Doing so may result in injury or failure of the fan module After the first use of the product do not connect disconnect the power supply module or fan module to from the main module more than 50 times Exceeding the limit may cause malfunction After the first use of the product do not insert remove a CFast card to from the product more than 10000 times Exceeding the limit may ...

Page 7: ...shutdown of the product Then supply input power again CAUTION When transporting lithium batteries follow the transportation regulations For details on regulated models refer to the MELIPC MI5000 Series User s Manual Startup CAUTION When disposing of this product treat it as industrial waste When disposing of batteries separate them from other waste according to the local regulations For details on...

Page 8: ...the PRODUCT in Nuclear Power Plants and any other power plants operated by Power companies and or any other cases in which the public could be affected if any problem or fault occurs in the PRODUCT Railway companies or Public service purposes and or any other cases in which establishment of a special quality assurance system is required by the Purchaser or End User Aircraft or Aerospace Medical ap...

Page 9: ...ng manual or consult Microsoft Corporation Contact information is available on the following website Microsoft Corporation support microsoft com en us contactus For the Wind River Systems product This product is loaded with VxWorks manufactured by Wind River Systems Inc as a real time operating system Mitsubishi Electric accepts no responsibility for dealing with or damage from problems caused by ...

Page 10: ... functions and parameter settings of the product Before using this product please read this manual and the relevant manuals carefully and develop familiarity with the functions and performance to handle the product correctly Please make sure that the end users read this manual Relevant product MI5122 VW ...

Page 11: ...g adjustment timing 28 Operation during daylight saving time 28 2 4 Clock Data Synchronization Setting Function 29 2 5 Time Setting Function SNTP Client 30 CHAPTER 3 PROGRAMMABLE CONTROLLER DEVICE MEMORY FUNCTION 33 CHAPTER 4 SLMP FUNCTION 36 4 1 SLMP Server Functions 36 Connection method 36 Supported commands 37 Available devices 38 Error codes at communication 38 CHAPTER 5 iQSS FUNCTION 39 CHAPT...

Page 12: ...lay time 94 CHAPTER 8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 95 8 1 Self Diagnostics Function 95 Self diagnosis locations 95 Self diagnostics timing 95 Checking errors 95 Operation upon error occurring 96 Operation upon error detection setting 96 8 2 Watchdog Timer WDT Function 98 Monitoring time setting 98 Monitoring start and reset 99 Operation during a timeout of the watchdog timer 99 8 3 Operati...

Page 13: ...ent information 135 11 2 Service Setting Function 140 11 3 IP Filter Function 141 CHAPTER 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 145 12 1 Connection Method 145 CHAPTER 13 SYSTEM COUNT FUNCTION 147 CHAPTER 14 TIMER EVENT FUNCTION 149 PART 3 COMMON FUNCTIONS CHAPTER 15 OS LINKING FUNCTIONS 152 15 1 Virtual Ethernet Function 152 15 2 Shared Memory Access Function 153 15 3 Inter OS Event Notif...

Page 14: ...k scan time 214 Slow access to the product 214 Master station cyclic transmission is stopped 214 The date and time of the Windows part and VxWorks part are different 214 The Time setting SNTP client function is not running normally 215 A Windows part forced restart cannot be run 215 Windows part forced restart is not complete 215 Shutdown of this product is not complete 215 An error occurs because...

Page 15: ...r code types 221 Watchdog timer error occurrence in the Windows part 221 List of error codes 222 Appendix 3 Event List 253 VxWorks part 253 CC Link IE Field Network 254 Appendix 4 Device List 256 Appendix 5 List of Special Relays 257 Appendix 6 List of Special Registers 258 Appendix 7 List of Link Special Relays 264 Appendix 8 List of Link Special Registers 271 Appendix 9 List of Buffer Memory 282...

Page 16: ...ns and parameters of a MELIPC Print book e Manual PDF MELIPC MI5000 Series User s Manual Startup SH 081930ENG Explains the performance specifications procedures before operation and troubleshooting of a MELIPC Print book e Manual PDF MELIPC MI5000 Series Programming Manual Windows SH 081934ENG Explains the programming specifications and dedicated function libraries of the Windows part of a MELIPC ...

Page 17: ...xchange data between stations on a network Slave station Generic term for local stations remote I O stations remote device stations and intelligent device stations Data link Generic term for cyclic transmission and transient transmission Transient transmission Function that carries out communications with other stations at a request from the product Fan module An abbreviation for a fan module for ...

Page 18: ...16 MEMO ...

Page 19: ...17 PART 1 PART 1 FUNCTIONS FOR Windows PART This part explains the functions for the Windows part 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS ...

Page 20: ...g page Page 98 Watchdog Timer WDT Function 1 Time up errors may be detected from hang ups of the user application Monitoring time setting This section shows the method for setting a watchdog timer monitoring time System watchdog timer A system watchdog timer can be set in System WDT Setting of WDT Watchdog Timer Setting Windows part Window Basic Parameter RAS Setting WDT Watchdog Timer Setting Win...

Page 21: ...rror a watchdog timer error to the effect that a time in excess of that set in watchdog timer monitoring settings has elapsed The following table lists the LED display and operation statuses that change due to a timeout of the watchdog timer LED display and operation statuses other than those listed do not change due to a timeout Function name Description Windows part System watchdog timer The sys...

Page 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...

Page 23: ...R DEVICE MEMORY FUNCTION 4 SLMP FUNCTION 5 iQSS FUNCTION 6 CC Link IE Field Network FUNCTION 7 CC Link IE Field Network Basic FUNCTION 8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 9 Telnet FUNCTION 10 NETWORK FILE ACCESS FUNCTIONS 11 SECURITY FUNCTION 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 13 SYSTEM COUNT FUNCTION 14 TIMER EVENT FUNCTION ...

Page 24: ...is configured by the C Controller module dedicated function CCPU_SetRTC Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual VxWorks SNTP Server Acquires and applies time information from an SNTP server constructed externally Page 30 Time Setting Function SNTP Client When the clock data is changed the followi...

Page 25: ...ure the clock data by a user application If another function is used the correct clock data may not be configured Clock date and time zone The clock data range is the range when the time zone is UTC When clock data will be changed from MI Configurator or another tool consider the time zone setting and then set a value within the range Operation during momentary power failure The clock RTC managed ...

Page 26: ...will be applied after the power supply of this product is turned OFF to ON or this product is reset Window Basic Parameter Operation Related Setting Clock Related Setting Clock Simple Settings Clock Settings Displayed items Item Description Setting range Time zone hour Configures the hour of the time zone UTC 14 UTC 13 UTC 12 UTC 11 UTC 10 UTC 9 UTC 8 UTC 7 UTC 6 UTC 5 UTC 4 UTC 3 UTC 2 UTC 1 UTC ...

Page 27: ...he time zone settings of the Windows part If the settings of the VxWorks part and Windows part do not match time data such as error and event occurrence times may not match The time zone of the Windows part is configured by Date and time Windows Start Windows System Tools Control Panel Clock Language and Region Date and Time If the time zone is changed the start time and end time of daylight savin...

Page 28: ... and ends at 2 00 on the first Sunday in November 2 Daylight saving time settings Daylight saving time is configured by Adjust clock for daylight saving time settings of Clock Settings The same month cannot be specified for the start and end of daylight saving time February 29 cannot be specified directly This can be specified by selecting the last day of February Window Basic Parameter Operation ...

Page 29: ...arch Week Last week first to fourth week Default Second week Day of week Sunday to Saturday Default Sunday Time 0 00 to 23 00 Default 2 00 End Month Set the daylight saving time end date 1 to 12 Default November Week Last week first to fourth week Default 1st week Day of week Sunday to Saturday Default Sunday Time 0 00 to 23 00 Default 2 00 Specified date Start Month Set the daylight saving time s...

Page 30: ... time When daylight saving time setting is enabled operation occurs using the date and time information after the correction for daylight saving time As a result dates and times output by functions that use clock data switch from before correction to after correction and sorting in order of occurrence number and date and time of occurrence may not match Consequently when checking output results in...

Page 31: ...ock managed by the VxWorks part run independently Therefore if one clock is changed the other clock is not synchronized If necessary configure the clock data of both clocks managed by the Windows part and VxWorks part Synchronization timing When Use was configured for Clock data synchronization clock data is synchronized at the following times Synchronization cycle When the power supply of this pr...

Page 32: ...of the VxWorks part of this product A time inquiry message is sent to the SNTP server The time acquired from the SNTP server is configured to the clock managed by the VxWorks part of this product The time information acquired from the SNTP server is Coordinated Universal Time UTC The time configured to the VxWorks part is the time after correction of the acquired time information to match the time...

Page 33: ...supply is turned ON or a reset Disable Enable Default Disable Execution Timing Set the execution timing of the time setting Fixed Time Time Intervals Default Fixed Time Time Intervals When Specified Time Intervals is selected set the time interval minute for the time setting 1 to 1440 minutes Default 1 minute Specified Time Hour Minute Day of Week Specificatio n of time Hour Minute When Fixed Time...

Page 34: ...ation timeout results when there is no response from the SNTP server within 20 seconds from the time inquiry When a communication timeout occurs there is no error but the event of the timeout occurrence is saved to the event history Page 253 Event List SNTP Server An SNTP server is necessary on the network connecting this product Delay by communication time The time to be set may be delayed by the...

Page 35: ...st Access to devices Device values can be changed and current values can be checked on the devices of this product by using one of the following methods Buffer memory access devices of this product can be accessed by specifying the CPU buffer memory access device Access using CPU No 1 U3E0 as the I O number of the CPU module and CPU buffer memory Gn as the area of the CPU buffer memory MI Configur...

Page 36: ...tes data by specifying a device type and a range to be written mdSendEx Writes data to devices in a batch Writing data to device During interrupt CCPU_ResetDevice_ISR Resets internal user devices and internal system devices bit devices of a MELIPC CCPU_SetDevice_ISR Sets internal user devices and internal system devices bit devices of a MELIPC CCPU_ToBuf_ISR Writes data to the buffer memory of a M...

Page 37: ...line MELIPC memory operation Clearing of values Precautions Clear device values when the operating status of this product is STOP If the status is RUN an error occurs If the power supply of this product is turned OFF to ON or the product is reset while the file register is being cleared the clearing of the file register may not be completed normally Clear the file register again Item Description C...

Page 38: ...e device communicate via Ethernet using the Ethernet port CH1 Windows part communicate using virtual Ethernet Page 152 Virtual Ethernet Function Precautions This product does not support the relay function SLMP requests cannot be relayed to other stations via the CC Link IE Field Network Data Exchange Frame Data Code The following table shows the data exchange frames and data codes compatible with...

Page 39: ...rs can be specified Writes values to word devices in 1 word units or 2 word units by specifying device number Nonconsecutive device numbers can be specified Read Block 0406 00 0 00 2 Reads data by specifying multiple blocks as regarding one block as n point of word devices or bit devices 1 point is 16 bit Nonconsecutive device numbers can be specified Write Block 1406 00 0 00 2 Writes data by spec...

Page 40: ...st 3 To use buffer memory devices it is necessary to specify subcommands and extension specifications 03E0H in addition to device codes For details refer to the following manual SLMP Reference Manual Error codes at communication For error codes stored in exit codes of response messages refer to the following 4000H to 4FFFH Page 220 List of Error Codes C000H to CFFFH Manual of network module to be ...

Page 41: ...ic detection of connected devices Uses an engineering tool to automatically generate a Device configuration diagram of iQSS compatible devices connected to this product iQ Sensor Solution Reference Manual Reflection of the communication setting Reflect communication settings such as an IP address to an iQSS supported device connected with Ethernet on the Device map area Sensor parameter read write...

Page 42: ...40 5 iQSS FUNCTION MEMO ...

Page 43: ... device assignment If master station and slave station with exception of local stations This can communicate 1 1 between master stations and slave stations The input status from slave station external devices is stored in the master station link device RX RWr in the master station link device status RY RWw is output to the slave station external device The order of slave stations is the same as th...

Page 44: ...d in the master station link device RX RWr using link scan The master station link device RX RWr status is read by a user program At output from master station The master station link device RY RWw status is changed by a user program The master station link device RY RWw status is stored in the slave station link device RY RWw using link scan The slave station link device RY RWw status is output t...

Page 45: ... own station transmission range The local station link device RY RWw status is stored in the master station link device RX RWr using link scan The master station link device RX RWr status is read by a user program At output from master station The master station link device RY RWw status is changed by a user program The master station link device RY RWw status is stored in the local station link d...

Page 46: ... link devices The link scan time can be set for Synchronous Communication Settings under Required Settings Page 193 Required settings if master station is selected by station type Shorten the link scan time by reducing the numbers of slave stations or total assigned point numbers of link devices At this time the total assigned point numbers of link devices will be the number of points from the lin...

Page 47: ...ed during the assignment of link devices and there is an empty range in the network range assignment do not change the values of link devices in the empty range If the values of link devices in the empty range are changed local stations and other systems may malfunction When accessing link devices access devices in the assigned range of the network range Objective Function name Description Writing...

Page 48: ...tation are link devices RX RY RWr RWw Setting method The block data assurance per station can be set for Supplementary Cyclic Settings in the master station Page 187 CC Link IE Field Network Parameters List Setting these in the master station guarantees that data for all stations is managed by station unit 1 Master station 2 Slave station 3 Cyclic transmission 4 Data guarantee 1 2 RWr RY RX RWw RY...

Page 49: ...tation RX RWr and the output status RY RWw from own station to other stations Read write the link device CCPU_ReadLinkDevice CCPU_WriteLinkDevice Read data Update is stopped of the link device input status for own station RX RWr so the read data is assured Write data Update of the link device input status from own station RY RWw to other stations is stopped so the read data is not sent to slave st...

Page 50: ...d RWr are maintained Output status of cyclic data when a stop error occurred on this product RY is cleared RWw is maintained Area for which data is cleared when a stop error occurs with this product Area for which data is saved Area dependent on configuration at slave station 1 Station No 0 master station 2 Station No 1 slave station excluding local station 3 Station No 2 Local station 4 Station N...

Page 51: ...n link devices and output statuses of a MELIPC retain or clear Cyclic transmission stop restart Cyclic transmission can be stopped stopping of data receiving from slave stations and data sending from own station during debugging and other situations Furthermore stopped cyclic transmission can be restarted Transient transmission does not stop Stop and restart of cyclic transmission is carried out i...

Page 52: ...eatedly called each time a link scan is completed When NULL is specified to a routine to be registered the routine is deregistered During CC Link IE Field Network synchronous communication Registered routines are called at the following timing during CC Link IE Field Network synchronous communications Function list For details on the C Controller module dedicated functions refer to the following m...

Page 53: ...tiple CPU system on another station by transient transmission setting a logical number is required Logical station number is a logical station number that can be used in a user program Specify a logical station number in MI Configurator or a user program For the specification method in MI Configurator refer to the following section Page 191 Access target settings For the specification method in a ...

Page 54: ... or 4 ms and the set value can be confirmed in the link special register synchronous communication cycle settings value SW01EA to SW01EB Manual setting To set a synchronization cycle manually select Manual setting in Synchronization Cycle Setting Method Slave station network synchronization communication settings To synchronize a slave station with the master station browse to Network Configuratio...

Page 55: ...g CC Link IE Field Network diagnosis Diagnosable Usable with restrictions Not diagnosable Item Connection destination of MI Configurator Restricted items Reference master station local station 1 Network configuration diagram error status display Page 60 Network configuration diagram Cable disconnection disconnected station display 2 Selected station status and fault details display If the module d...

Page 56: ...ved stations is possible Page 67 Reserved station temporary clear remove Temporary error disabled station settings remove If connected to a local station then only display of temporary error disabled stations is possible Page 69 Temporary error disabled station settings remove Item Connection destination of MI Configurator Restricted items Reference master station local station ...

Page 57: ...des of the Error icon For a ring connection when the CC Link IE Field Network Parameters Basic Settings Network topology settings are set to Line connection star connection and star connection line connection mixed the Faulty station illegal ring connection detected loopback executed icon is displayed If a loopback is executed because an error has occurred such as a cable disconnection then the Er...

Page 58: ...f the selected station will be displayed above the Selected station communication status monitor During an error a button such as PORT2 cable disconnection is displayed on the Selected station communication status monitor Click this button to confirm the details and solution for the error 4 From Operating test and Information confirmation setting at the bottom right of the window carry out various...

Page 59: ...sis screen do not match update the network configuration diagram so that it matches Updating the network configuration diagram reconnects all stations on the network which results in a momentary data link error for all stations and output may be OFF for connected slave stations Configure so that output is maintained if necessary Legend button Indicates the legend for icons displayed in CC Link IE ...

Page 60: ...hey have been data linked once disconnected stations such as those below will be displayed Stations that have had network reconnection processing as a result of the cable being removed and then reinserted or OFF to ON or that are disconnected after reconnection has completed Disconnected stations that have been removed from the network configuration by clicking the Update button Other Modules icon...

Page 61: ...ove an Ethernet cable from one of the stations on the network One of P1 or P2 The network topology becomes line connection and data link starts Corrective action 1 Check whether Network Topology under Basic Settings is different from the configuration of the network If it is different set Ring connection for Network Topology of Basic Settings and then write to the CPU module again When data link s...

Page 62: ...f the background color 3 The module status is displayed Use the Legend button to confirm details of icons If the Error Illegal ring connection detected Execute loopback icon is displayed handle as shown in Error details Troubleshooting 4 Displays the PORT to which the Ethernet cable is connected system configuration Displays network configuration diagram Star connection 1 Master station Station No...

Page 63: ...tation Station No 4 7 Remote device station Station No 5 system configuration Displays network configuration diagram Two stations connected to a switching hub 1 Master station Station No 0 2 Switching hub 3 Local station Station No 1 Branching is not displayed in the network configuration diagram Switching hub connected in cascade 1 Master station Station No 0 2 Switching hub 3 Intelligent device ...

Page 64: ...n to confirm details of the error Handle in accordance with the displayed Fault cause and Troubleshooting 5 Displays the module LED status as well as the P1 and P2 communication status will be displayed 6 Displays the cable status No Description 1 Set the station No to a slave station that does not have a number set In Network status this is only displayed if slave stations that fulfill all of the...

Page 65: ...the CC Link IE Field diagnoses window click the Communications test button 2 Input Communications destination settings and Communications data settings 3 Click the Execute test button If an error occurs then handle in accordance with the error message Precautions If a relay transmission station is set in Communications destination settings an error message is not displayed only the error code is d...

Page 66: ...tire network by the network configuration diagram of the CC Link IE Field diagnosis or the selected station communication status monitor Page 60 Network configuration diagram Page 62 Selected station communication status monitor Window Execution procedure 1 In the CC Link IE Field diagnoses window click the Cable test button 2 Input the station No for which to carry out a cable test then click the...

Page 67: ...tion during debugging and other situations Furthermore restart stopped cyclic transmission In link start stop transient transmission does not stop Cyclic transmission start and stop is possible even in Link special relay SB and Link special register SW 1 Master station 2 Slave station 1 3 Slave station 2 4 Slave station 3 RX RWr RX RWr RX RWr RY RWw RY RWw RY RWw RX RWr RY RWw 1 2 2 3 3 4 4 2 3 4 ...

Page 68: ...SW 4 Click the Execute button If the product has been reset or the power turned OFF to ON Even if cyclic transmission has been stopped through Link stop if the product is reset or power turned OFF ON then cyclic transmission will restart If link stopped to error disabled stations or temporary error disabled stations Be aware that stations that stopped a link are displayed as data linking in the CC...

Page 69: ...lear Remove reserved station temporary remove 1 Connect slave stations specified as reserved stations to the network 2 On the CC Link IE Field diagnoses window Network status select the icon for the station for which to temporarily clear reserved station status 3 Right click the selected icon and select Selected station reserved station temporary delete The text background color becomes orange and...

Page 70: ...onnect the disconnected station 2 Carry out reserve station temporary clear settings and remove temporary clear for the station to remove Confirm the station No set in the reserved station Confirm the station No set in the reserved station in the Reserved Station Function Enable window 1 Connect slave stations specified as reserved stations to the network 2 In the CC Link IE Field Diagnostics wind...

Page 71: ... module in Network status and carry out Temporary error disabled station settings Temporary error disabled station settings remove 1 On the CC Link IE Field diagnoses window Network status select the icon for the station for which to temporarily set error invalid station status 2 Right click the selected icon and select Selected station temporary error invalid station settings The text background ...

Page 72: ...e Enable Disable Ignore Station Errors button 2 In the Error disabled station list click the station to be set temporarily as an error disabled station If clicked the station display changes to red letters on a yellow background Only stations that are not set temporarily as an error disabled stations can be selected Stations that are not set temporarily as an error disabled stations are displayed ...

Page 73: ...is removed from the network Resetting the master station product or turning the power OFF results in the following differences between the master station and local station ERR LED status Temporary error disabled station settings status SW00E0 to SW00E7 If a difference occurs return to normal status as in the procedure below 1 Reconnect the disconnected station 2 Carry out reserve station temporary...

Page 74: ... Time The CC Link IE Field Network processing time comprises the following items Link scan time slave station response processing time transmission delay time 1 Master station 2 Slave station 3 Link device 4 Link scan time 5 Slave station response processing time 3 1 4 2 3 5 ...

Page 75: ...device station until data is stored in the link device of the master station CT Synchronous communication cycle Rio Processing time of intelligent device station remote device station Manual of intelligent device station remote device station being used Master station RY RWw intelligent device station remote device station output Times are shown below The time from when the link device of the mast...

Page 76: ...to Local station RX The following table shows the time from the link device of the master station turning ON or OFF until the device of the CPU module of the local station is turned ON or OFF CT Synchronous communication cycle SL Sequence scan time of local station Calculated value Transmission delay time no block data assurance per station setting Normal value CT 1 SL 1 Maximum value CT 2 SL 1 Ca...

Page 77: ... RWr The following table shows the time from when data was configured to the link device of the master station until data was stored to the device of the CPU module of the local station CT Synchronous communication cycle SL Sequence scan time of local station Calculated value Transmission delay time no block data assurance per station setting Normal value CT 1 SL 1 Maximum value CT 2 SL 1 Calculat...

Page 78: ...n link device RX RWr status is output to external devices The slave station link device RX RWr status is stored in the master station link device RX RWr using link scan The status of the link device RX RWr of the master station is stored to a device of the master station by a link refresh At output from master station The status of the device of the master station is stored to the link device RY R...

Page 79: ...o the time required for a link scan Page 83 Link scan operation The master station sends requests to slave station 1 slave station 2 Slave station 1 returns a response to the master station Slave station 2 returns a response to the master station After the configured link scan time elapses the master station starts sending another request When the master station sends a request when a cyclic trans...

Page 80: ...o it waits for a response from slave station 2 until the timeout period 500 ms has passed and then sends a request to slave station 1 slave station 2 However because there is no response from slave station 2 the link scan time is extended until the timeout period 500 ms The master station is unable to receive a response from the slave station 2 within the disconnect detection count 3 times therefo...

Page 81: ...e from a slave station The master station immediately disconnects that slave station regardless of the timeout period and disconnection detection count set in link scan settings The corresponding slave station generates a data link error The error code will be generated by the slave station The following table shows the operations of special relays and special registers when a slave station is dis...

Page 82: ...to 0 by turning the power supply OFF to ON or resetting depending on the timing of link scan and link refresh the latched data is output without being cleared to 0 To prevent the output of file register data of this product being latched perform the following operation Operation during refresh During output from a master station this product The programmable controller device user device file regi...

Page 83: ...ard response times reduces the effect of differences of the standard response times of slave stations For the standard response times check the manual of the slaves station to be used Because link scan times differ by group slave stations with the longest standard response time of the groups are affected Page 77 Cyclic transmission data flow Merging slave stations into one group To perform operati...

Page 84: ...g to the response processing time of each group Page 83 Link scan time settings The master station sends requests to the slave station 1 and slave station 2 that belong to group 1 The slave station 1 returns a response to the master station The slave station 2 returns a response to the master station After the link scan time set to the group 1 is elapsed the master station starts sending another r...

Page 85: ...ter completion of a link scan the next link scan starts immediately When the link scan setting is enabled After completion of a link scan link scan is stopped until the configured link scan time passes The next link scan is started after the configured link scan time passes Link scan time check Link scan time maximum minimum and current values can be confirmed using the following method 1 1 The ma...

Page 86: ...al VxWorks Objective Function name Description Writing data to device CCPU_WriteDevice Writes data to internal user devices and internal system devices of a MELIPC mdDevRstEx Resets bit devices mdDevSetEx Sets bit devices mdRandWEx Writes data by specifying a device type and a range to be written mdSendEx Writes data to devices in a batch Writing data to device During interrupt CCPU_WriteDevice_IS...

Page 87: ... the link device input status for own station RX RWr and the output status RY RWw from own station to other stations Read write the link device Read data Update is stopped of the link device input status for own station RX RWr so the read data is assured Write data Update of the link device input status from own station RY RWw to other stations is stopped so the read data is not sent to slave stat...

Page 88: ...e dedicated function CCPU_EntryCCIEFBLinkScanEndFunc to register routines After registration the registered routine is repeatedly called each time a link scan is completed When NULL is specified to a routine to be registered the routine is deregistered Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual VxWo...

Page 89: ... abnormal station input status RX is cleared Data from before RWr generates an error is saved Output status of cyclic data when a stop error occurred on this product RY and RWw are maintained Area for which input from faulty station is cleared Area for which clear save are different from this product Area for which data is saved Area dependent on slave station settings 1 Master station 2 Slave sta...

Page 90: ...us when this product is STOP can be set in Output status settings when MELIPC is stopped of CC Link IEF Basic Setting Page 162 BASIC PARAMETERS Link device output status The following table shows the relationship between link devices and output statuses of a MELIPC retain or clear Link device Output retention clear settings at MELIPC STOP When retention is configured When clearing is configured RY...

Page 91: ...n the network Reserved stations do not become faulty stations even if they are not actually connected Setting method In network configuration settings specify the slave station as a reserved station Page 177 Network Configuration Settings Reserve station settings such as occupied station number and IP address can also be input 1 Master station 2 Slave station 1 3 Slave station 2 4 Slave station 3 ...

Page 92: ...Field Network Basic diagnostics 7 3 CC Link IE Field Network Basic diagnostics Perform troubleshooting by performing the CC Link IE Field Network Basic diagnostics and checking the network status and error details Window Diagnostics CC Link IEF Basic Diagnostics ...

Page 93: ...nfirmed stations Error Stns station at which an error is occurring Unfixed Stns station with an unconfirmed transmission status not including reserved stations Diagnostics Target Group Select a group displayed in the list of diagnosis information Station No Displays the station No of the slave station Occpd Stns Displays the exclusive station number set in parameters Reserved Station Displays the ...

Page 94: ...the station number with the diagnoses information you wish to acquire to Diagnosis request information U3E0 G4635 2 Turning Diagnosis information display request U3E0 G4634 0 from OFF to ON will store diagnosis information in Diagnosis information 1 U3E0 G4637 to U3E0 G4648 and Diagnosis information 2 U3E0 G4652 to U3E0 G4661 If diagnosis information is stored then Diagnosis information display re...

Page 95: ... to a link scan time that is set in Link Scan Time Settings of CC Link IEF Basic Setting Page 162 Basic Parameter List Link scan time check Link scan time maximum minimum and current values can be confirmed using the following method CC Link IE Field Network Basic diagnosis Page 90 CC Link IE Field Network Basic diagnostics Buffer Memory Page 282 List of Buffer Memory 1 Master station 2 Slave stat...

Page 96: ...r input transmission delay time Input transmission delay time max Ls 2 SS ms Output transmission delay time The output transmission delay time shows the following The time from master station device turning ON or OFF until the slave station output RY turns ON or OFF The time from setting data in the master station device until the data is output to the slave station RWw Calculation method for outp...

Page 97: ...To separate the processing of a user program by operating status use the C Controller module dedicated function CCPU_GetCpuStatus MELIPC MI5000 Series Programming Manual VxWorks Checking errors The error conditions for the overall system and errors being currently generated can be checked in the MELIPC diagnostics window MI Configurator Operating Manual Information of errors that occurred are also...

Page 98: ...tarted automatically is saved in the event history For details on the internal configuration of this product Windows part and VxWorks part refer to the following manual MELIPC MI5000 Series User s Manual Startup Precautions Automatic restart at a Windows system error If Windows automatic restart is enabled and Restart is selected for when the Windows part stops this product may restart repeatedly ...

Page 99: ... during continuation errors using LED Display Settings of RAS Setting Window Basic Parameter RAS Setting LED Display Setting Displayed items Item Description Setting range MAIN ERR LED Minor error Continue error Set MAIN ERR LED to Display or Do not display when a minor error continuation error is detected Display Do not display Default Display ...

Page 100: ... the user watchdog timer by using the C Controller module dedicated function CCPU_StartWDT Set a monitoring time for the user watchdog timer within the range of 100 to 10 000 ms in 10 ms units The user watchdog timer does not run if it is not configured by the C Controller module dedicated function CCPU_StartWDT Function list For details on the C Controller module dedicated functions refer to the ...

Page 101: ...ed when a timeout occurred Page 100 Registration of routines Function name Description VxWorks part System watchdog timer The system automatically starts monitoring and resets using periodic processing The system can acquire the actual measured value of the time interval to reset the system watchdog timer Page 99 Reset interval of system watchdog timer If system processing has been suspended for a...

Page 102: ...tered routine of the C Controller module dedicated function CCPU_EntryWDTInt executed most recently is enabled The registered routine is executed as an interrupt service routine ISR Set the routine to be registered to minimize the routine processing and keep the processing time as a short as possible Precautions The registered routine is not executed while the operating system is in the interrupt ...

Page 103: ...a system watchdog timer error is occurring Operating status of Windows part 1 Displays the operating status of the Windows part Windows part preparing Status when the Windows part is starting while this product is turning ON or resetting or Windows is restarting Windows part running Status when the Windows part starts and is operating normally Windows part shutting down Status when the Windows shu...

Page 104: ...rogram processing depending on the operating status of the VxWorks part use the C Controller module dedicated function CCPU_GetCpuStatus MELIPC MI5000 Series Programming Manual VxWorks Change of the operating status Use one of the following methods to change the operating status Switch operations Use the STOP MAIN RUN switch MELIPC MI5000 Series User s Manual Startup remote operation Use a remote ...

Page 105: ... diagnosis Diagnostics MELIPC Diagnostics C Controller module dedicated function Use the C Controller module dedicated function CCPU_ClearError This section shows the procedure to clear errors by a user program 1 Execute the C Controller module dedicated function CCPU_GetErrInfo Acquire information of errors that occurred on this product 2 Clear the cause of continuation errors detected by this pr...

Page 106: ... that access the user drive cannot be used To access the user drive try again after turning the power supply of this product OFF to ON or resetting the product Remote operation function This function operates this product through MI Configurator or external devices using SLMP The following table shows the remote operations When using remote operations via a network use service setting functions IP...

Page 107: ...ch status is STOP Set the STOP MAIN RUN switch status to RUN STOP timing This product enters the STOP status when a remote STOP was executed by MI Configurator To change the remote STOP state to RUN again Change the operating status by using remote RUN User actions during a remote STOP Data processing of a user program continues even when the operating status of this product is remote STOP To sepa...

Page 108: ...ameter Operation Related Setting Remote operation settings Considerations before executing a remote RESET Set the operating status of this product to the STOP status Before a remote RESET close or exit user applications of the Windows part and VxWorks part If a remote RESET is performed during operation of a user program the user program or files may be corrupted Considerations after executing a r...

Page 109: ...IC AND MAINTENANCE FUNCTIONS 8 3 Operating Status Management Function 107 8 Windows part forced restart For details on Windows part forced restarts refer to the following page Page 122 Windows part forced restart ...

Page 110: ...ntary power failure time is detected This product enters the same state as when the following operations are performed Turning the power OFF and ON or resetting the product MELIPC MI5000 Series User s Manual Startup Resetting the product by the MELIPC RESET WIN RESET switch MELIPC MI5000 Series User s Manual Startup Resetting the product by a remote operation of MI Configurator Page 104 Remote ope...

Page 111: ... module filter cleaning notification is saved to the event history Page 253 Event List The FAN LED turns ON 1 MELIPC MI5000 Series User s Manual Startup 1 When this function turns on the FAN LED the FAN LED does not turn off even when the power supply of this product is turned OFF to ON or the product is reset Start this product in off line mode and then execute Alert reset After executing Alert r...

Page 112: ...nd sysClkRateSet is used to change the system clock rate of VxWorks the operation of the VxWorks part will be unstable Timing of system clock rate changes Changes of the system clock rate are enabled after a restart of the VxWorks part of this product To change the system clock rate always turn the power supply of this product OFF and ON or reset this product System clock rate during operation The...

Page 113: ...on initiator information is saved for troubleshooting when the event history is saved For details on events to save refer to the following Page 253 Event List Save capacity settings Configure the save capacity for event history files using Event History Setting of RAS Setting Window Basic Parameter RAS Setting Event History Setting Displayed items Saving using the C Controller module dedicated fun...

Page 114: ...t be able to collect event history under the following statuses Major error Cable failure Creation timing Event history files are created at the following times When the power of this product is turned OFF and ON or after a reset of this product when no event history file exists after a change of event history settings initialization At registration of event history no event history file exists Wh...

Page 115: ...t History Clearing the event history Use the Event History window Clear All button to delete all event history stored on the product If event history is cleared then an event indicating that the event history was cleared will be saved Precautions If the event history is being accessed from another instance of MI Configurator or similar or if the event history file cannot be accessed then clearing ...

Page 116: ... function CCPU_GetSwitchStatus Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual VxWorks Switch operation notification function This function issues an event notification stating that a switch was operated when a switch of this product was operated Event notifications of switch operations are received by u...

Page 117: ...tatus CCPU_SetLEDStatus_ISR CCPU_SetDotMatrixLED CCPU_SetDotMatrixLED_ISR Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual VxWorks LED name Operation applicability MAIN LED VX RDY LED WIN RDY LED MAIN ERR LED MAIN RUN LED STORAGE LED FAN LED INFO LED RS SD RD LED BATTERY LED Dot matrix LED Function name D...

Page 118: ...tus CCPU_GetDotMatrixLED CCPU_GetDotMatrixLED_ISR Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual VxWorks LED name Acquisition applicability MAIN LED VX RDY LED WIN RDY LED MAIN ERR LED MAIN RUN LED STORAGE LED FAN LED INFO LED RS SD RD LED BATTERY LED CC Link IE Field Network LED RUN LED ERR LED MST LED...

Page 119: ...onnection settings are not configured or the connection device is not supported is displayed External device Communications method The external device configured by the external device configuration is displayed If the connection device is not supported is displayed External device IP address The IP address of the connected device is displayed If the connection status is Disconnection settings are...

Page 120: ...SNTP server is connected to the Ethernet port CH1 To check the status of a connection with a device not covered by the external device configuration diagnostics use a command netstat ping etc to check the network status of VxWorks Precautions It is not necessary to configure the external device configuration for the connection of MI Configurator installed in the Windows part As a result it is not ...

Page 121: ... for when the Windows part stops this product may restart repeatedly If Restart is selected disable Windows automatic restart Windows Start Windows System Tools Control Panel System and Security System Advanced system settings Advanced Startup and Recovery Settings System failure Automatically restart Advance processing registration of Windows part forced restart Even when registered in advance wi...

Page 122: ... following manual MELIPC MI5000 Series Programming Manual VxWorks Operations during shutdown The Windows part and VxWorks part enter the following statuses during a shutdown Advance processing during shutdown VxWorks part processing that was registered by the user in advance can be executed before this product is shut down Advance processing is registered using the C Controller module dedicated fu...

Page 123: ...f the MELIPC shutdown function is run when the Windows part is running the WIN RDY LED may continue to flash and the MELIPC shutdown function may not be run If the WIN RDY LED continues to flash for a long time connect a display to this product and then check whether the Windows part is running If necessary either run the MELIPC shutdown function again or shut down Windows from the Windows Start m...

Page 124: ...r this product resets Operation during major errors and system watchdog timer errors If a major error or system watchdog timer error is occurring on this product requests of the individual reset function are not executed normally Execute this function after switching the power supply of this product OFF to ON or resetting the product to clear errors on this product Windows part forced restart Forc...

Page 125: ... flashes as the Windows part resets 3 Confirm that the WIN RDY LED is on remote operation Use a remote operation of MI Configurator Online Remote operation WIN RESET A WIN RESET cannot be run when a remote operation was performed by MI Configurator that is installed in the Windows part of this product C controller module dedicated function Execute the C Controller module dedicated function CCPU_Wi...

Page 126: ... function is not in the same status as when the power supply of this product is turned OFF and ON To clear the shared memory turn the power supply of this product OFF and ON or reset this product When user programs of the VxWorks part and Windows part are linked When user programs of the Windows part and VxWorks part are linked using virtual Ethernet or shared memory user applications of the VxWor...

Page 127: ...MI Configurator Online MELIPC memory operation Precautions Set the operating status of this product to STOP before initializing the user drive If the status is RUN an error occurs If the power supply of this product is turned OFF to ON or the product is reset during user drive initialization user drive initialization may not be completed normally Initialize the user drive again Data backup The fol...

Page 128: ...indow Basic Parameter External Device Connection Applicable Settings Telnet Server Setting Displayed items Accessing the Telnet server A login name username and password are used when using the Telnet function of the VxWorks part When the user authentication function is used enter the username and password registered for the user management information Page 135 User Authentication Function When th...

Page 129: ...Number of retries The following section shows the procedure to change the timeout time of a Telnet connection TCP while this product is in operation 1 Make a Telnet connection with this product using a Telnet tool 2 Use the shell command of the Telnet tool to execute a change command for the timeout time to start the Telnet server 3 Close the Telnet connection 4 Make a Telnet connection with this ...

Page 130: ... is executed without an argument the resource reserved by the system of the VxWorks part is closed so do not execute the command close without an argument specification Furthermore when for example a command to show the status show is executed an interrupt disabled state occurs for a long time Processing to be called from the interrupt routine is not executed and interrupts that occur at a fixed i...

Page 131: ...ayed items Precautions Operation while accessing file During file access do not perform the following operations Otherwise files may be corrupted When the power supply of this product is turned OFF or this product is reset Reconnection after timeout If a timeout error occurs during file transmission the TCP connection will be closed disconnected Log into this product again before restarting file t...

Page 132: ...t refer to the following manual MELIPC MI5000 Series User s Manual Startup File folder name Do not copy files folders that include characters that cannot be used by the VxWorks part to a shared folder of the VxWorks part After copying the following phenomena may occur Error Garbled file folder name 1 Loss of file folder 1 Even when a file folder name is garbled the file folder name before garbling...

Page 133: ...d easily using Explorer of the Windows part File sharing server settings Configure the file sharing server using File Sharing Server of File Sharing Server Setting Window Basic Parameter External Device Connection Applicable Settings File Sharing Server Setting Displayed items 1 If Use is set the user drive ROM and system drive SYSTEMROM are available publicly A External device personal computer e...

Page 134: ...e 192 168 3 3 If the IP address of the Ethernet port CH1 has been changed enter the IP address after the change Page 162 BASIC PARAMETERS 3 Enter the username and password Shared folders of the VxWorks part appear and files can be accessed When the user authentication function is used enter the username and password registered for the user management information Page 135 User Authentication Functi...

Page 135: ...refer to the following manual MELIPC MI5000 Series User s Manual Startup File folder name Do not copy files folders that include characters that cannot be used by the VxWorks part to a shared folder of the VxWorks part After copying the following phenomena may occur Error Garbled file folder name Loss of file folder For details on characters that can be used by the VxWorks part refer to the follow...

Page 136: ...thorized access When necessary to protect the system from unauthorized access from external devices ensure other measures in addition to this function are utilized We are unable to accept any responsibility for any problems with the system that may occur as a result of unauthorized access The following are example measures to counter unauthorized access Using a firewall Using a PC as a relay with ...

Page 137: ...s permitted access when the user authentication function is enabled Configure the following information for the user management information Username and password Access level Username and password The following table shows the usernames and passwords that can be configured for the user management information A password of eight characters or longer is recommended Access level Choose an access leve...

Page 138: ...ate to latest information Clearing of values Device File register Clock setting Clock setting Time acquisition of personal computer Time acquisition of the VxWorks part Execution of clock settings monitor Device buffer memory batch monitoring Shared memory monitoring Monitoring start Monitoring end Bit operation Watch Watch window Start of watch End of watch Change of values CC Link IE Field setti...

Page 139: ...ing end Configuration diagram update Configuration diagram update Communications test Test execution Cable test Test execution Link start stop Link start Link stop Forced link start Reserved station temporary clear remove Target station click Temporary error disabled station settings remove Target station click CC Link IEF Basic diagnostics CC Link IEF Basic diagnostics Monitoring start Monitoring...

Page 140: ...uns with the default settings This section shows the default settings for username password and access level User name target Password password Access level Administrators If Change of User authentication setting is Change always add one or more item of user management information with Administrator rights Item Description Setting range Change of user authentication settings Specify whether to cha...

Page 141: ...Window Displayed items Item Description User list The configured user management information is displayed Maximum 16 items Add The screen to add user management information appears delete Deletes the selected user management information Change Changes the selected user management information ...

Page 142: ...igurator operations are disabled parameters cannot be configured To enable service initialize this product MELIPC MI5000 Series User s Manual Startup Item Description Setting range WDB Required to connect CW Workbench 4 and WindRiver Workbench 4 Enable Disabled Default Enabled Shell Required to execute commands 1 MELSEC data link function Required to use MELSEC communication MI Configurator operat...

Page 143: ...e proxy server If this is not block access from computers that can access the proxy server will not be prevented Do not use the firewall function via standard operation of VxWorks when using the IP filter function If the firewall function is used the IP filter function may not run normally IP Filter Settings Configure the IP filter by using IP Filter Settings of Security settings Window Basic Para...

Page 144: ...et for target IP addresses 172 16 0 1 to 172 31 255 255 Item Description Setting range Access from the following IP addresses Select whether to block or allow an access from specified IP addresses Allow Block Default Allow Specify range Select this to specify the range of IP addresses that are to be blocked or allowed Target IP address Set an IP address to be blocked or allowed When Range Setting ...

Page 145: ...s Precautions The following range of IP addresses cannot be configured for IP addresses to be excluded 172 16 0 1 to 172 31 255 255 Item Description Setting range Target IP address Displays the range specified IP address IP address to clear Specify the IP address to clear 0 0 0 1 to 223 255 255 254 ...

Page 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...

Page 147: ...net port CH1 Page 162 BASIC PARAMETERS 2 Set a connection configuration in External Device Configuration of Basic Settings Page 183 External Device Configuration Ports used by the system Do not use ports used by the system The Ethernet port CH1 and virtual Ethernet use the following ports on the system Even in the case of port numbers not mentioned above ports 1 to 1023 are generally reserved WELL...

Page 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...

Page 149: ...ition of count value The count value can be acquired by a C Controller module dedicated function Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual VxWorks Item Description Range 1 1 μs counter Increased by 1 every 1 μs after the power is turned ON 0 to 4294967295 1 ms counter Increased by 1 every 1 ms afte...

Page 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...

Page 151: ... dedicated function Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual VxWorks Item Description range cycle Specify the cycle for the timer to report an event 0 1 to 60000 ms Synchronization type Specify the type of event to be reported by the timer Batch synchronization Individual synchronization Item Desc...

Page 152: ...150 14 TIMER EVENT FUNCTION MEMO ...

Page 153: ...151 PART 3 PART 3 COMMON FUNCTIONS This part explains the common functions between the Windows part and VxWorks part 15 OS LINKING FUNCTIONS 16 SERIAL INTERFACE SWITCHING FUNCTION ...

Page 154: ...FT PRODUCT AND GOT CONNECTION FUNCTION Connection of Windows part and VxWorks part The sections are connected by the following IP addresses configured to virtual Ethernet Windows part 172 16 0 2 VxWorks part 172 16 0 1 Precautions By using this function the connection is handled as a connection of MELSOFT products when MI Configurator installed on the Windows part is connected to the VxWorks part ...

Page 155: ...red memory from GOT or other external devices copy data to the buffer memory or a device that can be accessed from external devices Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual Windows MELIPC MI5000 Series Programming Manual VxWorks Shared memory size A size of 256 MB can be used as shared memory Shar...

Page 156: ...s specify the inter OS event number and send and receive inter OS event notifications Function list For details on the C Controller module dedicated functions refer to the following manual MELIPC MI5000 Series Programming Manual Windows MELIPC MI5000 Series Programming Manual VxWorks 1 VxWorks part 2 Windows part 3 Notifications of inter OS events Function name Description CCPU_ReceiveInterOSEvent...

Page 157: ...ime and then carries out processing from the C Controller module dedicated function CCPU_ReceiveInterOSEvent and later Furthermore when multiple inter OS events have been reported to the same inter OS event number when the C Controller module dedicated function CCPU_ReceiveInterOSEvent is executed they are processed as a single inter OS event report by the user program When multiple user applicati...

Page 158: ...tion after an update of shared memory The following diagram shows an example of the operations of a user program receiving and sending data between operating systems using the inter OS event notification function 1 VxWorks part 2 Windows part 3 Shared memory 1 2 Ó CCPU_WriteSharedMemory Ò CCPU_WaitSharedEvent Ô CCPU_RequestSharedEvent Õ CCPU_ReadSharedMemory Ò CCPU_WaitSharedEvent Ó CCPU_WriteShar...

Page 159: ...ory is executed Data written to the shared memory by the user program of the VxWorks part is read by the user program of the Windows part When a user program of the VxWorks part reads data of the Windows part The C Controller module dedicated function CCPU_ReceiveInterOSEvent is executed by a user program of the VxWorks part The user program of the VxWorks part waits for an inter OS event notifica...

Page 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...

Page 161: ...t is reset Window Basic Parameter Operation Related Setting Serial I F Setting Displayed items Remote debugging of the VxWorks part by serial communication Remote debugging using serial communication can be performed in the same way as with a Telnet connection After the serial communications setting is set to the VxWorks part the standard I O destination can be switched to the serial communication...

Page 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...

Page 163: ...161 PART 4 PART 4 PARAMETERs This part explains the parameters of this product 17 BASIC PARAMETERS 18 APPRICATION PARAMETERS ...

Page 164: ...following shows the basic parameters Name setting Window Displayed items Title setting Comment setting Item Description Setting range parameter No Title Set when setting the title 32 characters or less Unicode Default Blank 3100H Item Description Setting range parameter No Comment Set when setting comments 256 characters or less Unicode Default Blank 3101H ...

Page 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...

Page 166: ... simpl e settin gs Configure the daylight saving time setting through basic operations Clock simple settings By specifying Time zone and Adjust clock for daylight saving time a specified week or specified date is configured automatically Clock Simple Settings Clock simpl e settin gs Cloc k setti ng Configure the time zone and daylight saving time setting Time zone hour Set when using time zones on...

Page 167: ...Set the adjustment start time month 1 to 12 Default March Week Set the adjustment start time week Last week first to fourth week Default Second week Day of week Set the adjustment start time day Sunday to Saturday Default Sunday Time Set the adjustment start time time 0 00 to 23 00 Default 2 00 End Set the adjustment end time Month Set the adjustment end time month 1 to 12 Default November Week Se...

Page 168: ...66 17 BASIC PARAMETERS 17 1 Basic Parameter List Clock Simple Settings Acquire the time zone configured by the Windows part and apply the time zone and daylight saving time to the VxWorks settings Window ...

Page 169: ...o n of day of week Sunday Monday Tuesday Wednesda y Thursday Friday Saturday Configure to specify the day to configure the time during fixed cycle specification Sunday Configure whether to specify Sunday for the day specification Set Not Set Default Set Monday Configure whether to specify Monday for the day specification Tuesday Configure whether to specify Tuesday for the day specification Wednes...

Page 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...

Page 171: ...ce operation upon detection of a Main module temperature error If Shutdown is set the VxWorks part and Windows part shut down when an error is detected Shut down Do not shut down Default Shutdown 3501H Windows part stop Set operation of the Windows part when a stop state is detected due to a Windows bluescreen timeout detection from the Windows part system watchdog timer Do not restart Restart Def...

Page 172: ...sable the WDB service Enable Disabled Default Enabled 6E00H Shell Configure to enable or disable the Shell service If Enable is configured Use can be configured for the Telnet server settings MELSEC data link function Configure to enable or disable the MELSEC data link function service MI Configurator operations Configure to enable or disable the MI Configurator operation service ...

Page 173: ...ion Setting range parameter No Communication addressed to own station Configure the timeout value for communication addressed to own station Setting range 1 to 360 s 1 second units Default 15 sec 6E03H CC Link IE Field Network Configure the timeout value of the CC Link IE Field Network Setting range 1 to 360 s 1 second units Default 15 sec 6E07H ...

Page 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...

Page 175: ...ss 1 Set the own node CH1 IP address Configure the own node and the external device with which to communicate to the same class and subnet address Configure an IP address within the range of Class A Class B and Class C 0 0 0 1 to 223 255 255 254 Default 192 168 3 3 A012H Subnet mask 1 2 Set the own node CH1 subnet mask This is a setting to define the top bit of the IP addresses to use for network ...

Page 176: ...IE Field Network Basic link devices and the MELIPC devices Page 182 Refresh Setting 7420H Link Scan Time Settings Configure the link scan time setting The link scan time is retained in the interval configured for each group number However when the actual link scan time is longer than the setting operation follows link scan time Furthermore this is not an item to keep the transmission delay time co...

Page 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...

Page 178: ...hat have Ethernet functions A03AH IP filter function Set whether to use the IP filter function Do not use Use Default Do not use IP filter setting details Configure the settings to use the IP filter function and restrict access Page 142 IP filter setting details MELIPC search on network setting Configure the settings related to MELIPC searches on a network 6E20H MELIPC search response setting Sele...

Page 179: ...17 BASIC PARAMETERS 17 2 Network Configuration Settings 177 17 17 2 Network Configuration Settings Set a network configuration Window 1 Station list 2 Network configuration diagram 3 Drag and drop 1 2 3 ...

Page 180: ...pe Displays the station type master station slave station RX RY Setting Points 1 Set assignation of numbers of points RX RY in increments of 64 64 1 station share 128 2 station share 192 3 station share 256 4 station share Default 64 1 station occupied Start Displays the RX RY start number End Displays the RX RY end number RWw RWr setting Points 1 Displays numbers of points in increments of 32 Sta...

Page 181: ...he network configuration settings After configuration the information is applied to the slave stations From the station list or network configuration diagram select a module and then select Online Apply slave station communication settings 4 Parameters unique to slave devices can be read or written from the network configuration settings 1 For the parameters unique to slave devices refer to the ma...

Page 182: ...evice ran an unsupported function Check if the target device supports the function that was run C05CH A communication setting value is out of range A communication setting value that cannot be configured was configured for the target device A necessary setting item has not been configured on the target device Review the setting content and then run the command again C061H System error Check the co...

Page 183: ... run the command again CF53H CF56H System error Check the considerations of the function that was run Check the operation status and connection of target devices Check the Ethernet cable and hub connections Check the Ethernet line status Reset the CPU modules and target devices and then run the command again If the problem still cannot be resolved contact the manufacturer of the target device CF70...

Page 184: ...ettings are displayed MELIPC side Target The target for link refresh is displayed Specify Device device name Set the device of the link refresh target M B D W ZR Points The number of device points subject to link refresh is displayed A value the same as the number of points of the link side is displayed Start Set the start device number within the link refresh range M 0 to 61439 B 0 to 9FFFFH D 0 ...

Page 185: ...d and protocols used with external devices UDP connection devices OPS connection devices active connection devices unpassive connection devices fullpassive connection devices and MODBUS TCP connection devices cannot be used Window Basic Parameter External Device Cooperate Settings External Device Configuration Detail Setting ...

Page 186: ...ange 1 to 16 Model name Displays the model name of the connected external device Communications method Set the communications method with external devices MELSOFT connection SLMP Protocol Sets the communications protocols used with external devices TCP 1 UDP 2 3 Fixed buffer send receive settings These items do not require configuration MELIPC IP address The own node IP address set in External Dev...

Page 187: ...the transmission using the TCP protocol from the other device then this carries out retransmission processing using the following retransmission frequency and intervals If there is no ACK response to the TCP protocol 60 seconds after the last retransmission then the other device will be considered faulty and the connection disconnected Retransmission count 1 12 times Retransmission interval 2 retr...

Page 188: ...to Device List 1 or Device Configuration 2 2 Set each item 3 Click the Reflect and Close the Setting button Setting a target device from connection No 1 in the external device configuration is required If using a specific connection number set the MELSOFT connected device to the external device with the unused connection number If using connection No 5 only 1 2 3 ...

Page 189: ...ows CC Link IE Field Network parameters Required settings The following shows the required settings for CC Link IE Field Network parameters If a master station is selected by station type the following parameters are displayed in applicable settings Synchronization communication settings For details on each parameter refer to the following section Page 193 Required settings if master station is se...

Page 190: ...ter station Local station 7100H 7700H Item Description Setting range Parameter No Network No Set the network No for the network to connect to the CC Link IE Field Network 1 to 239 Default 1 7100H Item Description Setting range Parameter No Station number settings method Select the station number configuration method of local stations Local station only setting Set in parameters 7100H Station numbe...

Page 191: ...eters Window Displayed items Network configuration settings Network topology setting Item Description Setting range Parameter No Network configuration settings Set the slave station link device points number and assignment in the master station Page 195 Network Configuration Settings Item Description Setting range Parameter No Network topology setting Select to match the connection method in use w...

Page 192: ... If master station is selected in essential settings station type then the following parameters will be displayed in applicable settings Station unit block guarantee Communications mode For details on each parameter refer to the following section Page 194 Applicable settings If master station is selected in essential settings station type Window ...

Page 193: ...ear the MELIPC output settings when a stop error has occurred in the MELIPC Clear 7101H Item Description Setting range Parameter No Parameter name Set the parameter name as necessary 8 characters Default Blank 7310H Item Description Setting range Parameter No Other station event acquisition settings Set whether to acquire events generated by other stations on the same network If Acquire is selecte...

Page 194: ...ion is another CPU module in a multiple system configuration Window Item Description Setting range Logical station number Configure the logical station number 65 to 239 Default Blank Network No Configure the network number 1 to 239 Default Blank Station number Configure the station number 0 to 120 Default Blank Target CPU Select the target CPU CPU No 1 to 4 Default Blank ...

Page 195: ... Cycle Setting Method link scans for CC Link IE Field Network will operate with the cycle set for this item Item Description Setting range Parameter No Synchronization Cycle Setting Method Select the configuration method of the synchronization cycle The synchronization cycle is automatically set to the optimal synchronization cycle as required by the number of slave devices connected and cyclic as...

Page 196: ...y settings Communications mode Item Description Setting range Parameter No Station unit block guarantee In link device select whether to use station unit data guarantee Enable Disable Default Assure A040H Item Description Setting range Parameter No Mode Set the communications mode in accordance with usage applications High speed This carries out priority cyclic transmission and is the optimal comm...

Page 197: ...Sensor Solution Reference Manual Mode Setting Displays the master station mode Assignment Method Select the link device assignment method Point Start Enter the points and start numbers of link devices Start End Enter the start and end numbers of link devices Point Start Start End Default Start End Link Scan Time Approx Displays the approximate value for the link scan time No Displays the number of...

Page 198: ...at even if a slave station is added reserve station deleted link device assignment will not change meaning program change is not necessary In actual networks slave stations do not need to be connected Error Invalid Station ensure that slave stations in data link are not detected as faulty stations in the master station Not set Reserved Error Invalid Station Default No setting A001H A002H Pairing I...

Page 199: ...ils refer to the manual for the used slave station Link equal assignment and same point assignment for link numbers Equal assignment and same point assignment are set as follows Item Description Setting range Equal assignment Specify the header station and end station and assign the link path total point numbers equally Header station Set the station number of the header station for equal assignme...

Page 200: ...on not possible Page 210 Disconnect stations Page 210 Stations repeatedly disconnect and reconnect Page 210 Communication is unstable CC Link IE Field Network Basic Page 211 The transmission status is disconnected or unconfirmed Page 212 Cyclic data cannot be read correctly Page 213 Transmission status repeats disconnection and reconnection Page 214 Timeout occurs Page 214 Slow link scan time Page...

Page 201: ... a Japanese language OS the keyboard has an English layout Page 218 Even when changed the date and time values are changed to other values Page 218 Ethernet CH2 is not displayed in the network adapter Page 219 Fonts are corrupted Page 219 Visual Studio cannot be installed Page 219 A drive for CFast card does not appear Page 219 An application error appears while running a user program Page 219 The...

Page 202: ...ese measures this may indicate a hardware fault with the module Consult your local Mitsubishi representative Is the VX RDY LED off and the MAIN ERR LED flashing A severe error has occurred therefore take measures in accordance with the error code If the same phenomenon remains after these measures this may indicate a hardware fault with the module Consult your local Mitsubishi representative Is th...

Page 203: ...oes not start for a long time connect a display to the DisplayPort If an error such as repeated restarts occurs repeatedly restart the Windows part in Safe mode If the Windows part does not start for a long period of time after restarting the Windows part reset this product by a switch operation or turn the power of the product OFF and ON If this symptom occurs repeatedly data on the CFast card ma...

Page 204: ...nsure the distance between stations is within specifications Is the installation situation bend radius within specifications Set the bend radius within specifications Is the Ethernet cable broken Replace the Ethernet cable Are 121 or more slave stations connected Ensure no more than 120 slave stations are connected Is the switching hub being used operating correctly Check that a switching hub that...

Page 205: ...se around the product the stations and wiring Change the locations and wiring of modules Check item Corrective action Does the used Ethernet cable meet specifications Use Ethernet cables that meet the following standards Is the distance between stations within specifications Ensure the distance between stations is within specifications Is the installation situation bend radius within specification...

Page 206: ...personal computer and this product to a different network Is the specified IP address correct Specify the correct IP address In the following settings is access from the PC being blocked Basic Parameter External Device Cooperate Applicable Settings Security Settings IP Filter Settings In the IP filter settings unblock access from the PC Check item Corrective action Is the connection destination of...

Page 207: ...ct Are there 11 or more external devices making FTP connections to this product Adjust so that the number of external devices making FTP connections is 10 or less Can an FTP connection to this product be made from the Command prompt of Windows Change to an FTP client tool that can connect normally In the following settings is access from the PC being blocked Basic Parameter External Device Coopera...

Page 208: ... connected LAN network administrator On the connected LAN are there any duplicate IP addresses with the product and PCs Consult with the administrator of the connected LAN and ensure that there are no duplicated IP addresses Has the product been replaced Reset all terminals connected to the network Is the network under high load Consult with the administrator of the connected LAN and disconnect de...

Page 209: ...nitialize this product and then change the IP address of the Ethernet port CH1 to the default settings In the following settings are the virtual Ethernet IP address settings set to being blocked Basic Parameter External Device Cooperate Applicable Settings Security Settings IP Filter Settings Unblock the IP address of the virtual Ethernet in the IP settings Check item Corrective action An error oc...

Page 210: ...written to Disable the Unified Write Filter before writing When accessing the files writing reading etc is the STORAGE LED flashing If the access target is not the standard drive 1 of this product check the wiring If there are no problems with the wiring check the manual of the device being used If the access target is the standard drive 1 of this product this may indicate a hardware fault of this...

Page 211: ...fications of slave stations In the following settings are slave station RX RY settings or RWw RWr settings set Application Parameter CC Link IE Field Network Parameter Basic Settings Network Configuration Settings Set slave station RX RY or RWw RWr ranges Do the station numbers set below and the station set in the slave station match Application Parameter CC Link IE Field Network Parameter Basic S...

Page 212: ...INK LED is off or flashing perform troubleshooting for the corresponding module Is the distance between stations within specifications Ensure the distance between stations is within specifications Is the installation situation bend radius within specifications Set the bend radius within specifications Is the Ethernet cable broken Replace the Ethernet cable Is the switching hub being used operating...

Page 213: ... addresses that are the same as master station slave stations within the same network address Change master station slave station IP addresses to addresses that do not overlap Do master station and slave station network addresses match Correct IP address and subnet masks so the master station and slave station IP addresses match Correct so the master station slave station subnet masks have the cor...

Page 214: ...ction count U3E0 G4648 Page 282 List of Buffer Memory Check item Corrective action In the following settings is a slave station set as a reserved station Basic Parameters External Device Connection Settings CC Link IEF Basic Settings Network Configuration Settings Cancel reserved station specifications of slave stations Has the accumulated timeout count for the slave station thought to be faulty b...

Page 215: ... speeds used by the connected master station slave station Are there any delays in response error responses or no responses with functions using the Ethernet port CH1 such as FTP socket communications or SLMP Stop the function Alternatively review settings such as by increasing the interval between executions of these functions or decreasing their frequency Check item Corrective action Are the mas...

Page 216: ...heir frequency On the same circuit is CC Link IE Field Network Basic running at the same time on a different network address Separate the network to a separate circuit and create a CC Link IE Field Network Basic Are communications with other Ethernet devices being carried out on the same line Separate the network into a CC Link IE Field Network Basic network and a different Ethernet device network...

Page 217: ...ESET Set WIN RESET to Enable Was the MELIPC shutdown function run Turn the power supply of this product OFF to ON Check item Corrective action Were the following functions used for advance processing of Windows part forced restart CCPU_MELIPCShutdown CCPU_WinReset Switch the power supply of this product OFF to ON review the advance processing registered by the user for the Windows part forced rest...

Page 218: ... with the garbled name using only characters that can be used by the VxWorks part Alternatively rename the file or folder to be copied and then copy it again Check item Corrective action Was there an attempt to create a new file or folder directly in a folder of the VxWorks part using a New Folder or New operation of Windows Explorer Create a new file folder in a location other than a folder of th...

Page 219: ...ective action Is the DisplayPort cable connected correctly Correctly connect the DisplayPort cable Is the DisplayPort cable broken Replace the DisplayPort cable Is the display broken Replace the display to a new one Check item Corrective action Does the mouse cursor move Wait then try the operation again Check that a mouse is connected to a USB port Connect a mouse that has once been connected to ...

Page 220: ...ted to the USB port If it does not work then replace the USB device Are any USB3 0 devices being used Connect to a USB port supporting USB3 0 Check item Corrective action Is there sufficient free space on the C drive Remove unnecessary files to create free space Have unnecessary applications been installed Uninstall unnecessary applications Is the screen of Windows stuck for a long time Reset the ...

Page 221: ...ws to initialize the disk Is the partition format of the CFast card GTP Delete the configuration information from a CFast card in GPT format and initialize the card in MBR format For the initialization method of a CFast card refer to the following manual MELIPC MI5000 Series User s Manual Startup Is a drive letter assigned to the partition of the CFast card Assign a drive letter in the disk manage...

Page 222: ...y the user program outputting them to the dot matrix LED or monitor MELIPC MI5000 Series Programming Manual VxWorks Error code system Error codes are represented in four digit hexadecimal number unsigned 16 bit integer Errors that can be detected by the self diagnosis function and common errors that can be detected during data communications between modules are included in the following table Erro...

Page 223: ...in the Windows part If a watchdog timer error has occurred due to the watchdog timer function of the Windows part a notice is sent to the VxWorks part only when a system watchdog timer error occurred For details on the watchdog timer function refer to the following manual Page 18 Watchdog Timer WDT Function MAIN LED error classificatio n Error code Error details VX RDY MAIN RUN MAIN ERR On In acco...

Page 224: ...P server is operating normally and there is no failure on the network accessing the SNTP server computer 112EH Connection establishment failed A connection could not be established in the open processing Check the operation of the target device Check if the open processing has been performed in the target device Review the port number of the module IP address port number of the target device openi...

Page 225: ...lt your local Mitsubishi representative 184DH CFast card error An overcurrent to the CFast card has been detected Replace the CFast card Reset the system If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 184EH CFast card error Insertion removal of the CFast card has been detected Reset the system If the same error is displayed agai...

Page 226: ...dicate a hardware fault Consult your local Mitsubishi representative 2222H Parameter error Use of the function that is not supported by the module is enabled Check detailed information parameter information using the MELIPC diagnosis of an engineering tool and then review the parameter setting corresponding to the displayed number parameter number If the same error is displayed again this may indi...

Page 227: ...are fault Consult your local Mitsubishi representative 3C00H Hardware failure A hardware failure was detected Take measures to reduce noise Reset the system If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 3C01H Hardware failure A hardware failure was detected Take measures to reduce noise Reset the system If the same error is dis...

Page 228: ...ich the station based block data assurance setting is enabled on the network has been accessed when the stop error occurred An error was detected in the memory MELIPC is uncontrollable or damaged malfunction from noise or hardware fault Reset the system Lower the CPU usage rate of tasks with the higher rate or make them inactivated Review the user program Set a sufficiently long system WDT monitor...

Page 229: ...e failure A hardware failure was detected Take measures to reduce noise Reset the system If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 3E5CH Hardware failure A hardware failure was detected Take measures to reduce noise Reset the system If the same error is displayed again this may indicate a hardware fault Consult your local M...

Page 230: ...If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 3EA7H Hardware failure A hardware failure was detected Take measures to reduce noise Reset the system If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 3EA8H Hardware failure A hardware failure has been detected Take...

Page 231: ...ete the file and then create a file again 4024H File related error The specified file cannot be handled The specified file cannot be handled 4025H File related error The specified file is currently processing a request from another engineering tool Forcibly execute the request Or execute it again once the processing from another engineering tool has been completed 4027H File related error The spec...

Page 232: ...uest data error Check the specified request data 4081H Any other error File header information does not exist Reread the parameter and reset the MELIPC If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 4082H Any other error The specified command cannot be executed since it is being executed Execute the command again once the reques...

Page 233: ...e is a read only file Change the conditions for the specified file and execute the request again 4138H File related error Simultaneously accessible files exceeded the maximum Reduce file operations and execute again 4139H File related error The size range of the specified file has exceeded the existing one Check the size of the specified file and execute the request again 413AH File related error ...

Page 234: ... the MELIPC port number other device IP address port number and opening method Check that connection cables have not been removed 41A8H Ethernet port error The data length exceeds the permissible range Correct the data length If the sent data quantity exceeds the specified quantity this will be split and then sent 41ABH Ethernet port error Failed to communicate due to a retransmission timeout Revi...

Page 235: ... to access the file sector The format information data of the target drive memory is abnormal Back up the data of the ROM folder and then initialize the memory 41CBH File related error There is an error in the specification method of the file name Check the file and execute the request again 41CCH File related error The specified file does not exist Alternatively the specified subdirectory does no...

Page 236: ...nk related error The specified station cannot be accessed Check that the operating mode is not set to offline Check that there are no mistakes in the network No or station No settings 4A03H Link related error A request for network test was issued Check request data such as SLMP 4B00H Target related An error occurred on the access destination or the relay station Alternatively the specified connect...

Page 237: ...legal write to buffer memory reserved area Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 8867H Buffer memory access error Illegal write to buffer memory reserved area Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsu...

Page 238: ... memory access error Illegal write to buffer memory reserved area Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 8949H Buffer memory access error Illegal write to buffer memory reserved area Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault C...

Page 239: ... again this may indicate a hardware fault Consult your local Mitsubishi representative 8A60H to 8A6CH Buffer memory access error Illegal write to buffer memory reserved area Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 8AA0H to 8AAFH Buffer memory access error Illegal write to buffer memory res...

Page 240: ...again this may indicate a hardware fault Consult your local Mitsubishi representative 8BE0H to 8BE8H Buffer memory access error Illegal write to buffer memory reserved area Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative 8BF0H Buffer memory access error Illegal write to buffer memory reserved area...

Page 241: ...r memory reserved area Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative A001H Default Hardware failure Take measures to reduce noise Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative A002H Internal c...

Page 242: ...e failure was detected Take measures to reduce noise Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi representative AC14H Hardware failure A hardware failure was detected Turn the power supply OFF and ON If the same error is displayed again this may indicate a hardware fault Consult your local Mitsubishi represe...

Page 243: ... the slave station where the error occurred CFD0H Master station error The port No 61450 used in CC Link IE Field Network Basic has already been used Check the port No used in the external device configuration CFD1H Master station error Invalid value has been set in subnet mask Check the parameter setting CFE0H Cyclic transmission error slave station The cyclic transmission was executed for the sl...

Page 244: ...cy and then perform again Check that there are no faults with the request source cable or a switching hub connections D0A2H CC Link IE Field Network function related errors In transient transmission there was a transmit processing wait time out Lower the transient transmission usage frequency and then perform again Check that there are no faults with the request source cable or a switching hub con...

Page 245: ...t the transient request source and run again D20BH to D20CH CC Link IE Field Network function related errors No master station when setting specified master station in transient transmission Correct the target station No at the transient request source and run again D20DH CC Link IE Field Network function related errors In transient data transmission there was a transmit end wait time out In engin...

Page 246: ...t the application type or target station number at the transient request source and then run again D222H CC Link IE Field Network function related errors Error in the transient transmission command Correct the request command at the transient request source and run again D223H to D224H CC Link IE Field Network function related errors Transient transmission error detected In engineering tools CC Li...

Page 247: ...3CH CC Link IE Field Network function related errors There is an error in the SLMP target station number Correct the station number at the request source and then run again D23DH to D23EH CC Link IE Field Network function related errors There is an error in the SLMP request data There is an error in the device information acquisition request of CC IE Field Configuration Setting displayed in the Ne...

Page 248: ... errors Error in the transient transmission frame data length Correct the data quantity frame length at the transient request source and run again D2A4H CC Link IE Field Network function related errors Error in the transient transmission frame header information Correct the header information at the transient request source and run again D2A5H CC Link IE Field Network function related errors Error...

Page 249: ...itsubishi representative D605H CC Link IE Field Network function related errors Parameter error In Applicable parameters CC Link IE Field Network Parameters rewrite to MELIPC If the error code is displayed again even after taking an action consult your local Mitsubishi representative D611H CC Link IE Field Network function related errors Parameter error each station device range allocation error R...

Page 250: ...ation link device offset for set data and run again If the error code is displayed again even after taking an action consult your local Mitsubishi representative D619H to D61AH CC Link IE Field Network function related errors Parameter error In Applicable parameters CC Link IE Field Network Parameters rewrite to MELIPC If the error code is displayed again even after taking an action consult your l...

Page 251: ... MELIPC If the error code is displayed again even after taking an action consult your local Mitsubishi representative D624H CC Link IE Field Network function related errors Parameter error In Applicable parameters CC Link IE Field Network Parameters rewrite to MELIPC If the error code is displayed again even after taking an action consult your local Mitsubishi representative D625H CC Link IE Field...

Page 252: ...e requested After specifying the station for reserved station temporary clear temporary error disabled station settings SW0010 to SW0017 run again D70BH CC Link IE Field Network function related errors Reserved station temporary clear remove and temporary error disabled station settings remove requested simultaneously Temporary error disabled station settings remove with SB0010 to SB0011 and reser...

Page 253: ...and run again D842H CC Link IE Field Network function related errors Routing information to destination network number not recorded In transient transmission relay counts to other networks exceeded 7 times Correct the target network number at the transient request source and run again Correct the communications route from transient request source to destination and run again D844H CC Link IE Field...

Page 254: ... After cable test has completed run again D912H CC Link IE Field Network function related errors Transient transmission failed Lower the transient transmission usage frequency and then perform again Check that there are no faults with the cable or a switching hub connections D913H to D917H CC Link IE Field Network function related errors MELIPC error detected Consult your local Mitsubishi represen...

Page 255: ...history clear An event history was cleared 24000H Operation Information Clock setting The clock setting was performed 24001H Operation Information Remote operation request acceptance A remote operation request RUN STOP was accepted 24100H Operation Information Operating status change RUN The operating status was changed to RUN 24101H Operation Information Operating status change STOP The operating...

Page 256: ...tation Temporary error disabled station clear instruction received Temporary error disabled station clear instruction received 524H System Information Other station Temporary error disabled station settings execute Other station temporary error disabled station settings execute 525H System Information Other station Temporary error disabled station clear execute Other station temporary error disabl...

Page 257: ...C24H System Warning Other station Receive frame error occurred Reception frame error occurred on another station C25H System Warning Reception parameter error occurred Error detected in parameter received from master station administered station C27H System Warning Transient reception failure Own station transient frequency is too high therefore transient reception failed 20011H Operation Informat...

Page 258: ...eld network Basic of this product file register Used to store processing calculation and other results and send and receive data with GOT MELSOFT products and other external devices Data is retained even if the power supply of this product is turned OFF Classification Type Device name device Number of points Available ranges User device Bit Internal relay M 61440 points M0 to 61439 DEC Link relay ...

Page 259: ...d S at error occurrence SM52 battery low OFF Normal On Battery low This relay switches to ON when the battery voltage of the MELIPC drops below the specified value Becomes OFF if the battery voltage becomes normal later This relay synchronizes with BATTERY LED S at error occurrence SM53 AC DC DOWN Off No AC DC DOWN detection On AC DC DOWN is detected This relay switches to ON when a momentary powe...

Page 260: ...ata was updated is stored as a BIN code Month 1 to 12 S at error occurrence SD4 The hour when SD0 data was updated is stored as a BIN code Day 1 to 31 S at error occurrence SD5 The minute when SD0 data was updated is stored as a BIN code Hour 0 to 23 S at error occurrence SD6 The second when SD0 data was updated is stored as a BIN code Minute 0 to 59 S at error occurrence SD7 The day of the week v...

Page 261: ... at error occurrence SD81 to SD111 Detailed information 1 Detailed information 1 5 System configuration information SD81 With or without specification b4 CPU No b5 Network No b6 Station No SD82 Empty SD83 Blank If not specified this is 0 SD84 b0 to b7 Blank If not specified this is 0 SD84 b8 to b15 CPU No If not specified this is 0xFF SD85 Network No If not specified this is 0 SD86 Station No If n...

Page 262: ...4 Parameter information SD113 With or without specification b0 Parameter type b1 Parameter storage destination b3 Parameter No b4 Network No b5 Station No b6 System information SD114 b0 to b7 Parameter type 1 Basic parameters 2 CC Link IE Field Network Parameters SD114 b8 to b15 Parameter storage location 4 User drive SD115 Empty SD116 Parameter No SD117 Network No SD118 Station No 0 to 120 0 for ...

Page 263: ... set is stored as 32 bit data S initial SD263 Number of points assigned for Y H S initial SD264 Number of points assigned for M L The number of points of the M device currently set is stored as 32 bit data The number of points assigned is stored even if the number of points assigned for M is 32K or less S initial SD265 Number of points assigned for M H S initial SD266 Number of points assigned for...

Page 264: ...ansmission interlock S status change SD1540 to SD1543 Data link status of each station Data link status of each station The data link status of each station is stored using the following bit pattern OFF Normal station including a slave station not responding to an initial request from the master station because of the slave station power is OFF The slave station is not judged as a faulty station b...

Page 265: ...b0 to 9 1st row 1st to 9th dot b0 stores from 9th dot onwards b10 to b15 Reserved From SD1553 to SD1591 the corresponding information is stored like SD1552 S status change No Name Content Details Set by when to set SD1552 b0 b15 SD1591 SD1553 SD1554 SD1590 SD1589 SD1555 SD1588 1st column 2nd column 3th column 4th column 37th column 38th column 39th column 40th column 1st column Dot matrix LED 1st ...

Page 266: ...hat gives the stop instruction specifies using link start stop instruction details SW0000 and link start stop station instruction SW0001 to SW0008 0 No stop instruction 1 Stop instruction start up time enabled Conditions Enabled when baton pass status of own station SB0047 is OFF Enabled when only one point from SB0000 to SB0003 is ON SB0006 Clear communications error count Instruct a 0 clear for ...

Page 267: ... baton pass status of own station SB0047 is OFF When baton pass status of own station SB0047 is ON error the data immediately before is retained SB004A Own station minor error status The minor error occurrence status of own station is stored Off No minor error ON Minor error SB004B Own station moderate major error status The moderate major error occurrence status of own station is stored OFF No mo...

Page 268: ...ry error disabled station settings request end status Stores temporary error invalid station settings processing status from temporary error invalid station settings processing request SB0010 OFF Not ended SB0010 SB0058 OFF ON Normal end or abnormal end SB0010 SB0058 ON SB005A Temporary error disabled station settings clear request reception status Stores temporary error invalid station settings c...

Page 269: ...tation port 2 0 A reception frame error The circuit status warning level is not occurring 1 A reception frame error The circuit status warning level is occurring SB008F Own station port 2 error frame reception detection status latch 2 Shows if a reception frame error of the circuit status warning level occurred at own station port 2 when the power supply was turned ON 0 A reception frame error The...

Page 270: ...tely before is retained SB00D0 Current error disabled station settings status Stores presence of error disabled station settings OFF No settings ON Set If setting the status of each station can be confirmed using error invalid station settings status SW00D0 to SW00D7 Conditions Enabled when baton pass status of own station SB0047 is OFF When baton pass status of own station SB0047 is ON error the ...

Page 271: ...erate or major error Conditions Enabled when sub master function is used SB0110 Each station CPU minor error occurrence status The local station stores each station CPU module minor error occurrence status Remote I O station remote device station and intelligent device station stores the minor error occurrence status of each station OFF All stations normal or one or more moderate or major error st...

Page 272: ...r supply is turned ON 0 A reception frame error of the circuit status warning level is not occurring at port 2 of any station 1 A reception frame error of the circuit status warning level is occurring at port 2 of at least one station If a reception frame error of the circuit status warning level occurred the status of each station can be confirmed with Port 2 error frame reception detection statu...

Page 273: ... 0 No start stop instruction 1 Start stop instruction The numbers within the following illustration indicate the station numbers SW0010to SW0017 Reserved station temporary clear temporary error disabled station setting Specify a slave station to carry out reserved station temporary clear remove and temporary error disabled station settings remove 0 No specification 1 Specification The numbers with...

Page 274: ...ameter mismatch 1DH In CC Link IE Field Network synchronous communication initial processing 20H Moderate or major error 60H Invalid ring connection master station only SW004A Station requiring data link stop Stores the station number of the station requesting a stop for own station Range 1 to 120 125 master station Carry out data link stop request with system link stop SB0003 Conditions Enabled w...

Page 275: ...results Stores results from temporarily clearing of reserved stations at a reserved station specifications temporary clear request SB0012 0 Normal From 1 Error details error code Turning OFF reserved station specified temporary cancel request SB0012 clears stored error details SW0057 Reserved station specified enabled request results Stores results from canceling temporary clearing of reserved sta...

Page 276: ...N error the data immediately before is retained SW007C Port 2 cable disconnection detection count Stores the Port 2 cable disconnection detection accumulated count If clear communications error count SB0006 is ON the stored count is cleared If the count reaches the maximum value of 65535 FFFFH the count returns to 0 then continues SW007D Port 2 received error detection count Stores the Port 2 erro...

Page 277: ...nditions Each station baton pass status SW00A0 to SW00A7 each station data link abnormal status SB00B0 and each station data link status SW00B0 to SW00B7 are not related Only enabled for stations with network numbers the same as the master operating station SW00C0 to SW00C7 Reserved station settings status Stores each station reserved station settings status 0 Other than the reserved station inclu...

Page 278: ...for the station numbers after the maximum station number SW00E0 to SW00E7 Temporary error disabled station settings status Stores each station temporary error disabled station settings status 0 Other than temporary error disabled stations 1 Temporary error disabled stations The numbers within the following illustration indicate the station numbers fixed at 0 Conditions Enabled when baton pass stat...

Page 279: ... station SB0047 is ON error the data immediately before is retained Only enabled for stations with normal each station baton pass status SW00A0 to SW00A7 The status is not stored for the reserved stations and the station numbers after the maximum station number SW00F8 to SW00FF Network No matching status Stores the status of matching between the network No set in the master station and that of the...

Page 280: ...on indicate the station numbers fixed at 0 SW0110 to SW0117 Each station CPU minor error occurrence status The local station stores each station CPU module minor error occurrence status Remote I O station remote device station and intelligent device station stores the minor error occurrence status of each station 0 Normal or moderate or major errors occurring 1 Minor error The numbers within the f...

Page 281: ...t 0 Conditions Enabled when baton pass status of own station SB0047 is OFF When baton pass status of own station SB0047 is ON error the data immediately before is retained Only enabled for stations with normal each station baton pass status SW00A0 to SW00A7 SW0150to SW0157 Port 2 error frame reception detection status 1 Shows if a reception frame error of the circuit status caution level has occur...

Page 282: ... SB0047 is ON error the data immediately before is retained Only enabled for stations with normal each station baton pass status SW00A0 to SW00A7 The status is not stored for the reserved stations and the station numbers after the maximum station number SW0180to SW0187 Reserved station temporary clear settings status Stores each station reserved station temporary clear settings status 0 No reserve...

Page 283: ... 0 Conditions Enabled when baton pass status of own station SB0047 is OFF When baton pass status of own station SB0047 is ON error the data immediately before is retained Stations that have not run an inter module synchronous interrupt program because the CPU operating status is STOP or similar are also not synchronized 0 Only enabled for stations with normal each station baton pass status SW00A0 ...

Page 284: ...E Field Network function area Address decimal hexadecimal Area Name Initial value Read Write 0 to 4591 0H to 11EFH System area 4592 11F0H Control data area Group No 1 configured link scan time 0 Read 4593 11F1H Group No 1 configured slave station timeout time 0 Read 4594H 11F2H Group No 1 configured slave station disconnection detection timeout count 0 Read 4595H 11F3H System area 4596 11F4H Contr...

Page 285: ...link scan time 0 Read 4615 1207H Group No 1 minimum link scan time 0 Read 4616 1208H Group No 1 current link scan time 0 Read 4617 1209H System area 4618 120AH Control data area Group No 2 maximum link scan time 0 Read 4619 120BH Group No 2 minimum link scan time 0 Read 4620 120CH Group No 2 current link scan time 0 Read 4621 120DH System area 4622 120EH Control data area Group No 3 maximum link s...

Page 286: ...agnosis information 1 Accumulated disconnection detection count 0 Read 4649 to 4651 1229H to 122BH System area 4652 122CH Control data area Diagnosis information 2 Manufacturer code 0 Read 4653 122DH System area 4654 122EH Control data area Diagnosis information 2 Type name code lower 0 Read 4655 122FH Diagnosis information 2 Type name code upper 0 Read 4656 1230H Diagnosis information 2 Device ve...

Page 287: ...2 to 20003 4E22H to 4E23H Windows part system WDT reset maximum time 0 Read 20004 to 20005 4E24H to 4E25H Own node setting status storage area Ethernet port CH1 Own node IP address 0 Read 20006 to 20013 4E26H to 4E2DH System area 20014 to 20015 4E2EH to 4E2FH Own node setting status storage area Ethernet port CH1 Subnet mask 0 Read 20016 to 20017 4E30H to 4E31H System area 20018 to 20019 4E32H to ...

Page 288: ... 118976 to 119455 1D0C0H to 1D29FH System area 119456 1D2A0H RX offset size information Station No 1 RX offset 0 Read 119457 1D2A1H Station No 1 RX size 0 Read 119458 to 119693 1D2A2H to 1D38DH 119694 1D38EH Station No 120 RX offset 0 Read 119695 1D38FH Station No 120 RX size 0 Read 119696 1D390H Station No 0 RX offset 0 Read 119697 1D391 Station No 0 RX size 0 Read 119698 to 119711 1D392H to 1D39...

Page 289: ...ead 120464 1D690H Station No 0 RWr offset 0 Read 120465 1D691H Station No 0 RWr size 0 Read 120466 to 120511 1D692H to 1D6BFH System area 120512 1D6C0H Own station information network card information Manufacturer code 0 Read 120513 1D6C1H Device type 0 Read 120514 1D6C2H Model code 1 Read 120515 1D6C3H Version 1 Read 120516 to 120551 1D6C4H to 1D6E7H System area 120552 1D6E8H Other station inform...

Page 290: ...64FH Communication route establishment status network No 17 to 239 Communication route establishment status network No 17 to 239 0 Read 124496 to 130223 1E650H to 1FCAFH System area 130224 1FCB0H PORT2 side line error occurrence rate maximum Station No 1 0 Read 130225 to 130343 1FCB1H to 1FD27H Station No 2 to station No 120 0 Read 130344 1FD28H Station No 0 0 Read 130345 to 130351 1FD29H to 1FD2F...

Page 291: ...No 3 configured link scan time The link scan time during cyclic transmission configured by a C Controller module dedicated function CCPU_ChangeCCIEFBCycPrm function or MI Configurator is stored Unit ms U3E0 G4601 Group No 3 configured slave station timeout time The slave station timeout time configured by a C Controller module dedicated function CCPU_ChangeCCIEFBCycPrm function or MI Configurator ...

Page 292: ...clic transmission is stored Unit ms U3E0 G4623 Group No 3 minimum link scan time The minimum link scan time value during cyclic transmission is stored Unit ms U3E0 G4624 Group No 3 current link scan time The current link scan time value during cyclic transmission is stored Unit ms U3E0 G4625 System area U3E0 G4626 Group No 4 maximum link scan time The maximum link scan time value during cyclic tra...

Page 293: ... Third octet G4640 IP address If an IP address is not set in the parameter the values will be all 0 b0 to b7 Second octet b8 to b15 First octet G4647 Accumulated number of timeouts 0 No timeouts 1 to 65 535 Timeout count accumulated if the value exceeded 65 535 it returns to 1 G4648 Accumulated number of disconnection detection 0 No disconnections 1 to 65 535 Disconnected detection count accumulat...

Page 294: ...igured to the Ethernet port CH1 is stored G20004 b0 to b7 Fourth octet b8 to b15 Third octet G20005 b0 to b7 Second octet b8 to b15 First octet U3E0 G20006 to U3E0 G20013 System area U3E0 G20014 to U3E0 G20015 Subnet mask The subnet mask configured to the Ethernet port CH1 is stored G20014 b0 to b7 Fourth octet b8 to b15 Third octet G20015 b0 to b7 Second octet b8 to b15 First octet U3E0 G20016 to...

Page 295: ...712 to U3E0 G119953 Each bit corresponds to RY 1 bit Remote register RWw U3E0 G102048 to U3E0 G110239 RWw start numbers and point numbers for each station can be confirmed using the RWw offset size information U3E0 G119968 to U3E0 G120209 Page 296 RWw offset size information U3E0 G119968 to U3E0 G120209 Addre ss b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 U3E0 G 100000 RXF RXE RXD RXC RX...

Page 296: ...cial register SW U3E0 G118464 to U3E0 G118975 Addre ss b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 U3E0 G 110240 RWr0 U3E0 G 110241 RWr1 U3E0 G 118431 RWr1FFF Addre ss b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 U3E0 G 118432 SBF SBE SBD SBC SBB SBA SB9 SB8 SB7 SB6 SB5 SB4 SB3 SB2 SB1 SB0 U3E0 G 118463 SB1F F SB1F E SB1F D SB1F C SB1F B SB1F A SB1F 9 SB1F 8 SB1F 7 SB1F 6 SB1F 5...

Page 297: ...la With the exception of station No 0 Offset buffer memory address 119712 Station No 1 2 Size buffer memory address 119713 Station No 1 2 Address Description U3E0 G119456 Station No 1 RX offset U3E0 G119457 Station No 1 RX size word units U3E0 G119458 Station No 2 RX offset U3E0 G119459 Station No 2 RX word units U3E0 G119694 Station No 120 RX offset U3E0 G119695 Station No 120 RX size word units ...

Page 298: ...e exception of station No 0 Offset buffer memory address 120224 Station No 1 2 Size buffer memory address 120225 Station No 1 2 Address Description U3E0 G119968 Station No 1 RWw offset U3E0 G119969 Station No 1 RWw size word units U3E0 G119970 Station No 2 RWw offset U3E0 G119971 Station No 2 RWw size word units U3E0 G120206 Station No 120 RWw offset U3E0 G120207 Station No 120 RWw size word units...

Page 299: ...rk No 1 to 16 is stored Communication route establishment status network No 17 to 239 U3E0 G124481 to U3E0 124495 Communication route establishment information for each target station network No 17 to 239 is stored Address Description U3E0 G120512 Manufacturer code Own station master local module information is stored U3E0 G120513 Device type U3E0 G120514 Model code U3E0 G120515 Version Address De...

Page 300: ...e rate maximum station No 0 U3E0 G130344 Stores the maximum value for station No 0 to error frame reception occurrence rate PORT2 side line error occurrence rate current U3E0 G130352 to U3E0 G130472 Stores the current value for PORT2 error frame reception occurrence rate However the value is not stored in the own station No area PORT2 side line error occurrence rate current station No 1 to 120 U3E...

Page 301: ...MER_I8253 define DRV_TIMER_I8253_INSTANCE_0 define DRV_TIMER_IA_HPET define DRV_TIMER_IA_HPET_BUS define DRV_TIMER_IA_HPET_BUS_INSTANCE_0 define DRV_TIMER_IA_HPET_INSTANCE_0 define DRV_TIMER_IA_HPET_INSTANCE_1 define DRV_TIMER_IA_HPET_INSTANCE_2 define DRV_TIMER_IA_HPET_INSTANCE_COMPARATORS define DRV_TIMER_IA_HPET_INSTANCE_MAIN define DRV_TIMER_IA_TIMESTAMP define DRV_TIMER_IA_TIMESTAMP_INSTANCE_...

Page 302: ...RNCAT define INCLUDE_ANSI_STRNCMP define INCLUDE_ANSI_STRNCPY define INCLUDE_ANSI_STRTOD define INCLUDE_ANSI_TIME define INCLUDE_APPL_LOG_UTIL define INCLUDE_ARPAINETLIB define INCLUDE_ARP_API define INCLUDE_ATOMIC_OPERATORS define INCLUDE_AUX_CLK define INCLUDE_AVL_TREES define INCLUDE_AVL_UINT_TREES define INCLUDE_BANNER define INCLUDE_BASE_KERNEL define INCLUDE_BIOS_E820_MEM_AUTOSIZE define INC...

Page 303: ...LUDE_DEVMEM define INCLUDE_DISK_UTIL define INCLUDE_DISK_UTIL_SHELL_CMD define INCLUDE_DLL define INCLUDE_DMA_SYS define INCLUDE_DOSFS define INCLUDE_DOSFS_CACHE define INCLUDE_DOSFS_CHKDSK define INCLUDE_DOSFS_DIR_FIXED define INCLUDE_DOSFS_DIR_VFAT define INCLUDE_DOSFS_FAT define INCLUDE_DOSFS_FMT define INCLUDE_DOSFS_MAIN define INCLUDE_DOSFS_SHOW define INCLUDE_DOSFS_VOL_BIO_BUFFER_SIZE define...

Page 304: ...E_HASH define INCLUDE_HISTORY_FILE_SHELL_CMD define INCLUDE_HOOKS define INCLUDE_HOOK_SHOW define INCLUDE_HOST_TBL define INCLUDE_HPET_AUX_CLK define INCLUDE_HPET_TIMESTAMP define INCLUDE_HRFS define INCLUDE_HRFS_CHKDSK define INCLUDE_HRFS_DEFAULT_WRITE_MODE define INCLUDE_HRFS_FORMAT define INCLUDE_HW_FP define INCLUDE_HW_FP_MREGS define INCLUDE_HW_FP_SHOW define INCLUDE_HYPERVISOR_HVIF define IN...

Page 305: ... INCLUDE_IPIFCONFIG_CMD define INCLUDE_IPNET define INCLUDE_IPNET6_USE_MCAST_ROUTING define INCLUDE_IPNETSTAT_CMD define INCLUDE_IPNET_LOOPBACK_CONFIG define INCLUDE_IPNET_SOCKET define INCLUDE_IPNET_SYSCTL define INCLUDE_IPNET_USE_LOOPBACK define INCLUDE_IPNET_USE_MCAST_ROUTING define INCLUDE_IPNET_USE_NAT define INCLUDE_IPNET_USE_NETLINKSOCK define INCLUDE_IPNET_USE_ROUTESOCK define INCLUDE_IPNE...

Page 306: ..._DEFER define INCLUDE_JOB_QUEUE define INCLUDE_JOB_TASK define INCLUDE_KERNEL define INCLUDE_KERNEL_ARCH define INCLUDE_KERNEL_COMMON_HEAP define INCLUDE_KERNEL_PROXIMITY_HEAP define INCLUDE_LINKBUFPOOL define INCLUDE_LOADER define INCLUDE_LOADER_CODE define INCLUDE_LOADER_HOOKS define INCLUDE_LOAPIC_SYS_CLK define INCLUDE_LOCAL_AUTH define INCLUDE_LOGGING define INCLUDE_LOOPFS define INCLUDE_LSTL...

Page 307: ...efine INCLUDE_NETBUFPOOL define INCLUDE_NETMASK_GET define INCLUDE_NETPOOLSHOW define INCLUDE_NETSTAT define INCLUDE_NETWORK define INCLUDE_NET_BOOT define INCLUDE_NET_BOOT_CONFIG define INCLUDE_NET_DAEMON define INCLUDE_NET_DRV define INCLUDE_NET_HOST_SETUP define INCLUDE_NET_HOST_SHOW define INCLUDE_NET_INIT define INCLUDE_NET_POOL define INCLUDE_NET_REM_IO define INCLUDE_NET_SYSCTL define INCLU...

Page 308: ...SHOW define INCLUDE_POSIX_PTHREADS define INCLUDE_POSIX_SCHED define INCLUDE_POSIX_SEM define INCLUDE_POSIX_SEM_SHOW define INCLUDE_POSIX_SHM define INCLUDE_POSIX_SHM_API define INCLUDE_POSIX_SIGNALS define INCLUDE_POSIX_TIMERS define INCLUDE_POSIX_TIMER_SHOW define INCLUDE_POSIX_UMASK define INCLUDE_POSIX_USER_GROUP define INCLUDE_PSL_ITL_COMMON define INCLUDE_PTYDRV define INCLUDE_Q_FIFO define ...

Page 309: ...UNTING define INCLUDE_SEM_COUNTING_CREATE define INCLUDE_SEM_DELETE define INCLUDE_SEM_EVENTS define INCLUDE_SEM_EXCHANGE define INCLUDE_SEM_INFO define INCLUDE_SEM_LIB define INCLUDE_SEM_MUTEX define INCLUDE_SEM_MUTEX_CREATE define INCLUDE_SEM_OPEN define INCLUDE_SEM_READ_WRITE define INCLUDE_SEM_READ_WRITE_CREATE define INCLUDE_SEM_SHOW define INCLUDE_SHADOW_IDT define INCLUDE_SHELL define INCLU...

Page 310: ...efine INCLUDE_SYSTEMVIEWER_AGENT define INCLUDE_SYS_CLK define INCLUDE_SYS_HW_INIT_0 define INCLUDE_SYS_START define INCLUDE_SYS_TIMESTAMP define INCLUDE_SYS_WARM_BIOS define INCLUDE_TASK_CREATE_DELETE define INCLUDE_TASK_CREATE_HOOKS define INCLUDE_TASK_HOOKS define INCLUDE_TASK_HOOKS_SHOW define INCLUDE_TASK_INFO define INCLUDE_TASK_LIST define INCLUDE_TASK_OPEN define INCLUDE_TASK_RESTART defin...

Page 311: ..._SHELL_CMD define INCLUDE_VRFS define INCLUDE_VXBUS define INCLUDE_VXBUS_IOCTL define INCLUDE_VXBUS_PARAMS define INCLUDE_VXBUS_SHOW define INCLUDE_VXB_AUX_CLK define INCLUDE_VXB_SYS_CLK define INCLUDE_VXB_TIMESTAMP define INCLUDE_VXCPULIB define INCLUDE_VXDBG define INCLUDE_VXDBG_CPU_CONTROL define INCLUDE_VXDBG_HOOK define INCLUDE_VXDBG_MODULE define INCLUDE_VXDBG_RUNCTRL define INCLUDE_VXEVENTS...

Page 312: ...310 APPX Appendix 10 List of VxWorks Components define INCLUDE_XBD_PART_LIB define INCLUDE_XBD_RAMDRV define INCLUDE_XDR NAME component list ...

Page 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...

Page 314: ...Q Sensor Solution 39 L Link scan 83 Link scan time 44 83 93 Logical station number 51 M MAIN LED 115 116 Manager level 135 Monitoring time 18 98 O Operating status 101 R Refresh target device 80 Remote RESET 104 Remote RUN STOP 104 RWw RWr setting 178 196 RX RY setting 178 196 S SLMP command 37 SLMP supported device 36 Standalone development configuration 132 Station unit block guarantee 46 STOP R...

Page 315: ...I 313 MEMO ...

Page 316: ... Partial correction October 2018 SH NA 081932ENG C Partial correction October 2018 SH NA 081932ENG D Partial correction March 2019 SH NA 081932ENG E Partial correction This manual confers no industrial property rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may oc...

Page 317: ...been avoided if functions or structures judged as necessary in the legal safety measures the user s device is subject to or as necessary by industry standards had been provided 4 Failure that could have been avoided if consumable parts battery backlight fuse etc designated in the instruction manual had been correctly serviced or replaced 5 Failure caused by external irresistible forces such as fir...

Page 318: ...ows is either registered trademarks or trademarks of Microsoft Corporation in the United States and or other countries The company names system names and product names mentioned in this manual are either registered trademarks or trademarks of their respective companies In some cases trademark symbols such as or are not specified in this manual ...

Page 319: ......

Page 320: ...nge without notice When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permission HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHI KU NAGOYA JAPAN ...