background image

Installation and Commissioning

Instructions

Note: HP2000 (or HP10*/HP18*) required for commissioning

* Please note that the HP10 and HP18 offer different/limited programming options

LightSpot Washroom Series

UC1200PF

Summary of Contents for Ex-Or UC1200PF

Page 1: ...allation and Commissioning Instructions Note HP2000 or HP10 HP18 required for commissioning Please note that the HP10 and HP18 offer different limited programming options LightSpot Washroom Series UC1200PF ...

Page 2: ...enoid valve must be plumbed into the water feed to the urinal header tank and connected to the detector using 230V cable Multiple UC1200PF Larger areas can be covered by connecting extra units in parallel The total load current must not exceed 6Amps in case only one unit is activated N E L Permanent or switched supply LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH LIGHTING FAN OR VALVE LightSpot Ligh...

Page 3: ...fficient natural light is available It will not turn the load off whilst an area is occupied Active The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the l...

Page 4: ...the control of water for washroom management applications urinals In order to maintain good standards of hygiene the products feature a washroom mode 24hr Cycle that if enabled ensures that when urinals have not been used for 24 hours i e the controlled area has been unoccupied a hygiene flush occurs Please note that when controlling lighting and urinals it is not possible to have the photocell in...