12 Clintonville Road, Northford, CT 06472-1610 USA
203-484-7161 • FAX 203-484-7118 • 

6815 SLC Expander

Product Installation Document

PN LS10173-001SK-E:A   07/01/2017   ECN 16-0218

6815 SLC Expander

The 6815 SLC expander lets you add additional 
addressable devices to a compatible Fire Alarm 
Control Panels (FACP). 

Installation and wiring of this device must be 
done in accordance with NFPA 72 and local 
ordinances.

Compatibility

The 6815 is for use with compatible Honeywell 
Silent Knight and Farenhyt Series Fire Alarm 
Control Panels FACP's:

Note: For compatibility, programming and more information 

see FACP installation manual.

Specifications

Standby Current: 78mA

Alarm Current: 78mA

Operating Voltage: 24VDC

Operating Temperature: 32°F to 120°F 
(0°C to 49°C)

Mounting

You can mount the 6815 in a compatible FACP 
cabinet, in the 5895XL or RPS-1000 intelligent 
power module cabinet, or in the SK-NIC-KIT 
remote mounting kit.

Warning! 
The electronic components on the 6815 and 
the panel are sensitive to electrostatic 
discharge. Wear a grounding strap when 
handling any of the boards

.

To mount the 6815:

1. Remove power from the panel.

2. If mounting the 6815 in an FACP or 

5895XL, use the standoffs located under the 

panel assembly and secure with screws 
provided with the 6815.

–OR–

If mounting the 6815 in a 5815RMK or SK-
NIC-KIT orientate the 6815 board(s) as 
shown in Figure 1 and snap into place on the 
plastic standoffs.

Figure 1: Standoff Installation and 6815 Board 

Mounting

Wiring

See Table 1 and Figure 2 to wire a 6815 to a 
compatible FACP or the 5895XL.

Table 1: 6815 to FACP Connections

6815 Terminals

FACP SBUS Out Terminals

+

+

A

A

B

B