background image

Customised Mimic

Zonal Mimic

A Vigilon A3 Mimic panel (VIG-MIM-A3) must be
connected to a loop circuit of a Vigilon fire detection and
alarm system. It is used to provide indication of fire
events in the system. However it can also be used to
provide indication of fault and supervisory events in the
system. The panel can be mounted in landscape or
portrait orientation.

A Customised Mimic holds a pictorial overlay that
represents the protected building or an area within. A fire
event is indicated by the illumination of appropriate red
LEDs behind the overlay to show the location of the fire.

A Zonal Mimic provides a traditional zone by zone
indication of a fire. Each zone is given a location label to
identify the area within a building.

The panel illumination defaults to a Zonal Mimic but can
be reprogrammed during commissioning to be a
Customised Mimic. An array of red lights illuminates
individually or in groups. Illuminations may be applied to
include custom shapes, text and digital clock in small or
large size. A site specific 'welcome message' may be
configured for display during quiescent conditions that
can scroll if it is too long to fit the display area. First or
last fire flashing option, with in phase or anti phase flash.

The panel has its own mains derived power supply with
battery for standby power in the event of mains supply
failure.

Technical Data

Panel dimensions

height 403mm, width 338mm,
depth 101mm

Weight

7.9Kg without batteries
10.5Kg with batteries

Storage temperature

-10 to 55ºC

Operating temperature 0 to 45ºC

Relative humidity
(Non condensing)

Up to 90% temperature
5 - 45°C

Battery

2 x 6V 7Ah sealed lead acid
(weight 1.3Kg each)
The integral battery provides
power for 72 hours in standby
condition and a further
30 minutes in alarm.

Mains operating
voltage

230V 50Hz +10% -6%

Emission

BS EN61000-6-3 : 2001

Immunity

BS EN50130-4 : 1996 : Part 4

LVD

BS EN 60950-2006

Ingress protection

IP30 (estimated)

Colour

Door - Pantone 422
Back box - Graphite Grey

(RAL 7024)

Control

Cancel fault buzzer / lamp test
button

Indicators

1536 high intensity RED LEDs.

Loop connection

3-way connection to a loop
circuit

Maximum number per
loop
(A maximum load
factor of 1000 allowed
per Vigilon loop circuit)

Maximum number of combined
repeat and mimic panels per
loop = 4
load factor per panel = 3

Typical Mimic illuminations

4188-945_issue 2_05/10_pt1_A3 Mimic

1

Data and Installation

Vigilon A3 Mimic panel

VIG-MIM-A3

by Honeywell

Flashing in phase
or anti phase

Customised Mimic

Zonal Mimic

ZONE n

Zone in fire

- steady indication

Latest zone in fire

- flashing indication

Summary of Contents for Gent Vigilon A3 Mimic

Page 1: ...ast fire flashing option with in phase or anti phase flash The panel has its own mains derived power supply with battery for standby power in the event of mains supply failure Technical Data Panel dimensions height 403mm width 338mm depth 101mm Weight 7 9Kg without batteries 10 5Kg with batteries Storage temperature 10 to 55ºC Operating temperature 0 to 45ºC Relative humidity Non condensing Up to ...

Page 2: ...to the top side of the inner door 1 Set Mounting the backbox The A3 Customised Mimic panel can be mounted either landscape or portrait while an A3 Zonal mimic panel must only be mounted landscape when using the overlay supplied a Locate the package Back box assembly u Landscape orientation Portrait orientation b Knock out the required cable entry points from the back box c Mark out the 4 back box ...

Page 3: ...d j from the back box to the inner door assembly Connect the flat flexible cable k to socket P13 on the Master Repeat Card see details on fitting and remove of flat flexible cable How to disconnect a flat flexible cable Hold the locking tab by the edges at positions j and lift it upwards one side at a time k to disengage the flat flexible cable Then remove the cable l from the socket How to connec...

Page 4: ...he overlay in place using the magnetic strip The overlay is secured in place when the outer cover is fitted to the panel How to fit the outer cover Hook the Outer Cover over the top edge of the Back Box Close the bottom of the Outer Cover onto the Back box and secure the Outer Cover by the two captive screws on the cover using the key supplied Ensure the zonal mimic or customised mimic plan is loc...

Reviews: