5/21/2015                             Rev:

Distributed Audio Amplifiers

ECC-50DA/E

ECC-125DA/E

ECC-50BDA

Installation Manual

firealarmresources.com

Summary of Contents for Fire-Lite Alarms ECC-125DA

Page 1: ...D P N LS10027 000FL E D ECN 15 270 Document LS10027 000FL E 5 21 2015 Rev Distributed Audio Amplifiers ECC 50DA E ECC 125DA E ECC 50BDA Installation Manual firealarmresources com ...

Page 2: ...quate warning of a fire Smoke detectors cannot be expected to provide adequate warn ing of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materi als etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate ...

Page 3: ...sconnect AC power and batteries prior to removing or inserting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former or printed circuit board location D...

Page 4: ...e version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed man...

Page 5: ...Wiring Lengths 19 Class B Style Y 19 Class A Style Z 20 2 1 5 Audio Riser Wiring 21 2 1 6 Data BUS Wiring 22 2 1 7 Connecting AC Power 23 2 1 8 Backup Battery 24 2 1 9 Calculating Current Draw and Standby Battery 25 Section 3 ECC 50BDA Backup Remote Amplifier 26 3 1 UL 464 Low Frequency Sounders 26 3 2 Installation 26 3 2 1 Board Layout 27 3 2 2 Mounting the Cabinet 28 3 2 3 Installing the Optiona...

Page 6: ...set up in user programming Refer to the programming section of the ECC 50 100 Instruction Manual LS10001 000FL E 1 1 1 Board Layout Figure 1 1 shows the location of terminals dip switch and circuit expander connection used in the installation of the ECC 50DA NOTE The term ECC 50DA is used in this manual to refer to both the ECC 50DA 120 VAC version and the ECC 50DAE 240 VAC version amplifier unles...

Page 7: ... accordance with the National and or Local codes for fire alarm systems The cabinet can be surface or flush mounted For flush mount installation of the cabinet the hole for the enclosure should be 14 5 W x 24 75 H x 3 438 D 36 8cm W x 62 9cm H x 8 73cm D Do not flush mount in a wall designated as a fire break The outside dimensions of the cabinet are 16 W x 26 25 H x 4 125 D 40 64cm W x 66 68cm H ...

Page 8: ...ircuits High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be reduced by running the wire through ferrite beads or by wrapping it around a ferrite toroid core Figure 1 3 provides an example To AC ON 1 2 3 4 5 BATTERY OUT IN A B SBUS CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 CIRCUIT 1 IN IN IN IN OUT OUT OUT OUT AUDIO EXPANDER CIRCUIT 5 CIRCUIT 6 CIRCUIT 8 CIRCU...

Page 9: ...0 6200 9860 15680 70Vrms 25000 39700 63200 100520 20 10 25Vrms 10W 2125 3380 5375 8540 70Vrms 15200 24150 38400 61100 30 15 25Vrms 15W 1460 2320 3690 5870 70Vrms 11000 17500 27800 44200 40 20 25Vrms 20W 1100 1750 2780 4420 70Vrms 8500 13510 21500 34175 52 26 25Vrms 26W 760 1200 1920 3050 70Vrms 6100 9700 15400 24520 80 40 25Vrms 40W 550 875 1390 2200 70Vrms 4100 6500 10360 16480 100 50 25Vrms 50W ...

Page 10: ...rated from a system microphone to the ECC 50DAs The maximum resistance on the Audio Riser is 20Ω Connect the Audio Riser from TB22 on the ECC 50 100 main control board to the ECC 50DAs as shown in Figure 1 6 BATTERY IN OUT AUDIO EXPANDER Figure 1 5 Class A Style Z Speaker Configuration Supervised Power limited 50da_a wmf OUT IN A B SBUS OUT IN A B SBUS ECC 50 100 main control board Supervised Powe...

Page 11: ...ations Wire the Data BUS from TB12 on the main control board to the ECC 50DA shown in Figure 1 7 or Figure 1 8 ON 1 2 3 4 5 OUT IN A B SBUS 5 ECC 50 100 main control board Supervised Power limited Figure 1 7 Data BUS Connections of the ECC 50DA 50dadatawire wmf ON 1 2 3 4 5 OUT IN A B SBUS ON 1 2 3 4 5 OUT IN A B SBUS Supervised Power limited To next ECC 50DA max 8 Figure 1 8 Connecting Multiple E...

Page 12: ...t transformer mounting studs using the supplied locking hex nuts as shown in Figure 1 9 Module Voltage Transformer P N Standby Current Alarm Current ECC 50DA 25V 120 VAC 60 Hz 115061 350 mA 1100 mA ECC 50DAE 25V 230 VAC 50 Hz 115031 200 mA 600 mA ECC 50DA 70V 120 VAC 60 Hz 115061 350 mA 1200 mA ECC 50DAE 70V 230 VAC 50 Hz 115031 200 mA 600 mA Table 1 2 ECC 50DA AC Current Draw ON 1 2 3 4 5 BATTERY...

Page 13: ...or on the control panel See Figure 1 10 below 1 1 8 Backup Battery The following steps explain how to connect the batteries refer to Figure 1 11 1 Connect the black wire of the battery harness to the negative side of battery 2 2 Connect the jumper wire provided from the positive side of battery 2 to the negative side of battery 1 CIRCUIT 4 CIRCU IN IN OUT black green white Figure 1 10 AC Connectio...

Page 14: ...te Batteries have been rotated to show the top sides for illustration purposes only 50dabatt wmf Device No of Devices Current Per Device Standby Current Alarm Current ECC 50DA 25V system 1 Standby 85 mA 85 mA Alarm 525 mA 525 mA ECC 50DA 70 7V system 1 Standby 100 mA 100 mA Alarm 580 mA 580 mA ECC CE4 0 or 1 Standby 20 mA Alarm All Channels 180 mA mA A Current Subtotals mA mA Notification Devices ...

Page 15: ...ECC 50 125DA Instruction Manual P N LS10027 000FL E D 5 21 2015 15 Notes firealarmresources com ...

Page 16: ...r to the programming section of the ECC 50 100 Instruction Manual LS10001 000FL E 2 1 1 Board Layout Figure 2 1 shows the location of terminals dipswitches and expander connection used in the installation of the ECC 125DA NOTE The term ECC 125DA is used in this manual to refer to both the ECC 125DA 120 VAC version and the ECC 125DAE 240 VAC version amplifier unless specified ON 1 2 3 4 5 CIRCUIT 4...

Page 17: ... accordance with the National and or Local codes for fire alarm systems The cabinet can be surface or flush mounted For flush mount installation of the cabinet the hole for the enclosure should be 14 5 W x 24 75 H x 3 438 D 36 8cm W x 62 9cm H x 8 73cm D Do not flush mount in a wall designated as a fire break The outside dimensions of the cabinet are 16 W x 26 25 H x 4 125 D 40 64cm W x 66 68cm H ...

Page 18: ...ard where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be reduced by running the wire through ferrite beads or by wrapping it around a ferrite toroid core Figure 2 3 provides an example CIRCUIT 5 CIRCUIT 6 CIRCUIT 8 CIRCUIT 7 OUT...

Page 19: ... in Feet 1 2 W 1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG 10 5 25Vrms 5W 3900 6200 9860 15680 20 10 25Vrms 10W 2125 3380 5375 8540 30 15 25Vrms 15W 1460 2320 3690 5870 40 20 25Vrms 20W 1100 1750 2780 4420 52 26 25Vrms 26W 760 1200 1920 3050 80 40 25Vrms 40W 550 875 1390 2200 100 50 25Vrms 50W 450 715 1130 1800 150 75 25Vrms 75W 300 476 753 1200 200 100 25Vrms 100W 225 357 565 900 250 125 25Vrms 12...

Page 20: ...Class A Style Z Figure 2 5 illustrates how to wire speakers to the control panel using Class A Style Z wiring BATTERY CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 IN IN IN OUT OUT OUT AUDIO EXPANDER CIRCUIT 1 IN OUT Supervised Power limited Figure 2 5 Class A Style Z Speaker Configuration 125da_a wmf firealarmresources com ...

Page 21: ... messages generated from a system microphone to the ECC 125DAs The maximum resistance on the Audio Riser is 20Ω Connect the Audio Riser from TB22 on the main control board to the ECC 125DAs as shown in Figure 2 6 OUT IN B A SBUS OUT IN B A SBUS ECC 125DA ECC 125DA To next ECC 125DA ECC 50 100 main control board Supervised Power limited UL listed 15KΩ ELR at last panel on Audio Riser Figure 2 6 ECC...

Page 22: ...ns Wire the Data BUS from TB12 on the main control board to the ECC 125DA as shown in Figure 2 7 or Figure 2 8 OUT IN B A SBUS Figure 2 7 Data BUS Connections of the ECC 125DA Supervised Power limited 125dadatawire wmf ECC 125DA ECC 50 100 main control board OUT IN B A SBUS OUT IN B A SBUS to next ECC 125DA max 8 Figure 2 8 Connecting Multiple ECC 125DAs to the Data BUS Supervised Power limited mu...

Page 23: ...nals to the power source as shown in Figure 2 10 It may be necessary for a professional electrician to make this connection Module Voltage Standby Current Alarm Current ECC 125DA 120 VAC 60 Hz 300 mA 2200 mA ECC 125DAE 240 VAC 50 Hz 250 mA 1250 mA Figure 2 9 ECC 125DA AC Current Draw B G W Figure 2 10 AC Connection white green black 1225daac wmf firealarmresources com ...

Page 24: ...de of the battery 2 2 Connect the jumper wire provided form the positive side of battery 2 to the negative side of battery 1 3 Connect the red wire from the battery harness to the positive side of battery 1 BATTERY CIRCUIT 4 CIRCUIT 3 CIRCUIT 2 IN IN IN OUT OUT OUT AUDIO EXPANDER CIRCUIT 1 IN OUT Battery 1 Battery 2 Note Batteries have been rotated to show the tops for illustration purposes only F...

Page 25: ...evice Standby Current Alarm Current ECC 125DA 1 Standby 375 mA 375 mA Alarm 700 mA 700 mA ECC CE4 0 or 1 Standby 20 mA Alarm All Channels 180 mA mA A Current Subtotals mA mA Notification Devices Refer to device manual for number of devices and current ratings B Current Subtotals mA mA C Total current rating of all devices in system Line B X 001 A A D Number of standby hours 24 or 60 for NFPA 72 H ...

Page 26: ...nual P N LS10001 000FL E for more information The ECC 50BDA must also be enabled in user programming 70 volt operation of the ECC 50BDA is also set up in user programming Refer to the programming section of the ECC 50 100 Instruction Manual LS10001 000FL E Amplifier Audio Product Description ECC 50 100 Main console ECC 50 100 with ECC 50W 25V Main console with optional second 25V amplifier install...

Page 27: ... expander connection used in the installation of the ECC 50BDA TB1 TB3 TB4 B A W G B OUT IN OUT IN OUT IN TB6 TB5 J1 TB2 SW4 SW3 SW1 SW2 Audio Riser Data Bus Data Bus ID Dip Switch ECC 50WBU Connection Battery Connector AC Transformer Connector Audio Circuits Figure 3 1 ECC 50BDA Board Layout ecc dual50da wmf test switches Amp mode Dip Switch not used Amplifier B Amplifier A firealarmresources com...

Page 28: ...e in accordance with the National and or Local codes for fire alarm systems The cabinet can be surface or flush mounted For flush mount installation of the cabinet the hole for the enclosure should be 14 5 W x 24 75 H x 3 438 D 36 8cm W x 62 9cm H x 8 73cm D Do not flush mount in a wall designated as a fire break The outside dimensions of the cabinet are 16 W x 26 25 H x 4 125 D 40 64cm W x 66 68c...

Page 29: ...ECC 50WBU 1 Make sure that all power supplied to the ECC 50BDA has been removed 2 Insert the supplied M F standoffs in the locations shown below 3 Connect the backup amplifier cable harness P N 50116775 001 to the connector labeled Backup Amplifier on the ECC 50BDA 4 Lay the ECC 50WBU over the standoffs installed in step 2 and secure with supplied screws 5 Connect the other end of the cable harnes...

Page 30: ...uts and or conduits For the same reasons wiring within the cabinet should be routed around the perimeter of the cabi net It should not cross the printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be reduced ...

Page 31: ...G 14 AWG 12 AWG 10 5 25Vrms 5W 3900 6200 9860 15680 70Vrms 25000 39700 63200 100520 20 10 25Vrms 10W 2125 3380 5375 8540 70Vrms 15200 24150 38400 61100 30 15 25Vrms 15W 1460 2320 3690 5870 70Vrms 11000 17500 27800 44200 40 20 25Vrms 20W 1100 1750 2780 4420 70Vrms 8500 13510 21500 34175 52 26 25Vrms 26W 760 1200 1920 3050 70Vrms 6100 9700 15400 24520 80 40 25Vrms 40W 550 875 1390 2200 70Vrms 4100 6...

Page 32: ...stance on the audio riser is 20Ω The ECC 50BDA supports two audio riser channels The wiring method is the same for both channels Audio Riser 1 and Audio Riser 2 should never be wired together Connect the Audio Riser from TB22 on the main control board to the ECC 50BDAs as shown in Figure 3 7 TB4 B A OUT IN OUT IN TB6 TB5 TB2 Figure 3 6 Class A Style Z Speaker Configuration Supervised Power limited...

Page 33: ...12 on the main control board to the ECC 50BDA as shown in Figure 3 8 or Figure 3 9 Refer to section 2 of the ECC 50 100 Manual for information on setting SBUS addresses TB4 B A Figure 3 8 Data Bus Connections of the ECC 50BDA Supervised Power limited 50dualdatawire wmf ECC 50BDA ECC 50 100 main control board TB4 TB4 B A B A 50dualmultidatawire wmf ECC 50BDA ECC 50 100 main control board ECC 50BDA ...

Page 34: ...tting 3 3 2 8 Test Switch Use SW1 AMPLIFIER A Switch should be moved to the ON position for normal operation Move this switch to the Test position to test backup amplifier SW2 AMPLIFIER B Switch should be moved to the ON position for normal operation Move this switch to the Test position to test backup amplifier 3 2 9 Connecting AC Power At installation connect the AC terminals to the power source...

Page 35: ...black wire of the battery harness to the side of the battery 2 2 Connect the jumper wire provided form the positive side of battery 2 to the negative side of battery 1 3 Connect the red wire from the battery harness to the positive side of battery 1 B G W Figure 3 11 AC Connection white green black 1225daac wmf OUT IN OUT IN TB6 TB5 J1 TB2 Figure 3 12 Battery Connection to ECC 50BDA Note Batteries...

Page 36: ...ice Standby Current Alarm Current ECC 50BDA 25V 1 Standby 110 mA 110 mA Alarm 1 2 A 1 2 A ECC 50BDA 70 7V 1 Standby 110 mA 110 mA Alarm 1 4 A 1 4 A ECC 50WBU 1 Standby 40 mA 40 mA Alarm 110 mA 110 mA A Current Subtotals mA mA Notification Devices Refer to device manual for number of devices and current ratings B Current Subtotals mA mA C Total current rating of all devices in system Line B X 0 001...

Page 37: ...T TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the only warranty made b...