background image

 

 

7157 602  

EN1B-0003UK07 0402 

 

 

 

 
 

 

 

SmartEye 
Transmitter 

Installation Instructions 
 

 

 

Summary of Contents for 191790

Page 1: ...7157 602 EN1B 0003UK07 0402 SmartEye Transmitter Installation Instructions ...

Page 2: ......

Page 3: ...Contents EN1B 0003UK07 0402 1 Contents Contents 1 Overview 2 Mounting 4 Glossary 13 Technical data 14 Troubleshooting 15 ...

Page 4: ...erature probe e g in a food mobile case cabinet It sends the temperature digital input information to a SmartEye Receiver within the building It monitors the state of a digital input that can be used for applications e g defrost inhibit to prevent over temperature alarms during defrost cycle SmartEye Transmitters should not be confused with Hometronic HB 30 weather sensor range The measured data i...

Page 5: ...Includes 1 SmartEye Transmitter 2 Mounting bracket 3 2 battery cells AA 1 5V type LR6 mignon e g Energiser LR6 or Energizer HI Energy Lithium longer life span 4 Temperature probe cable assembly Not shown 5 TP002K temperature probe Not shown ...

Page 6: ...s Select a different mounting site if radio interference occurs Information on mounting the SmartEye Transmitter Best results are achieved when all devices are mounted at a height where clear RF paths are uninhibited by metal objects When selecting the mounting site ensure that Avoid metal objects directly in the path between SmartEye Transmitter and the SmartEye Receiver Transmitters and Receiver...

Page 7: ... non approved Temperature sensor will result in incorrect temperature readings Digital Input Refer to installation guide of SmartEye Genus Interface for configuration of Digital Input If configured as defrost inhibit connect the Digital Input to NO contacts of a relay activated during the defrost cycle This will prevent over temperature alarms during defrost The Digital Input and Common Ground ref...

Page 8: ... button is located next to the cable assembly socket and is used during the Teach In process in the commissioning stage of the system Mounting the SmartEye Transmitter 1 Securing the mounting bracket The metallic mounting bracket snaps onto the back of the Transmitter When mounting the unit ensure that the horizontal screw hole of the mounting bracket is positioned at the top ...

Page 9: ...ransmitter from the mounting bracket Open the battery compartment Press in the battery lid Pull up the housing frame Remove the battery lid Remove the used battery cells if necessary Dispose of used battery cells in conformance with the local statutory requirements Battery cells should not be disposed of in t he household waste You may be required by local law to dispose of used battery ...

Page 10: ...replace both battery cells Only use 1 5 V AA type LR6 mignon cells e g Energizer LR6 or Energizer HI Energy Lithium longer life span Insert the battery cells into the battery compartment Ensure that the polarity is correct Close the battery compartment and insert the Transmitter into the mounting bracket ...

Page 11: ...able entry hole in the interface box Screw in the stripped probe cable ends into the terminal block following the diagram adjacent or the label on the lid Repeat for digital input cabling if required Mount interface box using screw provided Replace lid The polarity of the Temperature Sensor is not important Green Black Probe return Dig IP Probe Dig IP return SmartEye Transmitter I F Box Link Red C...

Page 12: ...ed length Connect sensor to Transmitter connector as section 3 5 Teach In Refer to SmartEye Receiver Installation Instructions before installing the Receiver 5 1 First time installation requires the R eceiver to be defaulted Whilst holding down the button on the Receiver power it up Keep the button depressed until dEF appears on LCD display 5 2 Press Receiver button again until TEACH appears in th...

Page 13: ...taught in press button on Receiver again to scroll to the next position and repeat steps 5 3 and 5 4 5 6 If a position is skipped scroll on to end the Teach In process This is indicated by on LCD Return to step 5 2 this time scrolling past all Teach In positions to the required position 6 Teach In to Existing System 6 1 Follow steps 5 2 5 6 for all new Transmitters but scroll past all Teach In pos...

Page 14: ...nit must be taught in 7 1 Hold Receiver button until TEACH is displayed 7 2 Press button to scroll through until position of device to be removed is shown 7 3 Hold down button for at least 5 seconds PRESENT will disappear from LCD indicating the successful removal of unit 7 4 Repeat 7 2 7 3 for any other Transmitters to be removed ...

Page 15: ...mitted by the SmartEye Transmitters to the SmartEye Receiver SmartEye Genus Interface Interface unit that converts LONWORKS Network to Genus and performs temperature monitoring SmartEye Receiver Central unit that receives RF data from SmartEye Transmitters SmartEye system Wireless to Genus temperature monitoring system Teach In Assignment method for enabling SmartEye Transmitters to a SmartEye Sys...

Page 16: ...x 76 x 50 mm Power supply 2 Cells 1 5V AA type LR6 Mignon Alkaline or Lithium Temperature measuring range 49 C to 59 Cwith 0 1 C resolution Range 3 to 30 metres System accuracy 0 3 C typical Data transfer interval 240 to 330 seconds Battery Lifespan 1 Year approx Battery cells of the type Energizer HI Energy Lithium extend the permitted operating temperature range of the SmartEye Transmitter to 20...

Page 17: ...o devices Correct the mounting site of the SmartEye Transmitter Problem Cause Remedy SmartEye Transmitter is occasionally off line Genus sys tem alarm Metal obstruct ion in RF path preventing reliable communication Reposition SmartEye Transmitter or the SmartEye Receiver preferably upright in a position of height clear from metal objects LONWORKS is a trademark of Echelon Corporation registered in...

Page 18: ...nsmitter module has weak battery cells Change the battery cells if necessary Also refer to the operating in structions of the SmartEye Receiver Problem Cause Remedy Probe fault reported at Genus equipment Probe open circuit or short circuit Check probe leads and connection Replace probe assembly Teach In carried out without probe connected Press reset Teach In button on SmartEye Transmitter ...

Page 19: ...therwell Lanarkshire ML1 5SB Scotland United Kingdom Tel 44 0 1698 481698 www honeywell elm co uk Subject to change without notice Manufactured by certified to This document is definitive for the enclosed product and replaces all previous publications 7157 602 EN1B 0003UK07 0402 ...

Reviews: