background image

Galaxy

3-48C, 3-144, 3-144C, 3-520, 3-520C

Installation Manual

Honeywell Security

Summary of Contents for 3-144

Page 1: ...Galaxy 3 48C 3 144 3 144C 3 520 3 520C Installation Manual Honeywell Security ...

Page 2: ......

Page 3: ...ry 2 9 Battery Start up 2 9 On Board Power Supply Unit 2 9 Memory 2 10 RS485 Data Communication Bus AB Lines 2 10 RS485 Wiring Configurations 2 10 RS485 Wiring Recommendations 2 11 Zones 2 13 Zone Addresses 2 13 Zone Addressing with Onboard RIO Switch 2 14 Wiring Zones 2 14 Wiring Multiple Zones 2 15 Wiring Keyswitches 2 15 Wiring Terminator Buttons 2 16 Outputs 2 16 Output Applications 2 17 SPI H...

Page 4: ...ification Output Module 3 11 Technical Specification Relay Module 3 11 Power Supply Unit 3 12 Configuration 3 12 Installation Instructions 3 13 Battery 3 14 Battery Test 3 14 Specifications 3 14 EN50131 Compliance 3 14 Printer Interface Module A134 A161 3 15 Telecom Module E062 3 16 Connection to the PSTN 3 16 Programming the Telecom Module 3 16 RS232 Interface Module E054 3 17 Interface with a PC...

Page 5: ...r Key 4 5 Escape Key 4 6 Hash Key 4 6 Star Key 4 6 Power LED 4 7 Display 4 7 The Galaxy KeyProx 4 8 General 4 8 Addressing 4 8 Operation 4 8 Card Types 4 8 Section 5 Door Control Module MAX3 5 1 Introduction 5 1 Standalone 5 1 On line 5 1 Installing the MAX3 5 1 MAX3 Pack 5 1 Mounting the MAX3 5 1 Wiring the MAX3 5 2 Configuring a MAX3 Reader into the System 5 3 Configuring as On Line MAX3 5 3 Con...

Page 6: ... A 4 Removing a MAX Reader from the System A 5 Stand Alone Mode A 5 On Line Mode A 5 Programming Instructions for On Line Readers A 5 Operating Instructions On Line Modes A 6 Gaining Access A 6 Card Held Function A 6 Max Log A 7 Max Events Print Out A 7 Appendix B 3 Ampere Smart PSU P015 B 1 Grounding B 1 Appendix C Panel Comparisons C 1 Appendix D Declaration of Conformity D 1 Compliance and Appr...

Page 7: ...es Programming Manual part number IP1 0033 Variants The Galaxy 3 Series is available in five variants 3 48C 3 144 3 144C 3 520 3 520C The differences betweeneachvariantareshowninthefollowingtable Introduction Table 1 1 Galaxy 3 Series Variants NOTE The RS485 Expansion module gives two extra lines lines 3 and 4 on the 3 520 only VARIANT ON BOARD COMMS RS485 EXPANSION MODULE RS485 LINES 3 48C YES NO...

Page 8: ...1 2 Galaxy 3 Series Installation Manual ...

Page 9: ...allation Procedure Section 4 6 Connect the battery before replacing the control panel lid 7 Connect the mains wiring to the control panel Do not switch the mains ON 8 Replace the control panel lid and secure the fastening screws 9 Switch on the mains voltage 230 Va c 50 Hz 10 Thefollowingsequenceofeventsoccur the keypad buzzer and control panel horn if fitted activate for 10 20 seconds flashing is...

Page 10: ...1 4 Galaxy 3 Series Installation Manual ...

Page 11: ...addresses can be replaced by a combined keyprox unit NOTE Valid addresses for the keyprox are Line 1 0 1 2 This sets the address for both the keypad and card reader parts of the keyprox 8 outputs on board on board telecom area Max 4 MX03 OR OR NOTE RIOs RF RIO s and PSU s can be mixed on the lines The maximum number of combined modules is given in the table below PSTN comm 1 Smart PSU 4 P015 8 zon...

Page 12: ...is shown as 15 on the system If an ISDN module is attached keypad address C cannot be connected to line 1 address C is shown as 16 on the system Cable run 1 km max Certain keypad and max addresses can be replaced by a combined keyprox unit NOTE Valid addresses for the keyprox are Line 1 0 1 2 Line 2 0 1 2 3 This sets the address for both the keypad and card reader parts of the keyprox 8 outputs on...

Page 13: ...Os RF RIO s and PSU s can be mixed on the lines The maximum number of combined modules is given in the table below RS232 Serial Port PSTN 8 zones 4 outputs Power Unit 16 P025 or Power RIO 16 P026 Smart PSU 15 P015 8 zones 4 outputs RF RIO Module 15 C076 Power Unit 15 P025 or Power RIO 15 P026 Printer Interface 1 A134 A161 ISDN Module 1 E077 comm 3 RS232 Module 1 E054 comm 2 Telecom Module 1 E062 c...

Page 14: ... 3 RIO 1 GND GND 12V CTS RTS LED1 for Telecoms LED2 for RS232 LK5 LK3 12V 4 14 5 BAT BAT F1 F2 BAT BELL F4 AUX1 AUX2 3 144 3 520 only FLASH SRAM SPI Program Header OFF WALL TAMPER BATTERY START UP 1 2 3 4 5 6 7 8 SW3 RIO SWITCH Engineer socket RS485 Line1 Engineer socket RS485 Line 2 NOTE Fuse AUX1 controls RS485 line 1 RIO 0 zones 1 8 Fuse AUX2 controls RS485 line 2 RIO 1 zones 1 8 RS232 Port soc...

Page 15: ...tbewiredinadaisy chainconfiguration Thatis theAlinefromtheprevious module is connected to theA3 orA4 terminal of the Expansion Module The RS485 AB line must have a 680 ohm resistor fitted across the A and B terminals of the last module on the line If two lines are connected both ends must be terminated with a 680 ohm resistor and the appropriate link LK1 or LK2 removed RS485 Expansion Module Figur...

Page 16: ... through the hole on the right hand side of the enclosure base Securely anchor the cabletotheboxusingthetie wrapasshowninthefollowingFigure Figure 2 6 Securing the Mains Cable to the Enclosure Base Secure the panel base to the wall using three 1 5 No 8 round head steel screws through the holes provided The mains cable used must be a three core type with green yellow earth insulation of adequate cu...

Page 17: ...nel is the only device on the line 3 If another device is to be connected to the line connect the PHONE terminals on the PCB to terminals 2 and 5 on a second BT Master Socket There are two methods of connecting the on boardTelecom Module to the PSTN Method 1 Using cable suitable for connection to 2 8 mm diameter screw terminals strip back approximately 20 mm of the outer sheath and then remove app...

Page 18: ... T A C I D N I F F O D E L e l u d o m o t y l p p u s c d o N s 9 0 F F O s 1 0 N O n o i t a c i n u m m o c l a m r o N l l a c f o d n e t a e s l u p e l g n i S n o i t a c n u m m o c l a m r o N l l a c m r a l a f o d n e t a g n i h s a l F n o i t a c i n u m m o C d e l i a F y x a l a g g n i r o t i n o m m r a l a g n i r u d n O S M S d n a d l o g n o i t a c i n u m m o C l a m r...

Page 19: ...panel contains four fuses Details are given in the table below NOTE The G3 48 does not require fuseAUX2 Table 2 4 On board PSU Fuses Power Monitoring Characteristics Lowbatterylevel 11 2V Deep discharge protection 10 5V Overvoltageprotection 14 7V Stand by Battery l e n a P l o r t n o C y r e t t a B T A B l a n i m r e t e v T A B l a n i m r e t e v FUSE NAME VALUE AMPS MONITORS TYPE AUX1 1 0 R...

Page 20: ...e clip must maintain a firm pressure on the backup battery at all times RS485 Data Communication Bus AB Lines Communication between the Galaxy control panels and the modules attached to the system takes place on the ABlines ThecommunicationprotocolisRS485format Thecontrolpanelconstantlymonitorsthemodules attached to it Abreak in the communication from any of the modules generates a module tamper a...

Page 21: ... 2 9 TwinAB Line Daisy Chain configuration RS485 Wiring Recommendations Toensurethatthesystemcommunicatesatthemaximumlevelofefficiency thefollowingrecommendations must be adhered to 1 Eachcommunicationlinecansupport32devices Themaximumnumberofdevicesoneachline are Table 2 5 Communication Devices RS485 Recommendations A B A B Galaxy Control Panel 680 Ω EOL 680 Ω EOL A B Keypad Keyprox OR Module Key...

Page 22: ...r supplies should be connected in common to the 0 V of the Galaxy controlpanel 10 Ensure that any extension loudspeakers are not wired in the same cable as an AB pair of wires 11 Where possible ensure that the AB cable is at least 30 centimetres away from any other cables 12 Where possible ensure that the AB cable does not run parallel to other cables for extended distances maximum5metres Figure 2...

Page 23: ...of three reference numbers as shown inthefollowingfigure Figure 2 11 ZoneAddresses For example zone 3057 is the detector connected to line 3 RIO 05 zone 7 Zone Addresses Example 3057 Represents Panel Line No Represents RIO Address Represents Zone No 1 8 on RIO GALAXY G3 PANEL 1 2 3 4 RIO ADDRESS 05 ZONE 7 3 05 7 Galaxy Panel Zone 1001 Zone 1002 Remaining Zones 3 48 Final Exit Intruder 3 144 Final ...

Page 24: ...ard RIO0 Zone address range 1001 1008 Outputs 1001 1004 Onboard RIO1 Zone address range 1011 1018 Outputs 1011 1014 Switch on When the switch is set to this mode the onboard RIO s configure to the following addresses Onboard RIO0 Zone address range 1001 1008 Outputs 1011 1014 Onboard RIO1 Zone address range 0011 0018 Outputs 0011 0014 RIO Switch Table 2 9 End of Line Zone Resistance andConditions ...

Page 25: ... 2 kΩ to 1 kΩ has no effect This is programmed as a Keyswitch in the PROGRAM ZONES option If the keyswitch is spring loaded returns to its normal position the transition from 1 kΩ to 2 kΩinitiates the setting procedure of an unset system and instantly unsets a set system the transition from 2 kΩ to 1 kΩ the return to the normal position has no effect This is programmed as a Keyswitch in the PROGRA...

Page 26: ...ne Wiring s s e r d d A t u p t u O t l u a f e D n o i t c n u F e p y T g n i t a R e t a t S l a m r o N p u l l u p 3 k 3 h t i w t l u a f e D e l b a n E 0 e n i L 1 0 0 1 1 0 0 1 s l l e B d e s i r o t s i s n a r T A m 0 0 4 V 2 1 e v i t i s o P 2 0 0 1 2 0 0 1 e b o r t S e l o P e l g n i S r e v O e g n a h C O C P S y a l e R A 1 V 0 3 d e s i g r e n e e D 3 0 0 1 3 0 0 1 A P d e s ...

Page 27: ...larity of each output can be changed using option 53 PROGRAM OUTPUTS Note For the appropriate 3k3Ω pull up resistor refer to DIPswitch SW3 Table 2 1 The relay output is a single pole change over this can be used to drive output devices that require a clean set of contacts isolated from the output voltage Output Applications 12 V 3k3Ω 1kΩ typical 1kΩ 1kΩ 0 V Cut 3k3Ω to give open collector Typical ...

Page 28: ...overwriting of programminginformationbetweenpanelsusingtheSPIkey Theinformationisstoredinaversionindependentformatwhich allowspanelsofdifferentversionstoshare configurationinformation The panel software can also be updated using the SPI key using the menu structure see Galaxy 3 Series Programming Manual IP1 0033 Option 71 SPI Key SPI Header ...

Page 29: ...IO must be given a unique address before it is connected to a power supply This address is selected using the 16 way Rotary Address Switch SW1 Refer to Figure 3 1 RIOs 3k3Ω pull up resistors IC1 IC2 LED Tamper Switch SW2 LK1 SW4 IC4 Rotary Address Switch 1 2 3 4 Outputs B A RS 485 Power 1 2 3 4 5 6 7 8 Zones SLAVE LK2 LK3 LK4 S IC3 SW1 R1 R3 R5 R7 E E Rev 0 3 Galaxy Panel No of RIO s MAX Valid Add...

Page 30: ...ystem on exiting from engineer mode If the message XX Mod Added To View is displayed the system has recognised that a new module is present Press the A or B keys to confirm that the RIO has been added If this message is not displayed or the RIO is not on the list of added modules then the RIO is not communicating with the control panel or has been set to the same address as the RIO already connect...

Page 31: ...er to Galaxy Remote Input Output RIO Installer s Guide Part Number L 051 supplied with the RIO Entry Exit RIO A RIO is configured as an Entry Exit RIO if resistor LK2 is cut this allows a further sub system to be added to the Galaxy The Entry Exit RIO can be armed while the main system is unset allowing protection ofspecificareas ordisarmedwhenthemainsystemissetallowingaccesstoparticularareaswitho...

Page 32: ...ne 8 from 1 kΩ to 2 kΩ The disarming procedure can be started by activating the final zone zone 7 and gaining access to the keyswitch zoneviatheexitzone zone6 Activatingzones1 5duringthedisarmingperiodresultinanalarmcondition being generated If theEntry ExitRIOis disarmed while the main Galaxy is set then activation of any of its zones programmed as Intruder does not generated an alarm condition o...

Page 33: ...3 144 and 3 520 Connecting the RF RIO The RS 485 AB line of the RF RIO must be wired in parallel daisy chain configuration with the RS 485 AB line of the keypad connected to it The RF RIO requires 12 V d c range 10 5 to 16 0 V and 55 mA This can be supplied from the control panel power supply or from a remote power supply if the distance causes a large voltage drop on the cable RF RIO 1 2 3 4 Outp...

Page 34: ...ll be base address 1 base address 2 base address 3 For example Base address 2 followed by 3 4 and 5 Address Ranges This option allows the programming of the RIO addresses which are to be simulated by the RF RIO For example if the RF RIO being programmed supports 32 zones 4 RIO addresses and the base address programmed at the hexi decimal rotary switch is 02 the available addresses would be 02 03 0...

Page 35: ...neermode Ifthemessage XX Mod Added To View is displayed the system has recognised that a new module is present Press the A or B keys to confirm that the RF RIO has been added If this message is not displayed or the RF RIO is not on the list of added modules then the RF RIO is not communicating with the control panel The flash rate of the red LED LED1 on the RF RIO indicates the status of the commu...

Page 36: ...iewed on the panel however they are not used Figure 3 3 Galaxy Output Module Table 3 9 Valid Output ModuleAddresses O N O N 1 2 1 2 DIP Switch B A Engineer Socket RS485 line Rotary Address Switch Tamper switch and spring MODE TEST TAMPER Bypass Configuration Jumpers B A 0V 12V 12V 0V S screen cable connect RS485 line Module power supply 1 2 3 4 Primary Outputs 5 6 7 8 16 15 14 13 12 11 10 9 LED BU...

Page 37: ... Bterminals Configuring the Output Module TheOutputModuleisconfiguredintothesystemonexitingfromengineeringmode Theprocedureisidentical to that for Galaxy RIO s see Configuring the RIO Outputs Connecting Outputs The Output Module has two types of outputs Primary outputs are taken out on contacts CN1 to CN4 The maximum current load of outputs is 400 mA The outputs are in open collector mode Secondar...

Page 38: ...Configuration Jumpers The Output Module has three configuration jumpers MODE TESTandTAMPER Bypass MODE By disconnecting removing the MODE jumper the Output Module is switched to a mode that reflects output types 17 Horn and 18 E E Horn This mode is not recommended when the Output Module is fitted with Relay Modules as the relay contacts wear faster TEST ByconnectingtheTESTjumperalloutputsbecomeact...

Page 39: ...Operatingtemperature 40 deg C to 85 deg C Currentconsumption 15mA Outputload 4A 230Vac Relay Module Up to four Relay Modules can be connected to the Output Module at connectors RM1 to RM4 The Relay Module increases the maximum current load of one output up to 4A Jumpers JP1 to JP4 are used for setting up the output mode These can either be set to NO Normally Open when the jumper is on the left and...

Page 40: ...dules The 4 outputs are switched 0V 0Vactive Without the jumper links LK1 4 fitted the outputs will float in the OFF state They can apply a 12V signal if required by fitting the appropriate pull up jumper supplied LK5 will short out the off wall tamper if it is not used The SLAVE and E E links must be in place for normal operation FAULT OPAC Thisisanopencollectortransistorwhichisnormallyoff Theout...

Page 41: ...mainsfirst Thisunitcanbepoweredupfromthebatterybymomentarilyshorting LK10 Never leave LK10 connected as deep discharge of the battery will occur LK10 is for start up only Installation Instructions Theinstallationandwiringmustbeperformedbyacompetentengineer TheGalaxy3SeriesPowerSupply Unit must be connected to the a c mains supply 230 240Va c 50Hz via a fused connection outlet The fuse in the mains...

Page 42: ...Outputvoltage nominal 13 8V 14 5V Outputcurrent max 3 0A Operatingtemperature 10 deg C to 40 deg C Aux1 Aux2 Outputvoltage nominal 13 8V Outputcurrent max 0 75A each 14 5V Output not for EN50131 grade 3 use Outputvoltage nominal 14 5V Outputcurrent max 0 15A whenusingthiscurrent theAUX1 AUX2currentswill be reduced by an equivalent amount Batterychargecurrent max 1 4A Maximumripplevoltage lessthan1...

Page 43: ...nd the contents of the eventlogandtheprogrammingdetailsofthesystemtobeprintedout Themoduleisavailablewitheithera 25 way sub D type RS232 serial connector part number A161 OR 6 pin DIN plug part number A134 The printer must have a serial interface port The printer protocol must be set to Printer Interface Protocol Setting Start Bit ON Stop Bit ON Word Length 8 Data Bits Parity None Baud Rate 1200 ...

Page 44: ...heprogramandon lineservicing Figure 3 7 Telecom PCB Layout Connection to the PSTN TheTelecommunicationsNetwork Voltage TNV port LineAand B JP8 on the Module must be perma nently connected hardwired to the Public Switched Telephone Network PSTN via a BT Master Socket Note If the BT Master Socket is the newer type NTE5 then the connection can be carried out by an installation engineer If the BTMaste...

Page 45: ...ition of components on the RS232 PCB may vary with different hardware revisions NOTE This module cannot be used to copy or overwrite programming from the Galaxy 3 144 or 3 520 panels Interface with a PC The panel can be directly linked to a PC via the RS232 module allowing remote servicing via Galaxy Gold or systemsupervisionviaAlarmMonitoringorSIAprotocol RS232 Interface Module MEM BK SW2 TAMPER ...

Page 46: ...face Protocol Table 3 15 Baud rate DIPSwitch Settings Printer Interface DIP Switch Function Setting 1 Printer PC interface ON Printer 2 Stop Bits OFF 1 3 Word Length OFF 8 4 Even Odd Parity N A 5 Parity ON OFF OFF No Parity 6 BAUD Rate Must match printer Baud Rate 7 8 Baud Rate DIP Switch Setting 6 7 8 300 Off Off Off 600 Off Off On 1200 Off On Off 2400 Off On On 4800 On Off Off 9600 On Off On 192...

Page 47: ...dware and software line snatch Comprehensivelinefaildetectionandrteporting Two waycommunicationusingB ChannelandD Channel The ISDN Module is allocated keypad address C on line 1 of the panel and reports itself as Comm Mod 3 As a result of the addition of the ISDN Module keypad address C is not available on line 1 If this keypad is required the ISDN Module should be removed Figure 3 9 ISDN PCB Layo...

Page 48: ...TheaddedEthernetModuleisconfiguredintothesystemonexitingfromengineermodeandisallocated keypad address 15 B If the message XX ModAdded To View is displayed the system has recognised that a new module is present Press the A or B keys to confirm that com 4 has been added If this message is not displayed or the Ethernet Module is not on the list of added modules then the Ethernet Moduleisnotcommunicat...

Page 49: ...icallyforin housesecuritymanagers and allows access to key features of the Remote Servicing program in order to facilitate Eventlogcopying Holidayperiodchanges Summertimedatechange User code amendment Table 3 16 Galaxy PC Products and Order Codes Optional Software Packages M E T S Y S E D O C R E D R O t i K g n i c n e c i L e t i u S g n i c i v r e S e t o m e R T I K 0 3 0 R e d a r g p U e t ...

Page 50: ...Galaxy 3 Series Installation Manual 3 22 ...

Page 51: ...per Off walltamper Addressswitch RS485 serial connector Figure 4 1 Galaxy Mk7 Keypad KeyProx Power Consumption The Galaxy Mk 7 keypad keyProx requires a 12 Vd c supply from the control panel or a remote power supply Thecurrentconsumptionofthekeypad keyProxis Table 4 1 Keypad KeyProx Current draw w a r D t n e r r u C e d o M d a p y e K 7 k M x o r p y e K 7 k M F F O t h g i l k c a b l a n i m o...

Page 52: ...are 2 Use the backplate as a template then mark the locations for the three attachment screws in the requiredposition 3 If it is a new installation use the keyhole slot at the top of the backplate and the two elongated holes at the bottom If replacing an existing Mk3 keypad with a Mk7 keypad use the keyhole slot at the top of the backplate and the two knockout holes at the bottom This means that y...

Page 53: ...Figure 4 2 Galaxy Mk7 Keypad KeyProx Backplate Installation 8 Make sure that the power is disconnected then set the keypad to the required address using the 16 way rotary switch on the PCB 9 To re assemble the keypad connect the four way connector block onto the pins on the keypad PCB Attach the keypad front plate to the back plate by inserting the two clips on the top of the keypad front plate in...

Page 54: ...ngineer mode engineer code esc 8 The Mk7 keypad displays the message 1 MOD ADDED esc CONTINUE Press the esc key the keypad returns to the unset banner NOTE If this message is not displayed the keypad is not communicating with the control panel and has not been configured into the system In this case all connections and addresses should be rechecked NOTE If adding a keyProx to the system the messag...

Page 55: ...he buzzer sounding and the key display beinghighlighted To return keypad to operational mode remove and reapply power Keypad KeyProx Operation Number Keys Table 4 4 Default Codes The number keys are also used once access to the system has been gained to select and modify options View Keys Enter Key These keys are used to initiate the setting of the Galaxy Pressing the A or B key immediately after ...

Page 56: ...s is enabled pressing the ºand keys simultaneously when the normal banner is displayed indicates the group set status R Ready to Set all active zones in group closed F Faulted at least one of the active zones in the group is open S Set P Part Set L Locked Out Group not assigned to keypad Note The Show Status indicates the set conditions of groups when the system is set keypad blank or unset normal...

Page 57: ...system in order to provide continuedprotectionintheeventofamainsfailure Thebatteryisnotincluded Display The Galaxy Keypad KeyProx have a 2 x 16 character backlit display used to display programming informa tionandsystemstatus D E L r e w o P s u t a t S c a s u t a t S y r e t t a B s u t a t S e s u F N O K O c a K O y r e t t a B K O s e s u F h s a l f w o l S l i a F c a K O y r e t t a B K O ...

Page 58: ...he reader to operate MAX mode must be enabled in the panel programming option 63 2 1 Options MAX MAX Mode The MAX addressing function in option 63 2 2 MAX Address is not required for keyprox units Operation The operation of the KeyProx is identical to the Mk7 keypad The proximity reader is seen by the panel as an on line MAX reader It is programmed in exactly the same way with the exception that i...

Page 59: ...memory Note The MAX3 defaults to standalone mode It can be configured to on line mode directly from and of the Galaxy 3 Series control panels On line The MAX3 can operate in on line mode with the Galaxy 3 Series control panel range as a completely inte grated module on the system In this configuration the MAX3 can be used for both door control and alarm systemset unsetcontrolwithcompleteusertracea...

Page 60: ...iguration Thediagramsbelowprovidesdetailsforbothconfigurations TheMAX3 relay is configured in either the NC or NO configuration depending upon the variant purchased MX03 Normally Closed MX03 NO Normally Open NOTE Fitting of an external relay may be required when using AC powered locks Figure 5 1 Online Connection diagram Figure 5 2 Standalone Connection diagram Installation cont d 0 1 2 3 454 ...

Page 61: ...PERATINGMODE of MAX3 to be assigned select 0 On Line and press the ent key NOTE Ifreprogramminganexistingstand alonereader thesystemautomaticallyselectstheOn Line operating mode The MAX3 can then be readdressed The keypad displays the current address of the MAX3 and the range of valid addresses Enter the new MAX3 address and press the ent key the Galaxy then reprograms the ad dress of the MAX3 The...

Page 62: ...s the ent key The MAX3 reader is readdressed as 32 When the reprogramming is complete the MAX3 bleeps LED 3 7 on the MAX3 switches on and the keypad display returns to 2 MAX Address 3 Disconnect the AB line from the MAX3 reader Ensure that all other modules keypads RIOs and on line MAX3 readers are still daisy chained into the Galaxy panel If the MAX3 reader is the last module on the AB line remov...

Page 63: ... while the LED 2 is on and access the area 4 Close the door LED 2 switches off and LED 3 switches on The door must be closed within the programmed Close Timeout if the door remains open longer than this an alarm is activated Card Held Function The MAX3 card can be assigned a single menu option refer to option 42 1 8 CODES User Codes MAX Function To activate the function assigned to the MAX3 card h...

Page 64: ...ew the log of another MAX3 use the A or B key to select the required address To escape from the Access Doors option press the esc key MAX3 Events Print Out The MAX3 events can be printed out as they occur to an on line printer To print the MAX3 events ensure that option 51 27 PARAMETERS On Line Print is enabled Select option 51 28 PARAMETERS On Line Level and enter 2 to print out all system events...

Page 65: ...Focus function will work in either order but if the card is presented first it will simply enable the PIN to gain access to the normal menu see option 42 Codes for programming Timed Anti Passback When theTimedAnti Passback feature is enabled it will prevent more than one use of any particular card at a particularreaderwithinagiventimeperiod Seeoption 63 2 3 6 Options MAX Max Parameters Anti Passba...

Page 66: ...Galaxy 3 Series Installation Manual 5 8 ...

Page 67: ...dance with the manufacturer s recommendations via the relay 3 The Horn output is an open collector This is connected to the output device via a relay NOTE With MAX software version 1 23 the horn output does not function when the reader is programmed as on line operating mode 4 The Egress switch is used to activate the door strike allowing the door to be opened without activating the horn the egres...

Page 68: ...kit box P N MX02 locate the position of the screws and mark and cut out the recess area required NOTE Ensure that there is sufficient wall surface to securely fix the screws 2 Fit the MAX reader into the flush mounting kit push the reader in from the rear ensuring that the four retaining arms on the flush mounting kit click into place 3 Securely attach the module to the wall with 2 No 8 roundhead ...

Page 69: ... MX01 software V1 32 can be reprogrammed as stand alone or on line as often as required In on line mode the horn output is non functioning in stand alone mode the horn output is fully functional Configuring as a Stand Alone MAX 1 Ensure that the MAX is connected to the Galaxy RS485 AB line and the MAX mode is enabled option 63 2 1 OPTIONS MAX MAX Mode 2 Select option 63 2 2 OPTIONS MAX MAX Address...

Page 70: ...s Enter the new MAX address and press the ent key the Galaxy then reprograms the address of the MAX The keypad indicates the old and new MAX addresses and the status of the reprogramming NOTE All new MAX readers default to address 7 It is recommended that when adding a reader it is addressed as the lowest available number on the line When the reprogramming is complete the MAX bleeps the LEDs on th...

Page 71: ...figured into the system Removing a MAX Reader from the System Stand Alone Mode The stand alone MAX reader is not connected to the AB line therefore it can be removed simply by disconnecting the power to the reader There is no requirement to access engineer mode On Line Mode 1 Access engineer mode 2 Disconnect the MAX reader AB line and power 3 Exit engineer mode The message 1 MOD MISSING to View i...

Page 72: ...user card NOTE Access cannot be gained using a standard user card Card Held Function The MAX card can be assigned a single menu option refer to option 42 2 8 CODES User Codes MAX Function To activate the function assigned to the MAX card hold the card in front of the reader for three seconds all of the LEDs switch on If a keypad has been assigned to the MAX function then it displays the details of...

Page 73: ...eturn to the MAX address display To view the log of another MAX use the A or B key to select the required address To escape from the Access Doors option press the esc key Max Events Print Out The MAX events can be printed out as they occur to an on line printer To print the MAX events ensure that option 51 27 PARAMETERS On Line Print is enabled Select option 51 28 PARAMETERS On Line Level and ente...

Page 74: ...Galaxy 3 Series Installation Manual A 8 ...

Page 75: ...w The integrated RIO has eight programmable zones and four programmable outputs It is programmed and operates in exactly the same way as the standard Galaxy RIO The Smart PSU has two separately fused regulated 12 Vd c outputs each capable of supplying one ampere to additional modules and devices A fused regulated voltage is also supplied to charge a 12 volt lead acid stand by battery For further i...

Page 76: ...Galaxy 3 Series Installation Manual B 2 ...

Page 77: ... 20 On Off per group 20 On Off per group Timed Lockout Yes Yes Yes Pre Check Yes Yes Yes Part Set Yes Yes Yes Library Words 538 538 538 RS485 Lines 1 2 4 RIO s 4 8 per line 63 15 line 1 16 lines 2 3 4 Output Module 4 4 per line 4 per line Keypads 8 8 per line 8 per line Keyprox 3 7 3 line 1 4 line 2 24 3 line 1 7 lines 2 3 4 MAX s 4 4 per line 8 per line RS232 Module Support on board 1 optional on...

Page 78: ...Galaxy 3 Series Installation Manual C 2 ...

Page 79: ...issionsystemsandequipment General requirementsforalarmtransmissionsystems EN50136 1 3 1998 Alarmsystems Alarmtransmissionsystemsandequipment Requirementsforsystemswithdigitalcommunicatorsusingthepublic switchedtelephonenetwork EN50136 2 1 1998 Alarmsystems Alarmtransmissionsystemsandequipment General requirementsforalarmtransmissionequipment EN50136 2 3 1998 Alarmsystems Alarmtransmissionsystemsan...

Page 80: ...is product is suitable for use in systems designed to comply with PD 6662 2004 at grade 3 and environ mentalclassII Public Switched Telephone Network PSTN approval The equipment has been approved to Council Decision 98 482 EC for Pan European single terminal connec tion to the Public SwitchedTelephone Network PSTN However due to differences between the individual PSTNsprovidedindifferentcountriest...

Page 81: ...y 1 5A 0 75Adedicated to battery Operatingtemperature 10 deg C to 40 deg C Powersupply TypeA G3 144 520 Total capacity 2 5A 1 25Adedicated to battery Operatingtemperature 10 deg C to 40 deg C Auxiliary 12Voutputs 12Vnominal G3 48 0 5Aintotal 50 0mVmaximumripple Auxiliary 12Voutputs 12Vnominal G3 144 520 1 0Aintotal 50 0mVmaximumripple Fuses AUX1 1 0A 20 mm anti surge AUX2 1 0A 20 mm anti surge BEL...

Page 82: ...e 180x155x35mm LxBxH Doorguard 995g C075 Size 150x185x40mm LxBxH Printer Interface 6 Way DIN Plug 120 g A134 Printer Interface 25 Way D Plug 130 g A161 Box Size 75x52x28mm LxBxH CableSize 2m for 4 Way IDC and 0 3m for 6 Way 25 Way plug PCBs Weight OrderCode 2 75APowerBlock 163g A270 Size 115x102x33mm LxBxH GalaxyPowerRIOControl 118g A250 Size 120x120x43mm LxBxH GalaxyPowerUnitControl 118g A251 Siz...

Page 83: ...x90x15mm LxBxH Note The above weights and order codes are from the populated Printed Circuit Board PCB only Device Quiescent Current mA Device Quiescent Current mA Galaxy 3 48C 150 RS232 Module E054 E055 50 Galaxy 3 144 150 4 Way Relay Interface C037 160 Galaxy 3 144C 150 General Purpose Relay Interface A060 40 Galaxy 3 520 150 Galaxy Mk 7 LCD Keypad 55 Galaxy 3 520C 150 Key Prox 90 Galaxy RIO Not...

Page 84: ...E 4 Galaxy 3 Series Installation Manual ...

Page 85: ...0006 Credit card ASK Keytag YX0 0004 Tear drop ASK Grey Fob YX0 0020 Remote M odules RIO PCB A158 B RIO boxed C072 Telecom Module E062 01 RS232 Module E055 RS232 Module boxed E054 Printer Interface A134 6 pin DIN connector Printer Interface A161 25 way sub D connector ISDN Module E077 Ethernet Module E080 2 RF RIO boxed C076 RF RIO PCB A215 Output Module boxed C078 Output Module Kit PCB A238 Relay...

Page 86: ...Galaxy 3 Series Installation Manual F 2 ...

Page 87: ...allation Procedure 4 2 Keypad Keyprox Operation4 5 L Line Monitoring 2 8 M MAX3 5 1 Memory 2 10 N O On board Power Supply Unit 2 9 Optional Modules and Facilities 3 1 Output Module 3 8 P PCB Layout 2 4 Power Supply Unit 3 12 Power Consumption 4 1 Printer Interface Module 3 15 Q Quick Setup 1 3 R RFRIO 3 5 RS232 Interface Module 3 17 RS 485 Data Communication Bus AB Lines 2 10 RS485 Expansion modul...

Page 88: ...1 2 Galaxy 3 Series Installation Manual ...

Page 89: ...1 3 Galaxy 3 Series Installation Manual ...

Page 90: ...1 4 Galaxy 3 Series Installation Manual Honeywell Security UK 64 Newhouse Industrial Estate Motherwell Lanarkshire ML15SB UK Copyright Honeywell Security II1 0033 Rev 2 0 ...

Reviews: