background image

 

 

 

© 2010 GE Security, Inc. 

1 of 6

P/N 1061018 • REV D • ISS 10FEB10

Description 

The 250-CO Carbon Monoxide Detector monitors the levels of CO 
gas and gives early warning when potentially dangerous levels 
exist. It does not detect fire, smoke, or any other gas.  

The 250-CO provides a multicolored LED and a sounder to indicate 
the detector status. Use Table 1 to determine the status of the 
detector. The detector automatically resets when CO is no longer 
detected. 

The 250-CO Carbon Monoxide Detector is intended for indoor-
dwelling unit applications in both residential and commercial 
occupancies, including single/multiple family residential 
occupancies, hotel rooms, dorm rooms, and other areas approved 
by the authority having jurisdiction (AHJ). 

The 250-CO detector can connect to either UL 985 (Household Fire 
Warning) or UL 864 (Commercial Fire) control panels. It is not 
intended for use in industrial applications such as gasoline 
refineries or parking garages, which require different listings. 

The 250-CO detector is not intended to meet the requirements of 
CAN/CSA-6.19 (Residential Carbon Monoxide Alarming Devices). 
Please check with the local codes concerning the applicability of 
this requirement for each installation. 

The 250-CO detector has an optional adapter mounting plate. To 
purchase the plate order P/N 250-COPLT-5PKG. 

Features 

Test/hush button:

 Use the test/hush button to test the alarm and 

silence an activated alarm. Pushing the test/hush button silences 
the integral sounder for five minutes. The red alarm light stays on, 
and if CO is still present after five minutes, the detector once again 
sounds in the temporal-four pattern. The hush feature does not 
operate at CO levels above 350 ppm (parts per million). 

Distinct 85 dB temporal-four sounder alarm:

 The 85 dB 

temporal-four sounder provides a distinctive alarm notification 
that is easy to differentiate from smoke alarm notification devices. 
The alarm beeps four times, pauses five seconds and then repeats 
the pattern. 

The built-in sounder is a supplementary alarm notification device. 
The control panel is considered the primary alarm notification 
device. 

WARNING: 

Use only with a UL Listed control panel that recognizes 

different alarm types (fire, burglary, CO, etc.) and that provides a 
distinct notification for each type. 

Sensor end of life indicator:

 The detector uses both a flashing 

green LED and intermittent sounder chirps to indicated that the 
detector needs replacing. The detector also signals a trouble 
condition when the CO sensor reaches end-of-life. When 
connected to a UL Listed control panel, the trouble relay can 
report a trouble condition locally at the panel and optionally at the 
central station, if the system is monitored. 

Common trouble relay:

 The trouble relay opens to indicate a 

trouble condition upon lost power, CO sensor cell trouble, or cell 
end-of-life. 

Figure 1: Recommended CO detector locations 

 

 CO 

detector 

locations 

 

GE 

Security 

250-CO Carbon Monoxide 

Detector Installation Sheet 

Summary of Contents for 250-CO

Page 1: ...he alarm and silence an activated alarm Pushing the test hush button silences the integral sounder for five minutes The red alarm light stays on and if CO is still present after five minutes the detector once again sounds in the temporal four pattern The hush feature does not operate at CO levels above 350 ppm parts per million Distinct 85 dB temporal four sounder alarm The 85 dB temporal four sou...

Page 2: ...on The 250 CO Carbon Monoxide Detector is a four wire device designed to use a Class 2 output from a UL 985 or 864 Listed control panel or auxiliary power supply All wiring must conform to the NFPA 70 National Electric Code UL 2075 Standard for Gas and Vapor Detectors and Sensors NFPA 720 Standard for the Installation of Carbon Monoxide CO Detection and Warning Equipment and applicable codes Use 1...

Page 3: ...ring and Figures 3 to 5 below and insert the wires under the appropriate screw terminals 10 Tighten both screws to secure the base to the wall plate 11 Replace the detector cover 12 Apply power The LED should flash green for approximately four seconds and then pulse green 13 Test per testing instructions below Figure 2 Screw terminals 1 2 3 4 1 Sounder 2 Sensor 3 Alarm relay 4 Terminals and are fo...

Page 4: ... occurs signaling end of life To silence the detector push the test hush button Figure 3 Single device single zone configuration 1 2 PWR PWR 1 Alarm IDC NO 2 End of line device provided by the life safety system Note Relay is shown in the normal state for this detector Figure 4 Multiple devices single zone configuration 2 1 PWR PWR 1 Alarm IDC NO Note Relay is shown in the normal state for this de...

Page 5: ... may also prevent the detector from being heard if distance or closed or partly closed doors muffle the sounder This unit is not designed for the hearing impaired CO detectors are not a substitute for life insurance Though these detectors will warn against increasing CO levels we do not warrant or imply in any way that they will protect lives from CO poisoning They should only be considered as an ...

Page 6: ...6 of 6 P N 1061018 REV D ISS 10FEB10 ...

Reviews: