background image

MOUNTING

The AMM-4F mounts directly to 4-inch square electrical boxes (see Figure 2). 
The box must have a minimum depth of 2

1

8

 inches. Surface mounted electri-

cal boxes (SMB500) are available from Gamewell-FCI.

FIGURE 2. MODULE MOUNTING:

NOTE: For UL Listed security installations, the AMM-4F must be mounted 
within the control panel enclosure.

ISOLATED 

QUADRANT

C1066-00

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and 
regulations. This module is intended for power limited wiring only.

1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.  Set the address on the module per job drawings.
3.   Secure module to electrical box (supplied by installer), shown in Figure 2.

Specifications

Normal Operating Voltage: 

15 to 32 VDC

Maximum Current Draw: 

5.0 mA (LED on) 

Average Operating Current: 

375µA (Velociti Mode); 350µA (CLIP Mode); 600µA; (communicating IDC shorted)

EOL Resistance: 

47K Ohms

Maximum IDC Wiring Resistance: 

1,500 Ohms

Maximum IDC Voltage: 

11 Volts

Maximum IDC Current: 

450µA

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 4

1

2

˝ H x 4˝ W x 1

1

4

˝ D (Mounts to a 4˝ square by 2

1

8

˝ deep box.)

Accessories: 

SMB500 Electrical Box

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to 
the control panel installation manual for detailed system information. If the 
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

The AMM-4F Monitor Module is intended for use in intelligent, two-wire sys-
tems, where the individual address of each module is selected using the built-
in rotary switches. It provides either a 2-wire or 4-wire fault tolerant initiating 
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Gamewell-FCI system control panel (list available from Gamewell-FCI).

FIGURE 1. CONTROL AND INDICATORS:

C1067-00

INSTALLATION AND MAINTENANCE INSTRUCTIONS

AMM-4F Monitor Module

I56-3553-003

12 Clintonville Road, Northford, CT  06472

(203) 484-7161; Fax:  (203) 484-7118

www.gamewell-fci.com

Velociti

®

 Series

  

I56-3553-003 

 

 02-10

Reviews: