INSTALLATION INSTRUCTIONS

69-0251-3

AT120A, AT140A, AT150A, AT175A 

Universal Transformers

APPLICATION

These transformers are for use in 24 Vac nominal control 

circuits. They are typically used in heating/cooling control 
systems but can be used in any application that does not 
exceed the load ratings. They meet National Electrical 

Code Class 2 “not wet” and Class 3 “wet” requirements 

and are Underwriters Laboratories (UL) Inc. listed under 

UL 1585. They can be mounted through a 7/8 in. knock-
out on the accessory mounting plate (included), or with 
the integral mounting feet. See Table 1 for additional 

specifications.

INSTALLATION

When Installing this Product …

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazard-
ous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

CAUTION

Electrical Hazard.
Can cause electrical shock or equipment 
damage.

Disconnect power supply before beginning 
installation.

Table 1. Model Specifications.

Model 

Number

Primary

Secondary

Output Rating at 

100 Percent Power 

Factor

Input 

Voltage 

(60 Hz)

Wiring 

Connections

Voltage

Wiring 

connections

Open 

Circuit

At Rated 

Power 

Output

AT120A

120/208/
240

9 in. leads

27.0

24.0

Screw 
terminals

20 VA

AT140A

120

9 in. leads

27.0

24.0

Screw 
terminals

40 VA

120/208/
240

120/240

208/240

AT150A

120/208/
240

9 in. leads

27.5

24.0

Screw 
terminals

50 VA

AT175A

120/208/
240

9 in. leads

27.5

24.0

Screw 
terminals

75 VA

Summary of Contents for AT120A

Page 1: ...the product or cause a hazard ous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Hazard Can cause electrical shock or equipment damage Disc...

Page 2: ... the way out 2 Hold the mounting plate with the keyhole slots up and the raised portion of the large center knockout away from you 3 From the back thread the primary leadwires through the round center hole in the plate 4 Fit the clamp and screw through the round hole 5 While holding the plate in place tighten the setscrew securely against the rim of the hole See Fig 3 Avoid damaging the leadwires ...

Page 3: ...necessary Mount the plate on the outlet box using two screws obtained locally Mounting Through Outlet Box Knockout Hole The transformer can be mounted on an outlet box using the clamp on the primary end bell The mounting plate is not used To mount the transformer on an outlet box 1 Turn the clamp screw almost all the way out 2 From outside box thread the primary leadwires through suitable 7 8 in k...

Page 4: ...wer supply and perform a voltage check 1 Place controlled equipment in operation and observe through one complete cycle 2 Using a voltmeter check for proper primary and secondary voltages 3 If voltage readings are incorrect be sure primary voltage connections are made correctly 4 Measure voltage again a If correct primary voltage is measured and secondary voltage is significantly less than the vol...

Reviews: