DUAL TEMPERATURE SENSOR 

 

INSTALLATION AND OPERATING INSTRUCTIONS 

 

INTRODUCTION

 

The Honeywell Ademco

 

TS300 is a hardwired temperature monitor able to accurately detect variations in temperature. It 

can monitor the temperature at the unit and at a remote location (using a T280R) simultaneously. Alarm annunciations 
include a local piezo sounder and two programmable NO/NC outputs which activate when the mapped high or the low 
limit(s) is exceeded, protecting equipment, property, and perishable items.  The NO/NC alarm outputs may be delayed by 
increments of one minute to allow for expected momentary temperature variations such as during a refrigeration unit's 
defrost cycle. The audible alert, if programmed, sounds when the temperature limit is violated and can be silenced with 
the press of a button for a programmed duration. The TS300 can accurately monitor any temperature within the range 
from 32

°

F to 140

°

F (0

°

C to 60

°

C).  A T280R Remote Temperature Probe may be used to monitor temperature within the 

range from -40

°

F to 140

°

F (-40

°

C to 60

°

C) or to monitor temperature in a harsh environment.

 

 

INSTALLATION

 

Mount the unit on a wall at a convenient viewing height. For accurate temperature sensing at the unit, do not mount the 
TS300 near any heat or cooling source. If the unit does not trip the panel, insure that the contact configuration (NO/NC) 
as defined in the Setup Procedure agrees with that of the zone to which it is connected.  

 

TO THE INSTALLER

 

Regular maintenance by the installer and frequent testing by the user are vital to continuous satisfactory operation of any 
alarm system.  The TS300 and the T280R should be tested periodically, at least once a month, depending on conditions. 
The installer should assume the responsibility of developing and offering a regular maintenance program to the user as 
well as acquainting the user with the proper operation and limitations of the alarm system and its component parts.  
Recommendations must be included for a specific program of frequent testing to ensure the system's proper operation at 
all times.

 

 
 

 

 

Illustration A 

 
SETUP PROCEDURE

 

Remove the front cover from the TS300.  With power applied to the unit, press the SETUP MODE switch (see Illustration 
A). Press the Left button to lower a numeric limit by a value of one (press and hold to decrement by tens); Press the right 
button in raise a numeric limit by a value of one (press and hold to increment by tens). Pressing either button will toggle 
the either/or choices. When your preferred setting is displayed, press the setup button to accept and move to the next 
parameter

 

Note that, when setting High/Low limits in Centigrade mode, incrementing/decrementing will raise/lower the limit by the 
equivalent of 1

°

 Fahrenheit (or 10

°

 F, if button is pressed and held). 

 

 

 

Summary of Contents for TS300

Page 1: ...he unit does not trip the panel insure that the contact configuration NO NC as defined in the Setup Procedure agrees with that of the zone to which it is connected TO THE INSTALLER Regular maintenance by the installer and frequent testing by the user are vital to continuous satisfactory operation of any alarm system The TS300 and the T280R should be tested periodically at least once a month depend...

Page 2: ...obe map See Table 2 for map designations 3 Hysteresis provides a buffer so that temperature that is shifting back and forth around the alarm limit point will not create multiple alarms You set the of degrees that the temperature will have to rise above the temperature low limit set point or drop below the high limit set point for the alarm to turn off For example if you set the HYS at 3 degrees an...

Page 3: ...er the selected delay time has expired If the delay time is set to 0 the alarm will be immediate The maximum delay time is 255 minutes 4 hours 15 minutes The output will remain in its alarm state until the temperature returns to within the selected limits as buffered by the programmed degrees of hysteresis As long as the temperature remains outside the selected temperature limits the display will ...

Page 4: ...uropean union harmonization legislation Logo de conformité CE Ce produit est conforme à la législation d harmonisation dans l Union européenne pertinente CE Richtlinien L ogo Dieses Produkt stimmt mit den relevanten Harmonisierungs gesetzen der EU überein Logotipo de cumplimiento de CE Este producto cumple con la legislación de uniformidad de la Unión Europea pertinente Logo conformità CE Questo p...

Reviews: