background image

 

 

ADEMCO 4297

V-Plex

®

 Loop Extender Module

For Use With Control/Communicators Supporting V-Plex

®

 Loop Devices 

 

INSTALLATION AND SETUP GUIDE 

GENERAL INFORMATION 

The ADEMCO 4297 V-Plex

®

 loop extender module is an 

accessory for use with Ademco control panels that support  

V-Plex (polling loop) devices.  The 4297 module receives 

signals from the control panel via its "input" loop, and then 

re-transmits boosted copies of these signals via its 

"extension" loop.        

 

The 4297 draws power for its internal circuitry and its 

extension loop from a supplementary power supply such as 

the control panel’s auxiliary power output.    
Also, the 4297 isolates open and short circuit faults 

occurring on its extension loop from its input 

 

loop. These characteristics allow the 4297 module to be 

used to extend the control panel's polling loop, to provide 
additional polling loop current, and to provide

 

electrically 

isolated branch loops. 

 

The 4297 module is fully supervised and causes the control 

panel to trigger supervision fault indications for devices 

wired to the extension loop when operating power to the 

module fails, or when an open or short circuit occurs on the 

extension loop.  Refer to the control panel's installation 
instructions for the type of supervision fault indication 

provided. 

 

Important Notes: 

*

 The 

4297 

cannot

 be used to increase the number of  

polling loop zones supported by the control panel. 

*

  The 4297 is 

not

 designed to be used in a Class A    

wiring configuration. 

MOUNTING     

For UL burglary and all fire installations: 

Mount the 4297 module inside a UL Listed enclosure such as 

the control panel's enclosure.  Note that the enclosure must 
be UL Listed for the desired application; i.e., use an attack-

resistant enclosure with a tamper switch for commercial 

burglary applications. 

For non-UL certified installations: 

Mount the 4297 module directly on a surface using the 
slotted holes located on the back of its housing (mounting 

screws provided). Feed the wires through the slot on the side 

or through the breakout located on the back of the housing. 

Affix the connections label provided to the inside of the 4297 

module's cover or in the control panel cabinet, if used. 

WIRING CONNECTIONS 

The 4297 module provides a 9-position terminal block for 

making power, earth ground and polling loop connections. 

The screw terminal assignments on this terminal block are 

described in Figure 

1

UL NOTE:

 Use only 14-22 gauge wire.

 

ULC

 

For ULC fire installations, the 4297 can be used to 
connect the fire alarm control panel to the Vista fire 
transmitter. It is not to be used to connect fire alarm 
detectors to the ADEMCO (Vista) fire transmitter. 

 

 

4297-003-V1

9

8

7

6

5

4

3

2

1

TB1

EXTENSION POLLING LOOP
(CLASS B, STYLE 3)
MAX LINE IMPEDANCE 20

}

}

}

}

INPUT POLLING LOOP
(FROM CONTROL) (CLASS B,
STYLE 3)

12VDC POWER INPUT (FROM
CONTROL PANEL OR A SUP-
PLEMENTAL POWER SUPPLY
LISTED FOR THE APPLICATION) 

 

+

+

(NO CONNECTION)

+

FOR IMPEDANCES BELOW WHICH
GROUND FAULTS WILL BE
ANNUNCIATED, REFER TO THE
"SUMMARY OF CONNECTIONS"
LABEL FOR THE CONTROL PANEL.

NOTES:

1.

3.

2.

 

ALL CIRCUITS ARE SUPERVISED AND POWER LIMITED.
ELECTRICAL SPECIFICATIONS:

WHEN USING AN EXTERNAL POWER SOURCE, CONNECTIONS MUST
BE MADE TO A UL864/UL1481 REGULATED POWER SUPPLY.

WHEN A SUPPLEMENTARY POWER SUPPLY IS USED, CONNECT IT TO
TERMINALS 1 & 2. CONNECT THE POWER SUPPLY (-) TO AUX POWER (-)
ON THE CONTROL PANEL. USE A CLASS II (POWER LIMITED) SUPPLY.

POLLING LOOP VOLTAGE: 8-11 VDC
INPUT POWER VOLTAGE: 12 VDC
INPUT POWER CURRENT: 180MA

*

*

FOR CE INSTALLATIONS
TERMINAL 3 MUST BE
CONNECTED TO
EARTH GROUND

4. USE ONLY 14-22 GAUGE WIRE.

              :400MA (LOOP SHORTED)

 

Figure 1.  4297 Wiring Connections 

 

Power Supply Connections  

The 4297 module can draw power for its internal circuitry 

and its extension loop from a supplementary power supply 

such as the control panel's auxiliary power output.  See 

Figure 2. 

 

UL

  All power-limited wiring must be separated from non-power 

limited and high-voltage wiring by 1/4" (6.4 mm). 

  Refer to the control panel installation instructions for 

programming / installation requirements. 

 

 

When Using One 4297 

Use one 4297 to extend the polling loop, to provide additional 

polling loop current, or to provide an extension loop which is 

electrically isolated from the input loop. 

Make the connections shown in Figure 3 when only one 4297 
module is used.  Make sure that the wire run length limits 

indicated in Table 

1

 are not exceeded. 

 

When Using Multiple 4297s 

Use multiple 4297s to provide up to eight extension loops 

which are electrically isolated from each other, or to provide 

more current than one 4297 can supply. 
Make the connections shown in Figure 4 when multiple 4297 

modules are used.  Do not wire 4297 modules in series (i.e., 

do not wire one module’s extension loop to another module’s 

input loop). Do not use more than eight 4297 modules in 

parallel unless otherwise stated in the control panel's 
installation instructions.  Make sure that the wire run length 

limits indicated are not exceeded.  

Important Notes: 

*  Twisted pair is recommended for all polling loop wire runs. 
*  If an intercom system is being used, keep the polling loop 

wiring as far from the intercom wiring as possible 

(minimum 6 inches). If this spacing cannot be achieved, use 

shielded wire.  Note that use of shielded wire reduces the 

maximum permissible polling loop wire run length, as 

indicated in Table 

1

 on page 2

.

 

Reviews: