Function

MicroVersaTrip Plus™ and MicroVersaTrip PM™  Trip
Units are designed with UL-listed interchangeable  Rating
Plugs. These Rating Plugs change the per-unit (1

X

)

continuous current rating of the  breaker.  A  circuit
breaker frame equipped with a suitable Rating Plug has a
long-time trip value equal to the ampere  rating marked
on the Rating Plug.

For  example, a breaker frame with a 1600 A sensor and
an 800 A Rating Plug has an 800 A  continuous current
(long-time) rating.

Several Rating Plugs are available for  each sensor rating
and each Rating Plug is keyed for a  particular sensor
rating.

The available Rating Plugs for the AKR and Power
Break® families are listed in Table 1.

Front Label

The  front  label,  shown in Figure 1, is visible when the
Rating Plug is installed. The items listed are:
Sensor Rating (S)

The ampere rating of the
corresponding breaker frame.

Rating Plug Amps (X)

The Rating Plug continuous

current in amperes.

Test

The test-jack receptacle is used
with Test Kit catalog number
TVRMS2 for overcurrent and
ground-fault functional testing.

Catalog Number

Follows the format TRppBqqqq,
where pp refers to the sensor
rating (S) and qqqq refers to
the plug rating (X).

Figure 1. Front of Rating Plug, showing label.

UL Label

The UL label is  mounted on the side  of the Rating Plug
and is not  visible  when the Rating Plug is installed. The
label lists the circuit  breaker frames  that will accept  that
Rating Plug.

Installation

Before installing a  Rating  Plug  into a MicroVersaTrip
Plus or PM Trip Unit, inspect the plug  for  damage,  then
follow these steps:

1

1

1

1 .... Verify that the Rating  Plug catalog number

matches the desired continuous current rating  (X)
and the sensor rating (S) on the breaker frame.

2

2

2

2 .... Hold the Rating Plug between the thumb and

forefinger, then push  it  into the Trip Unit. Proper
engagement is verified by a click.

C

C

C

C A

A

A

A U

U

U

U T

T

T

T IIIIO

O

O

O N

N

N

N :::: Do not attempt to push  the Rating Plug

into the Trip Unit if there is resistance. This may
indicate the wrong Rating Plug for the sensor rating.  Stop
immediately and verify that the breaker  sensor  rating (S)
and the Rating Plug nameplate “S=” value are the same.

Removal

The Rating Plug is seated firmly in the Trip Unit. As
illustrated in Figure 1, there are tabs at the sides of the
Rating Plug  for removal. A Rating Plug Removal Tool,
catalog number TRTOOL,  also  known as an integrated
circuit (DIP) extractor, is required  to remove the Rating
Plug. Grasp the tabs of the Rating Plug with  the tool, as
illustrated in Figure 2. Be careful to hold the tabs and not
the  front  cover, as the Rating Plug could be damaged
otherwise. Gently pry the Rating Plug  out by pulling  away
from the  Trip  Unit.  A  left–right  wriggling motion assists
the removal.  Insure  that the tabs are held securely until
the Rating Plug is completely removed.

N

N

N

NO

O

O

OT

T

T

TE

E

E

E:::: Protection to the breaker is  maintained  at  only

25% of the sensor rating when the Rating Plug is
removed. If the breaker is carrying more than  25%  of the
sensor load rating, the breaker will trip after the time-
delay setting.