power distribution unit

kit

fits hp 19-inch racks

E7671A
E7674A
E7675A
E7676A

Summary of Contents for E7671A

Page 1: ...power distribution unit kit fits hp 19 inch racks E7671A E7674A E7675A E7676A ...

Page 2: ...CHECK THE VOLTAGE before connecting any equipment to the PDU Failure to check the voltage could lead to severe equipment damage The voltage of the PDU receptacles equals the voltage of the receptacle to which the PDU is connected This voltage must be within the input voltage range of the equipment installed in the rack n CHECK THE POWER SOURCE RECEPTACLE to be sure it is installed near the rack an...

Page 3: ...forms to the following Product Specifications Safety IEC 950 1991 A1 A2 A3 A4 EN 60950 1992 A1 A2 A3 A4 Supplementary Information The product herewith complies with the requirements of the Low Voltage Directive 73 23 EEC and 93 68 EEC and carries the CE Marking accordingly Mt View CA 94043 1 November 2002 Location Date Susan Kipers Business Manager For Compliance Information European Contact Your ...

Page 4: ...DU E7675 63001 16 amp PDU E7676 63001 16 amp PDU 4 1 5981 1470EN Installation guide Tools Needed T 25 Torx driver Overview The HP Power Distribution Units PDUs are designed to provide flexibility for your power requirements The PDUs can be mounted both vertically and horizontally on the rear rack columns depending on your rack configuration Use the EIA holes for horizontal mounting and the accesso...

Page 5: ...5 Overview ...

Page 6: ...s to the equipment Note If the PDU will be used to connect to the wall outlet be sure to place the PDU toward the bottom of the rack This allows the cable to extend easily out the bottom of the rack under the rear door if a rear door is installed 2 Attach the PDU to the accessory outside holes in the rack column with the Torx screws and hex nuts Use the hex inserts located toward the top and botto...

Page 7: ...es on the inner edge of the rack column for this configuration 1 Determine where you will place the PDU on the rear rack columns usually across the top or across the bottom Consider if you need access to any of the rack equipment then locate the PDU so the power cables do not hinder access to the equipment Note If the PDU will be used to connect to the wall outlet be sure to place the PDU toward t...

Page 8: ...he power cables from the devices to the PDU 5 When connecting the PDU to the wall outlet or UPS be sure to secure the main power cable with the clamp as shown in the figure below 6 Plug main cable into wall outlet or UPS 7 Turn on power to devices Note If the PDU is placed at the bottom of a rack containing ballast the sockets on the PDU must be facing the top of the rack 8 Installation Tighten cl...

Page 9: ...tallation according to local electrical and building codes Optional Cables P N Voltage Current Connector Plug Type Length E7742A 250V 10AMP C13 C14 2 5m 8 2 E7743A 125V 10 AMP C13 5 15P 2 5m 8 2 E7798A 250V 16AMP C19 C20 2 5m 8 2 E7802A 125V 16AMP C19 5 20P 4 5m 14 8 E7803A 250V 16AMP C19 L6 20P 4 5m 14 8 E7804A 250V 16AMP C19 C20 4 5m 14 8 E7805A 250V 16AMP C19 L6 30P 4 5m 14 8 E7806A 250V 16AMP ...

Page 10: ...ange without notice Copyright Hewlett Packard Company 2002 All Rights Reserved Reproductions adaptations or translation without prior written permission is prohibited except as allowed under the copyright laws November 2002 Document Part Number 5981 1470EN ...