KSL 

Compact Electronic Air Flow Switch 

 

PRODUCT DATA 

 

GENERAL 

These highly reliable compact electronic flow switches are 
designed for detecting air flow in ducts or pipes. 
The device's sensitivity is adjusted using a potentiometer. 
When the air flow speed reaches a customer-preselected 
threshold value (switchpoint), the device switches an 
electronic circuit. The switching state is indicated by an LED. 
 

FEATURES 

  PG7 connection for easy mounting directly to ducts. 

  No moveable parts in the detection zone. 

 Temperature-compensated 

operating 

range. 

  Highly resistant to contamination and corrosion. 

 

DIMENSIONS 

56

10

15

140

82

47

Ø 10

21.5

47

PG7

TIGHTENING

SCREW

DEPRESSION

INDICATING

DIRECTION OF

FLOW

CIRCULAR

MOUNTING

BRACKET

Ø 4 mm

M16x1.5

LATERAL

HOLE

CENTRIC

HOLE

 

Fig. 1. KSL, dimensions (mm) 

 

SPECIFICATIONS 

Type 

KSL-230 

KSL-24 

Media air 

air 

Power supply 

230/240 VAC ±10% 

24 VAC/DC ±10% 

Power indication 

green "voltage" LED 

green "voltage" LED 

Power consump. 

4 VA 

4 VA 

Ambient temp. 

-20 ... +60 °C 

-20 ... +60 °C 

Medium temp. 

-10 ... +80 °C 

-10 ... +80 °C 

Relay contact 

SPDT 

SPDT 

Contact load 

250 VAC, 10(2) A 

250 VAC, 10(2) A 

Switch indication 

yellow "air flow" LED 

yellow "air flow" LED 

60-sec electrical 
outage protection 

ON/OFF (jumper) 

ON/OFF (jumper) 

Outage prot. ind. 

Yellow "time" LED 

Yellow "time" LED 

Setpt. adjustment 

potentiometer 

potentiometer 

Range 

0.1 … 30 m/sec 

0.1 … 30 m/sec 

Response time 

1…10 sec 

1…10 sec 

Immersion depth 

130 mm 

130 mm 

Max. pressure 

10 bar 

10 bar 

Process connec-
tion 

PG7 + circular 
mounting bracket 

PG7 + circular 
mounting bracket 

Housing IP 

IP 65 

IP 65 

Sensor IP 

IP 67 

IP 67 

Protection class  

II 

II 

Wiring terminals  

5 x 2.5 mm

2

 

5 x 2.5 mm

2

 

Probe material 

MS58 nickel-plated 

MS58 nickel-plated 

Weight 

400 g 

400 g 

 

MOUNTING 

  Select a mounting location in an area of calm flow. 

Specifically, the device should not be mounted 
immediately upstream or downstream from bends 
(upstream calming distance = approx. 5X the duct 
diameter; downstream calming distance = approx. 3X the 
duct diameter). Vertical and horizontal mounting possible. 

  After selecting an appropriate mounting location, securely 

fix the circular mounting bracket into place on the duct 
using at least two screws. 

  Now slide the probe through the 10-mm centric hole in the 

circular mounting bracket until the tip of the probe is at the 
proper depth (in the middle of the duct). 

  Rotate the device to ensure that the air flows through the 

lateral opening at the tip of the probe. Specifically, the 
small depression (see Fig. 1) should face 

towards

 the 

oncoming air. 

  Finally, securely fix the device in place using the 

tightening screw (see Fig. 1). 

  Maintenance: The sensor should be cleaned regularly by 

immersion in soapy warm water for about 10 minutes 
under warm water flow using a clean rag. Do not use 
screwdrivers or other hard tools to clean the sensor! 

 