5800CO Carbon Monoxide Detector

with Built-in Wireless Transmitter

INSTALLATION AND SETUP GUIDE

 

GENERAL INFORMATION  

The 5800CO is a 3V battery powered wireless Carbon Monoxide (CO) 
detector intended for use with wireless alarm systems that support 
5800 series devices. Refer to control/communicator installation 
instructions for compatibility. 

Compatible Controls:

 This detector can be used with 5800 series 

compatible controls (Listed to UL864 and/or UL985) that support a 
carbon monoxide zone type and utilize a 5881 receiver.  

The detector consists of an electrochemical carbon monoxide 
sensor assembly coupled to a wireless transmitter. The 
transmitter can send alarm, trouble, end-of-life, tamper, and 
battery condition messages to the system’s receiver. Refer to the 
wireless system’s instructions for the maximum number of 
transmitters that can be supported. 

NOTICE: These instructions should be left with the 
owner/user of this equipment.

 

IMPORTANT: 

This detector must be tested and maintained 

regularly following NFPA 720 requirements. 

WARNING: 

This product is not intended for use in industrial 

factories or commercial parking garages. 

 

Detector Description 

• Listed to UL standard 2075  
  CO sensitivity is evaluated to UL 2034 
• Supervised 
• Local  sounder 
• Dual LED’s 
• Test/Hush  button 
• Surface  mount to wall or ceiling 
• Optional drywall anchors included 

The 5800CO contains a piezoelectric horn which generates the ANSI 
S3.41 temporal 4 pattern in an alarm condition (see note below Table 
1 for temporal 4 pattern). In alarm, a message is also sent to the 
control panel and the detector’s zone number is displayed at the 
console. The alarm message is transmitted every 4 seconds until the 
carbon monoxide condition has cleared and the detector has reset. 
During an alarm condition, pressing the detector’s test button will 
silence the piezoelectric horn for five minutes. Once the detector has 
reset, a RESTORE message is transmitted to the control panel and 
the transmitter’s zone number can be cleared from the panel. The 
mounting base installation is simplified by the incorporation of 
features compatible with drywall fasteners or other methods that 
provide a method for securing the detector in place. 

Two LEDs and a sounder on the detector provide local visual and 
audible indication of the detector’s status as listed in Table 1. 

During initial power-up, the red and green LEDs will blink together 
once every 10 seconds four times. It takes about 30 seconds for the 
detector’s CO sensor to stabilize (see Table 1). 

After power-up has completed and the detector is functioning 
normally, the green LED blinks once every 10 seconds. The LED 
indication must not be used in place of the tests specified under 

TESTING THE DETECTOR.

  

Table 1: Detector LED Modes 

 

Green LED 

Red LED 

Sounder 

Normal (standby)  Blinks every 

10 seconds 

Off Off 

Alarm/Test Off 

Blinks every 
1 second 

Temporal 4 
Pattern

 

Low Battery 

Off 

Blinks every 
45 seconds 
for 37 days 

Chirp every 45 
sec beginning 7 
days after LED 
blinks, continues 
30 days 

Detector Trouble 

Off 

Blinks every 
5 seconds 

One chirp every 
45 seconds 

Detector End-of-
Life 

Off 

Blinks every 
10 seconds 

One chirp every 
45 seconds 

Power Up 

Blinks every 
10 secs

††

 

(w/red LED)

 

Blinks every 
10 secs 

††

 

(w/green LED)

 

Off 

† Temp 4 pattern is repeated pattern of four short beeps followed by 
a five second pause. If ambient conditions return to normal, the 
detector will self-restore out of alarm and into the previous mode. 

††

 Red and green LEDs blink a total of four times, once every 10 

seconds. 

Hush feature:

 If required, the audible alarm can be silenced for five 

minutes by pushing the Test button. The red alarm light will 
continue to flash in temp-4 pattern. If carbon monoxide is still 
present after the 5-minute hush period, the audible alarm will sound. 
The hush feature will not operate at levels above 350 ppm (parts per 
million) carbon monoxide. 

Trouble feature: 

When the sensor supervision is in a trouble 

condition, the detector will send a trouble signal to the panel. The red 
LED blinks once every five seconds. Trouble conditions include an 
open circuit, sensor removal (tamper), and sensor end of life. 

End of Life Timer feature: 

When the detector has reached the end 

of its life, the detector will send a trouble signal to the panel. This 
indicates that the CO sensor inside the detector has passed the end 
of its life and the detector must be replaced. This detector’s lifespan 
is approximately six years from the date of manufacture. Refer to 
Detector Replacement section. 

Low Battery Detection:

 

The 5800CO is powered by a single 3-volt 

CR123A or DL123A Lithium battery (included). The detector checks 
for a low battery at least every 65 minutes. If a low battery is 
detected, the transmitter sends a low battery message to the control 
panel, which beeps and displays the detector’s zone number. In 
addition, the red LED of the detector will blink every 45 seconds. 
After 7 days the detector’s horn will “chirp” about every 45 seconds 
(red LED continues to blink) for up to 30 days. Pressing the test 
button during this time will silence the chirps for 12 hours, if no 
other trouble conditions exist. The battery should be replaced 
BEFORE the chirps begin. Be sure to replace the battery with a fresh 
one. 
 

This device complies with Part 15 of the FCC rules and RSS210 of 
Industry Canada. Operation is subject to the following two 
conditions:  (1) This device may not cause harmful interference, and 
(2) This device must accept any interference received, including 
interference that may cause undesired operation. 

 

Unauthorized changes or modifications could void the user’s 
authority to operate the equipment. 

 

Summary of Contents for 5800CO

Page 1: ... TESTING THE DETECTOR Table 1 Detector LED Modes Green LED Red LED Sounder Normal standby Blinks every 10 seconds Off Off Alarm Test Off Blinks every 1 second Temporal 4 Pattern Low Battery Off Blinks every 45 seconds for 37 days Chirp every 45 sec beginning 7 days after LED blinks continues 30 days Detector Trouble Off Blinks every 5 seconds One chirp every 45 seconds Detector End of Life Off Bli...

Page 2: ...es proper carbon monoxide detection see Figure 4 for suggested detection locations and a strong wireless transmission path Proper Carbon Monoxide Detection Location In a wall location the detector should be at least as high as a light switch and at least six inches from the ceiling In a ceiling location the detector should be at least 12 inches from any wall Where to install ideally Within 10 feet...

Page 3: ... 5800CO 004 V0 PUSH RECESSED BUTTON WITH A 0 18 MAX DIAMETER TOOL TEST H U S H D O N O T P A I N T N O R M A L A L A R M C A R B O N M O N O X I D E D E T E C T O R W A R N I N G I N A L A R M M O V E T O F R E S H A I R C A U T I O N ADDITIONAL M A R K INGS ON BACK LEDs RECESSED TEST BUTTON Figure 5 Recessed Test Button Opening Testing Signal Strength NOTE Remove battery tab before installation T...

Page 4: ...re identified during this inspection have the equipment serviced immediately Note any combustion equipment not inspected by the technician and consult the manufacturer s instructions or contact the manufacturers directly for more information about CO safety and this equipment Make sure that motor vehicles are not and have not been operating in an attached garage or adjacent to the residence IMPORT...

Reviews: