background image

IPOTS-COM IP/POTS Digital Communicator

Product Installation Document

PN LS10184-000GE-E:B   6/6/2018   18-244

1

 

Description

The IP/POTS Communicator card transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched 
telephone network and/or 

I

nternet protocol. It also allows remote programming or interrogation of the control panel using AlarmNet®.

2

 

Installation

2.1  50 Point and 198 Point Panel Installation

1.

Disconnect all power from the fire panel.

2.

Remove the two screws at the bottom of the board that are used to attach the board to the chassis.

3.

Replace the screws with two 3/4” standoffs from the hardware kit.

4.

Insert the plastic PCB spacer into the hole marked “Communicator Support”.

5.

Install the 5” cable from the hardware kit into the header on the main PCB marked “Communicator” and the header on the IPOTS-COM
labeled “Main Board Int” as shown below.

6.

Holding the IPOTS-COM on an angle, align the pins on the plastic keypad bezel to the holes on the sides of the communicator.

7.

Lay the IPOTS-COM flat and snap it onto the PCB spacer.

!

WARNING: THIS SYSTEM CONTAINS STATIC SENSITIVE COMPONENTS

WEAR A PROPER GROUNDING WRIST STRAP AND WORK ON A STATIC-SAFE WORKSPACE TO PROTECT
ELECTRONIC ASSEMBLIES.

RTN-

OUT-

COMMUNICATOR

DISPLAY

24V

RTN+

OUT+

BATTERY

N/L2

EARTH

H/L1

USB-A

C

NO

NC

C

NO

NC

C

NC

NO

SUPV

TRBL

ALRM

ANN-LC

SLC

RMT SYNC

ANN-BUS PRI

ANN-BUS SEC

NAC4

NAC3

NAC2

NAC1

@

Remove screws and install standoffs

Insert PCB spacer

Plastic pins

Cable
header