background image

 

 

 

 

 

Floor Standing

Cooling Only (R410A,50/60Hz)

6CSP0-04A (Replace : 6CSP0-03C)

P/No.: MFL60778813

Summary of Contents for AP-Q100LFA0

Page 1: ...Floor Standing Cooling Only R410A 50 60Hz 6CSP0 04A Replace 6CSP0 03C P No MFL60778813 ...

Page 2: ...its the interi or design and maintains the harmony of the room Installation of floor standing unit is easy and it has very low oper ating noise Apart from that it has very special features such as child lock neuro fuzzy control logic dual plasma fil ter In installation field we can use this unit as the duct system also which makes it more dynamic and diversified than other units A lot of informati...

Page 3: ...Functions 4 Specifications 5 Dimensions 6 Piping Diagrams 7 Wiring Diagrams 8 Capacity Tables 9 The Coefficient of Capacity Change 10 Air flow and temperature distributions reference data 11 Operation Range 12 Sound Levels 13 Installation 14 Function of Remote Control ...

Page 4: ...pacity kW Refrigerant Model Name Power Supply V Ø Hz 36 10 5 R410A AP Q36GRA0 220 240 1 50 220 1 60 48 14 1 AP Q48GTA0 100 28 7 AP Q100LFA0 380 415 3 50 380 3 60 n 0 Series Nominal Capacity Class_Max kBtu h Rated Capacity kW Refrigerant Model Name Power Supply V Ø Hz 60 14 1 R410A AP Q60GT3E4 220 240 1 50 220 1 60 n 4 Series ...

Page 5: ...loor Standing Type Air Conditioner Function A Basic Model Type Q Inverter Cooling Only Set unit U Outdoor unit N Indoor unit n 0 Series A P Q 60 G T 3 E 4 Chassis Type Development Sequence Electric Standard Volts Freq Phase G 220 240V 1Ø 50Hz 220V 1Ø 60Hz L 380 415V 3Ø 50Hz 380V 3Ø 60Hz Nominal Cooling Capacity Max Ex 60 57 000 Btu h Type of Air Conditioner AP R410A Floor Standing Type Air Conditi...

Page 6: ...ontrol X X Electric heater X X High ceiling operation X X Auto Elevation Grille X X Reliability Hot start X X Self diagnosis O O Convenience Auto changeover X X Auto cleaning O O Auto operation artificial intelligence O O Auto Restart O O Child lock O O Forced operation X X Group control X X Sleep mode X X Timer on off O O Timer weekly X X Two thermistor control X X Individual control Standard Wir...

Page 7: ...l X X Electric heater X X High ceiling operation X X Auto Elevation Grille X X Reliability Hot start X X Self diagnosis O O Convenience Auto changeover X X Auto cleaning O X Auto operation artificial intelligence O O Auto Restart O O Child lock O O Forced operation X O Group control X X Sleep mode X X Timer on off O O Timer weekly X X Two thermistor control X X Individual control Standard Wired re...

Page 8: ...ion X X X O Restart delay 3 minutes O O O O Self diagnosis O O O O Soft start X X X X Test function O O O O Convenience Night Silent Operation O O X X CAC network function Network soluation LGAP O O O O Device APUQ36GRA0 APUQ48GTA0 APUQ100LFA0 APUQ60GT3E4 Central Controller PQCSZ250S0 PACEZA000 PACS5A000 PACP5A000 PACM5A000 PMNFP14A1 BNU Building Network Unit PLNWKB000 PQNFB17C0 ODU Dry Contact X ...

Page 9: ... 150 Running Current Indoor Unit only A 0 50 Casing Color Middle White Dimensions Body W x H x D mm 590 1 840 320 W x H x D inch 23 7 32 x 72 7 16 x 12 19 32 Net Weight Body kg lbs 36 0 79 4 Heat Exchanger Row x Column x Fins per inch x No 3 x 38 x 19 x 1 Face Area m2 ft2 0 30 3 26 Fan Type Sirocco Air Flow Rate SH H M L m3 min 23 5 21 0 17 0 14 0 SH H M L ft3 min 830 742 600 494 Fan Motor Type BL...

Page 10: ...Rated W Running Current Indoor Unit only A Casing Color Dimensions Body W x H x D mm W x H x D inch Net Weight Body kg lbs Heat Exchanger Row x Column x Fins per inch x No Face Area m2 ft2 Fan Type Air Flow Rate SH H M L m3 min SH H M L ft3 min Fan Motor Type Output W x No Dehumidification Rate l h pts h Sound Pressure Level SH H M L dB A Sound Power Level Cooling dB A Piping Connections Liquid mm...

Page 11: ...wer Supply Cable included Earth No x mm2 3C x 4 0 3C x 5 0 Casing Color Warm Gray Warm Gray Dimensions W x H x D mm 950 834 330 950 1 170 330 W x H x D inch 37 13 32 x 32 27 32 x 13 37 13 32 x 46 1 16 x 13 Net Weight kg lbs 65 0 143 3 83 0 183 0 Compressor Type Twin Rotary Twin Rotary Model Model x No GPT442MBA x 1 GPT442MBA x 1 Motor type BLDC BLDC Motor Output W x No Refrigerant Type R410A R410A...

Page 12: ...ections Power Supply Cable included Earth No x mm2 3C x 6 0 5C x 6 0 Casing Color Warm Gray Warm Gray Dimensions W x H x D mm 950 x 1 380 x 330 1 090 1 625 380 W x H x D inch 37 13 32 x 54 11 32 x 13 42 29 32 63 31 32 14 31 32 Net Weight kg lbs 82 0 180 8 143 0 315 0 Compressor Type BLDC INV Scroll BLDC INV Scroll Model Model x No RJA036MAA x 1 JBA068MAF x 1 Motor type BLDC BLDC Motor Output W x N...

Page 13: ...licable national codes 3 All electrical components and materials to be supplied on the site must comply with the local regulations or international codes 4 Electrical characteristics chapter should be considered for electrical work and design Especially the capacity of power cable and circuit breaker for outdoor unit should be more than that of electrical characteristics chapter Note PR4 Chassis A...

Page 14: ...ns or applicable national codes 3 All electrical components and materials to be supplied on the site must comply with the local regulations or international codes 4 Electrical characteristics chapter should be considered for electrical work and design Especially the capacity of power cable and circuit breaker for outdoor unit should be more than that of electrical characteristics chapter Note PT2 ...

Page 15: ...5 Dimensions 12 _ Floor Standing Floor Standing Floor Standing APNQ60GT3E4 PT3 Chassis ...

Page 16: ...s or applicable national codes 3 All electrical components and materials to be supplied on the site must comply with the local regulations or international codes 4 Electrical characteristics chapter should be considered for electrical work and design Especially the capacity of power cable and circuit breaker for outdoor unit should be more than that of electrical characteristics chapter Note PF2 C...

Page 17: ...5 Dimensions 14 _ Floor Standing Floor Standing Floor Standing 5 2 Outdoor Units U4 Chassis APUQ36GRA0 ...

Page 18: ...5 Dimensions Floor Standing _ 15 Floor Standing Floor Standing U5 Chassis APUQ48GTA0 ...

Page 19: ...5 Dimensions 16 _ Floor Standing Floor Standing Floor Standing U3 Chassis APUQ60GT3E4 ...

Page 20: ...5 Dimensions Floor Standing _ 17 Floor Standing Floor Standing APUQ100LFA0 U7 Chassis ...

Page 21: ...TH2 Th4 Thermistor for outdoor air temperature CN TH3 Th5 Thermistor for condensing temperature outlet CN TH3 Th6 Thermistor for condensing temperature mid CN TH1 Th7 Thermistor for discharge pipe temperature CN TH2 Th8 Thermistor for suction pipe temperature CN TH2 Service Valve Liquid Service Valve Gas Indoor Unit Refrigerant flow Cooling E E V Accumulator Compressor Outdoor Unit Th4 Th5 Th6 Th7...

Page 22: ...n Service Valve Gas Models AP Q48GTA0 Location Description PCB Connector Th1 Thermistor for indoor room temperature CN ROOM TH Th2 Thermistor for evaporator inlet temperature CN EVA TH Th3 Thermistor for evaporator outlet temperature CN EVA TH2 Th4 Thermistor for outdoor air temperature CN TH2 Th5 Thermistor for condensing temperature mid CN TH4 Th6 Thermistor for discharge pipe temperature CN TH3...

Page 23: ...are Connection Service Valve Gas Pressure Sensor Models AP Q60GT3E4 Location Description PCB Connector Th1 Thermistor for indoor room temperature CN ROOM TH Th2 Thermistor for evaporator inlet temperature CN EVA TH Th3 Thermistor for evaporator outlet temperature CN EVA TH2 Th4 Thermistor for outdoor air temperature CN_AIR Th5 Thermistor for condensing temperature mid CN_MID Th6 Thermistor for dis...

Page 24: ...r for discharge temperature CN_DISCHA_BK Th5 Thermistor for inlet air temperature CN_AIR_YL Th6 Thermistor for condensing temperature CN_MID_BR Pressure Sensor CN_H_PRESS_RD Refrigerant Flow Cooling M Accumulator Inverter Compressor Strainer Strainer Pressure Sensor Outdoor Unit Strainer Electronic Expansion Valve S Oil Seperator Th4 Th6 Th5 Th2 Th1 Th3 Indoor Unit Refrigerant flow Cooling Fan M S...

Page 25: ...22 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q36GRA0 ...

Page 26: ...Floor Standing _ 23 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q48GTA0 ...

Page 27: ...24 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q60GT3E4 ...

Page 28: ...Floor Standing _ 25 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q100LFA0 ...

Page 29: ...2 12 04 8 96 3 59 11 51 8 52 3 94 11 19 8 42 3 86 10 88 8 20 3 46 16 0 22 0 14 68 10 45 3 11 14 07 10 13 3 14 13 26 9 76 3 79 12 88 9 63 4 07 12 35 9 19 4 24 12 03 9 10 4 04 11 72 8 87 3 51 18 0 25 0 15 53 10 82 3 36 14 92 10 51 3 38 14 10 10 15 3 98 13 72 10 04 4 22 13 19 9 60 4 30 12 87 9 52 4 03 12 55 9 30 3 42 19 0 27 0 15 95 11 09 3 40 15 34 10 78 3 43 14 52 10 43 4 03 14 10 10 29 4 15 13 61 ...

Page 30: ...9 92 8 91 24 52 19 25 9 69 23 45 18 66 10 64 22 80 18 01 10 70 22 16 17 45 9 36 16 0 22 0 29 89 21 73 8 40 28 66 21 08 8 89 27 01 20 30 10 24 26 23 19 65 11 00 25 15 19 11 11 47 24 51 18 47 11 19 23 86 17 93 9 47 18 0 25 0 31 63 21 92 9 08 30 39 21 31 9 13 28 72 20 59 10 75 27 94 19 95 11 40 26 86 19 45 11 63 26 22 18 84 11 18 25 57 18 32 9 49 19 0 27 0 32 49 22 12 9 18 31 25 21 51 9 26 29 58 20 8...

Page 31: ...it Qactual Q Ti To x Fpiping Notes Equivalent pipe length m actual pipe length m number of band x 0 3 m 1 Rate of change in capacity due to the pipe length Capacity coefficient factor for piping length Capacity class kBtu h by Model name Pipe length m 5 7 5 10 15 20 25 30 35 40 45 50 Capacity coefficient factor for piping length Fpiping 36 48 1 000 1 000 0 993 0 980 0 967 0 953 0 940 0 927 0 914 0...

Page 32: ...1 2 0 5 0 25 0 25 0 25 2 5 0 25 0 25 Air velocity m s Temperature C 10m 8m 6m 10m 8m 6m 2 7m 2m 1m 0m 4m 2m 0m 2 7m 2m 1m 0m 4m 2m 0m Models APNQ36GRA0 Models APNQ48GTA0 Discharge Angle 90 0 5 0 5 0 5 0 5 0 25 0 25 0 25 2 1 1 1 3 4 2 5 24 22 20 20 22 18 16 14 3 5 1 5 Air velocity m s Temperature C 10m 8m 6m 10m 8m 6m 3 2m 2m 1m 0m 4m 2m 0m 3m 0m 4m 2m 0m 3 2m 2m 1m 3m ...

Page 33: ... 19 15 16 14 19 18 18 17 20 Air velocity m s Temperature C 2 7m 2m 1m 0m 0m 2 7m 2m 1m 0m 8m 6m 4m 2m 8m 6m 4m 2m 1m 3m 5m 7m 0m 7m 5m 3m 1m Models APNQ100LFA0 Discharge Angle 90 0 5 0 5 0 5 1 5 1 5 2 5 3 5 2 5 0 5 1 1 1 1 2 2 3 4 0 25 16 18 20 18 20 22 14 0 25 0 25 0 25 0 5 0 5 Air velocity m s Temperature C 10m 8m 6m 10m 8m 6m 3 2m 2m 1m 0m 4m 2m 0m 3m 0m 4m 2m 0m 3 2m 2m 1m 3m ...

Page 34: ...Floor Standing _ 31 Floor Standing Floor Standing 11 Operation Range 10 14 48 118 18 64 32 90 Indoor Unit C F DB Outdoor Unit C F DB Continuous operation g n i l o o C ...

Page 35: ... Model Sound Levels dB A SH H M L APNQ36GRA0 52 48 44 41 APNQ48GTA0 53 50 47 43 APNQ60GT3E4 53 50 47 45 APNQ100LFA0 58 55 51 Octave Band Center Frequency Hz Octave Band Sound Pressure Level 0dB 20μPa 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold Octave Band Center Frequency Hz Octave Band S...

Page 36: ...Sound Levels APNQ100LFA0 Octave Band Sound Pressure Level 0dB 20μPa 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency Hz NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold ...

Page 37: ...und Levels dB A APUQ36GRA0 54 APUQ48GTA0 55 APUQ60GT3E4 59 APUQ100LFA0 60 Octave Band Center Frequency Hz Octave Band Sound Pressure Level 0dB 20μPa 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold Octave Band Center Frequency Hz Octave Band Sound Pressure Level 0dB 20μPa 10 20 30 40 50 60 70 ...

Page 38: ...Sound Levels APUQ100LFA0 Octave Band Center Frequency Hz Octave Band Sound Pressure Level 0dB 20μPa 10 20 30 40 50 60 70 80 63 125 250 500 1000 2000 4000 8000 NC 15 NC 20 NC 25 NC 30 NC 35 NC 40 NC 45 NC 50 NC 55 NC 60 NC 65 Approximate Hearing Threshold ...

Page 39: ...ly 300mm 300mm 300mm 50 mm 50 mm 1 000 mm 400 mm 13 1 Select the best location 13 1 1 Indoor Unit There should not be any heat source or steam near the unit There should not be any obstacles to prevent the air circulation A place where air circulation in the room will be good A place where drainage can be easily obtained A place where noise prevention is taken into consideration Do not install the...

Page 40: ...s no direct influence of snow or rain Place with no danger of snowfall or icicle drop Place without weak floor or base such as decrepit part of the building or with a lot of snow accumulation Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid frequent flood ed area Ensure that the space around the back is more than 300 mm on the opposite side to the...

Page 41: ...s 2 If there is any vibration transmitted to the building mount the rubber underneath the outdoor unit Refrigerant amount Before shipment this air conditioner is filled with the rated amount of refrigerant including additional amount required for air purging subject to 7 5m piping length The rated amount of refrigerant is indicated on the name plate But when the piping length exceeds 7 5 meters ad...

Page 42: ...ng Refer to figure 3 1 Plug the pipe through holes with putty or insulation material procured locally to stop up all gaps as shown in the figure 3 2 Insects or small animals entering the outdoor unit may cause a short circuit in the electrical box Continuous Torque wrench 250mm Pipe Size Torque 1 4 16 2 N m 3 8 38 4 N m 1 2 55 6 N m 5 8 75 7 N m 3 4 110 10 N m Forward Sideways Backward Figure 1 Ga...

Page 43: ...pen the control cover with Driver Trap Seal a small opening around the pipings with gum type sealer OUTDOOR UNIT Trap is required to prevent water from entering into electrical parts Taping Drain hose Pipings Connecting cable Power supply cord Plastic Plastic band band Plastic band Seal a small Seal a small opening around opening around the pipings with the pipings with gum type sealer gum type se...

Page 44: ... 1 L 2 N 3 Make sure the rubber bushes are Properly used in knock out holes after connecting main Power cable Connecting cable terminal Power cord terminal Cord clamp Cord clamp Make sure the rubber bushes are Properly used in knock out holes after connecting main power cable Connecting cable terminal Power cord terminal Cord clamp Make sure the rubber bushes are Properly used in knock out holes a...

Page 45: ...er source and unit A disconnection device to adequately disconnect all supply lines must be fitted For service operations The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could give rise t...

Page 46: ...tion refer to Outdoor Unit Installation Guide at the Seaside CAUTION 13 5 Installation guide at the seaside 13 5 1 Selecting the location Outdoor Unit 1 If the outdoor unit is to be installed close to the sea shore direct exposure to the sea breeze should be avoided Install the outdoor unit on the apposite side of wind blowing 2 Even if it is unavoidable to install the outdoor unit on the seaside ...

Page 47: ...er ON OFF button Operation will start when this button is pressed and stop when the button is pressed again 3 Indoor fan speed button To select the desired fan speed 4 Temperature setting button 5 A Cooling button 6 Auto cleaning button 7 D Dehumidification button Can effectively remove humidity when at the time of rainy season or high humidity 8 C Auto operation button In operation this function ...

Page 48: ...ics Inc 128 Yeoui daero Yeongdeungpo gu Seoul Korea 07336 http partner lge com The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance and ISO14001 certificate for environmental management system The specifications designs and information in this brochure are subject to change without notice ...