Installation: 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mounting methods 

ImperLED E luminaries can be surface mounted on walls or ceilings. For these mounted installations, special 

accessories are included. A recessed kit is also available.

 

 

Step 1: Place a flat blade screwdriver and pull up gently the 6 diffusor clips from both sides to remove the 

diffusor. 

Step 2: Place a flat blade screwdriver and pull up gently the reflector. 

Step 3: Install the plastic base with the included mounting screws and plugs. If the hole that exists is not useful, 

drill another hole on one of the designated positions in order to pass the cables and install the included 

gasket (verify that it is not deformed). 

Step 4: Always use in any case round cable, with a diameter of 5-10mm (H05RN-F type 2x1mm

2

 or any other 

type, at least equal to its mechanical and electrical properties). ATTENTION! The cable must not be 

deformed in any way (this requirement is important to ensure the IP rating). 

Make a hole in the center by using a small screwdriver. Pass the round cable through the gasket. 

Step 5: Connect the mains cable to the respective terminal block: L for live wire, N for neutral. Power supply 

cables cross section should be 0.8 – 3 mm

2

. The C1 and C2 terminals are used for elBus communication 

(optional), DALI communication (optional) or voltage-free contact (optional). 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

ImperLED E

 

GB 

Dimensional drawings: 

 
                                                                                                                                                                                         

 

Summary of Contents for ImperLED E

Page 1: ... of the designated positions in order to pass the cables and install the included gasket verify that it is not deformed Step 4 Always use in any case round cable with a diameter of 5 10mm H05RN F type 2x1mm2 or any other type at least equal to its mechanical and electrical properties ATTENTION The cable must not be deformed in any way this requirement is important to ensure the IP rating Make a ho...

Page 2: ...r on the luminaire PICTOGRAM INSTALLATION Step 1 Place a flat blade screwdriver and pull up gently the diffusor clips from both sides to remove the diffusor Step 2 Install the pictogram you need in the diffusor and refit it to the luminary In case you need to change the pictogram follow the same procedure Step 3 Fill in the letter G on the specification label Note In case of battery replacement th...

Page 3: ...on test is performed This test will last for 60 minutes and can only be performed when the battery is fully charged steady green indicator LED The light source will be lit and the yellow indicator LED will flash during this test sequence Fault reset Activate the magnetic contact for a period lasting between 10 and 15 seconds to delete all indicated errors Then the luminaire enters regular operatio...

Page 4: ...n av de avmerkede plassen Monter nippel påse at den ikke er deformert Pkt 4 Benytt alltid rund kabel med en diameter på 5 10mm H05RN F type 2x1mm2 eller annen type tilsvarende minst de mekaniske og elektriske egenskapene MERK Kabelen må på ingen måte være deformert dette er viktig for å opprettholde armaturens tetthet Lag et hull i nippelen med en liten skrutrekker tre den runde kabelen gjennom ni...

Page 5: ...e IP65 tetthet Slå på nettspenningen PIKTOGRAMINSTALLASJON Pkt 1 Bruk en flatspor skrutrekker til forsiktig å trekke opp de 6 låseklipsene på lampedekslet Ta av lampedekslet Pkt 2 Installer valgt piktogram i lampedekslet og monter tilbake dekslet Dersom du behøver å bytte ut piktogrammet følg samme prosedyre Pkt 3 Fyll inn bokstaven G på spesifikasjonsetiketten Merk Dersom batteriet skal skiftes u...

Page 6: ...rikapasitetstest Denne testen varer i 60 minutter og kan kun utføres om batteriet er fullt oppladet grønn LED lyser fast Armaturen vil lyse i denne perioden og gul LED blinke Feilreset Aktiver magnetkontakten kontinuerlig i en periode på mellom 10 og 15 sekunder for å slette alle indikerte feil Armaturen går deretter over i normal drift ImperLED E Combi ST LED 230V 1h wPict 10y Artikkelnr 290406 1...

Page 7: ...ngshålet inte passar ska ett nytt hål borras på en av de markerade platserna Montera genomföringen se till att den inte är deformerad Steg 4 Använd alltid en rund kabel 5 10 mm i diameter H05RN F typ 2x1mm2 eller annan typ motsvarande åtminstone de mekaniska och elektriska egenskaperna OBS Kabeln får inte på något sätt deformeras detta är viktigt för att bibehålla armaturens täthet Gör ett hål i g...

Page 8: ...ATION Steg 1 Använd en platt spårskruvmejsel för att försiktigt dra upp de 6 låsklämmorna på lampskyddet Ta bort lampskyddet Steg 2 Montera det valda piktogramet i lampskyddet och sätt tillbaka locket Om du behöver byta ut piktogramet följ samma procedur Steg 3 Ange bokstaven G på specifikationsetiketten Notera Vid ett batteribyte måste det ersättas med ett nytt av samma typ och kapacitet Bytet sk...

Page 9: ...lan 5 till 10 sekunder startas ett test av batterikapaciteten Testet pågår under 60 minuter och kan endast startas när batteriet är fullt uppladdat grön diod lyser konstant Armaturens LED lampa tänds upp och den gula indikeringsdioden blinkar under testperioden Återställning av fel Aktivera magnetkontakten kontinuerligt under en period mellan 10 till 15 sekunder för att återställa eventuella felin...

Reviews: