background image

UTY-DCGYZ1
UTY-DCGGZ1

PART NO. 9378379206-03

[Original instructions]

OPERATING MANUAL

CENTRAL REMOTE CONTROLLER

KEEP THIS MANUAL FOR FUTURE REFERENCE

Summary of Contents for Airstage UTY-DCGGZ1

Page 1: ...UTY DCGYZ1 UTY DCGGZ1 PART NO 9378379206 03 Original instructions OPERATING MANUAL CENTRAL REMOTE CONTROLLER KEEP THIS MANUAL FOR FUTURE REFERENCE ...

Page 2: ...ion 27 3 2 3 Sound Setting 28 3 2 4 Date Setting 28 3 2 5 Password Setting 30 3 3 Maintenance 31 3 3 1 Error History 31 3 3 2 Display Sensor Values 31 3 3 3 Information 32 3 4 Installer Setting 33 3 4 1 Language Setting 33 3 4 2 Central Controller Address Setting 33 3 4 3 Indoor Unit Registration 34 3 4 4 Temp Unit Setting 36 3 4 5 Remote Setting 36 3 4 6 External Input Setting 37 3 4 7 Mail Setti...

Page 3: ...VER CAUSED AND ON ANY THEORY OF LIABILITY WHETHER IN CONTRACT STRICT LIABILITY OR TORT INCLUDING NEGLIGENCE OR OTHERWISE ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE Portions based on XySSL Copyright C 2006 2008 Christophe Devine Copyright C 2009 Paul Bakker polarssl_maintainer at polarssl dot org All rights reserved Redistribution and use in...

Page 4: ...unit Do not repair or modify by yourself It may cause a fault or accident Do not use flammable gases near the unit It may cause a fire from leaking gas CAUTION This mark indicates procedures which if improperly performed might possibly result in personal harm to the user or damage to property Do not set vessels containing a liquid on this unit Doing so will cause heating fire or electric shock Do ...

Page 5: ...from general purpose equipment to VRF system batch operation stop emergency stop is enabled Or external output from VRF system to general purpose equipment operation stop signal normal abnormal signal is also enabled B VRF System This is all of the indoor units outdoor unit as well as those of relevant control equipment Central remote controller standard remote controllers that are connected with ...

Page 6: ...s the ID individually assigned to each indoor unit and is used for control J Remote controller address 0 15 This is the group of indoor units that have been connected with remote controller cable or single indoor unit K R C G address Remote controller group R C G address is made up of the refrigerant system address and the indoor unit address of indoor unit with remote controller address 0 Hereaft...

Page 7: ...tioner operating status can be monitored set and controlled Operation system Refer to Chap 2 Batch Setting Individual Setting Schedule Setting Master setting system Refer to Chap 3 Menu Select screen 1 Group Setting 2 Preference 3 Maintenance 4 Installer Setting ...

Page 8: ...es of screen input From main screen you can access to desired setting screen by simple operation When setting at small pop up display in this controller you can set while checking the information of the screen behind pop up 1 4 1 Name of Part Main screen Left menu Always display Menu button Group or R C G button Group scroll button R C G scroll button Group expansion cancel button Other sample scr...

Page 9: ...rrent screen End Ends the process and closes the pop up Icon The functions such as Delete and Copy are iconized Icon Description Deletes the currently displayed setting Copies the currently displayed setting Adds the new timer However when the number of settings reaches the upper limit this button is disabled Deletes the selected line Copies the selected line Adds the new line However when the num...

Page 10: ...screens are operated The menu is closed after 20 minutes passes The left menu of monitoring screen is not closed even when other screen is operated or 20 minutes passes The pop up with display releasing condition continues to display until the condition is satisfied For example the pop up display notifying that VRF system is in a special state is not closed until the special state is released Samp...

Page 11: ...gisters the group name Max 13 characters Up to 50 groups can be registered Delete icon Deletes the group When there is no group after deletion There is no group to display is displayed New icon Adds the group When the number of registered groups reaches 50 this button is disabled Already selected R C G Indicates that the R C G is already selected by other groups R C G list When selected checkbox i...

Page 12: ...er initialization is set the following wizard are displayed in wizard format Perform the settings 1 Language Setting Refer to 3 4 1 4 2 Panel Calibration Refer to 3 2 2 4 3 Central Controller Address Setting Refer to 3 4 2 4 4 Indoor Unit Registration Registration Refer to 3 4 3 3 5 Date Setting Refer to 3 2 4 1 3 2 4 2 Automatic scan for all units connected at initial start up is performed and on...

Page 13: ...oup setting are displayed on the Monitoring screen Refer to 3 3 1 The display item can be set on the Monitoring screen Refer to 2 1 1 R C G are expanded in dotted line R C G belonging to the tapped group are displayed 4 2 3 5 6 7 9 8 When the triangle mark on the bottom right corner is tapped the R C G belonging to the group are displayed When the R C G are expanded the bottom right corner of squa...

Page 14: ...lays as follows Outdoor unit Outdoor Unit Indoor unit Group name or R C G name This controller Central Controller Schedule icon Displays the operation schedule setting screen Refer to 2 3 Change Items icon Sets the contents to be displayed on the screen Refer to 2 1 1 Menu button Displays the Setting Menu screen by tapping this button which is always displayed Refer to Chap 3 Group display Display...

Page 15: ... are stopped Yellow Even one unit of groups or R C G is on a test operation Displayed regardless of operation mode The icons of R C prohibition Temp upper and lower limit and Schedule are displayed when Management Status is checked Refer to 2 1 1 When the room temperature is out of the room temperature sensor range the icon of over upper limit or below lower limit is displayed Display icon When re...

Page 16: ... be displayed Initial value Auto Auto When the number of registered group is 6 or less icons are large When it is 7 or more icons are small Large Icons are large maximum number of display group 6 Small Icons are small maximum number of display group 12 2 2 Operation Setting Perform the operation setting for the group or R C G registered to this controller 1 Batch setting Performs the same setting ...

Page 17: ...ing range Auto 18 to 30ºC 64 to 88ºF Cool Dry 18 to 30ºC 64 to 88ºF Heat 10 to 30ºC 44 to 88ºF Set Temp Custom Auto Heat Fan Speed Sets Fan Speed Auto High Med High Med Med Low Low Quiet Air Flow Direction Sets Air Flow Direction Refer to 2 2 2 1 Anti Freeze Sets Anti Freeze operation Select On or Off Economy Sets Economy operation Select On or Off Temperature Limit Sets Temp Limit Refer to 2 2 2 ...

Page 18: ...limit setting of Auto Cool Dry and Heat No Item Description Set temperature Enable Disable Sets Enable or Disable of upper and lower limit setting Select from Enable or Disable Auto upper limit Sets the Auto upper limit with 0 5ºC 1ºF increments Range 18 0 to 30 0ºC 64 to 88ºF Auto lower limit Sets the Auto lower limit with 0 5ºC 1ºF increments Range 18 0 to 30 0ºC 64 to 88ºF Cool Dry upper limit ...

Page 19: ...Timer and Filter Reset can be set to prohibited state When All is checked other checkboxes are disabled 2 3 Schedule Setting When the password is set at start up enter the password Refer to 3 2 5 1 Tap the Schedule icon of left menu on the monitoring screen 2 Tap Create New Schedule or schedule name The pop up of schedule detail setting is displayed When the schedule is not set Create New Schedule...

Page 20: ... Delete icon Deletes the currently displayed schedule Copy icon Newly creates the same schedule as the setting schedules at the end of the existing schedules and displays the new creation screen New icon Creates the new schedule at the end of the existing schedules and displays the new creation screen Day of week Switches the timer to be set to the day of week Create new timer Day Off Deregister a...

Page 21: ...ton Displays the R C G registered to the group 2 3 2 Timer Detail Setting Set the details of timer setting 1 2 5 3 6 4 7 8 9 When Select Delete is selected 1 Select the timer you want to delete When you try to delete the timer setting to the schedule Timer cannot be deleted because it is used for the following schedule To delete this reset the schedule setting is displayed Note ...

Page 22: ...ist number is the smallest number of 1 to 10 which is not listed Time Sets the timer time Refer to 2 3 2 1 On Off Selects On or Off Cancels the change by selecting Reset Mode Selects the mode Auto Cool Dry Fan and Heat Selectable mode depends on the indoor unit Deletes the change by selecting Reset Set Temp Selects the set temperature with 0 5ºC 1ºF increments Setting range 10 to 32ºC 44 to 91ºF C...

Page 23: ...imer No Item Description Hour Selects the set time hour of timer When selected the time is checked Minute Selects the set time minute of timer When selected the time is checked AM PM Selects the set time AM PM of timer When selected AM or PM is checked ...

Page 24: ...ding day of week is reset Example When Day off is set to Monday After Day off setting is determined Day off is enabled until next Monday Monday schedule is disabled On Tuesday the Day off setting of Monday is reset The disabled schedule is reset and the setting returns to its original state 1 Tap the Schedule 2 Tap the Day Off All 3 Set the item and tap the OK button No Item Description Day of wee...

Page 25: ...he date and time 3 2 4 5 Password Setting Sets the passwords 3 2 5 3 Maintenance 1 Error History Displays the error history 3 3 1 2 Display Sensor Values Displays the sensor values 3 3 2 3 Version Displays the version information 3 3 3 4 Installer Setting 1 Language Setting Sets the languages 3 4 1 2 Central controller Address Setting Sets the Central Controller address 3 4 2 3 Indoor Unit Registr...

Page 26: ...escription Group name Registers the group name Max 13 characters Up to 50 groups can be registered The names can be input using keyboard and they can also be selected from the fixed form phrase Delete icon Deletes the group When there is no group after deletion There is no group to display is displayed New icon Adds the group When the number of registered groups reaches 50 this button is disabled ...

Page 27: ...ss Sets the brightness Dark 1 2 3 Bright Screen lit while in error status Selects Enable or Disable of the setting for emergency light on Enable Disable 3 2 2 Panel Calibration Calibrate the position of LCD panel The buttons on the touch panel operate normally by calibration Only procedure 4 is displayed at initial setting 1 Tap the MENU button 2 Tap the Preference 3 Tap the Panel Calibration 4 Ta...

Page 28: ...able Disable 3 2 4 Date Setting Perform the setting for date and time 3 2 4 1 is displayed at initial setting 1 Tap the MENU button 2 Tap the Preference 3 Tap the Date Setting 4 Select the process from the submenu below No Item Description Display Format Setting Sets the display format of date and time Refer to 3 2 4 1 Date and Time Setting Sets the date and time of the system Refer to 3 2 4 2 Sys...

Page 29: ...ly Summer Time Setting When summer time system is used tap the Enable 4 Time Zone Setting In the displayed list as shown at the left figure set the time zone of the area where this controller is installed Date and Time are displayed in the format set at 3 2 4 1 Display Format Setting 3 2 4 3 System Clock Adjustment Perform the system clock adjustment 1 Set the item and tap the OK button No Item De...

Page 30: ...d Changes the password Initial value 0000 Refer to 3 2 5 1 Change Setting Changes the password setting Refer to 3 2 5 2 3 2 5 1 Change Password 1 Set the item and tap the OK button No Item Description Change Password Sets 4 to 8 digits password when it is set Enter the password twice 3 2 5 2 Password Setting 1 Set the item and tap the OK button Initial value All Enable No Item Description Group Se...

Page 31: ...ime Error occurrence date and time Name Units where an error occurs One of Indoor Unit R C G name Outdoor Unit and Central Controller Address Address of the units where an error occurs Indoor Unit Refrigerant system No Unit No R C G internal identification No Outdoor Unit Refrigerant system No Unit No Central Controller Address of this controller Model name One of Indoor Unit R C G name Outdoor Un...

Page 32: ...ress For Outdoor Unit Refrigerant system No Unit No 6 Sensor values of the tapped unit are displayed Sensor Name Value Date Time Mail When the Mail button is tapped Send screen is displayed and sensor value information is sent to the set mail address Refer to 3 4 7 3 3 3 Information The version of this software and MAC Address are displayed 1 Tap the MENU button 2 Tap the Maintenance 3 Tap the Inf...

Page 33: ...utsch Français Italiano Pycckий Português Türkçe Język polski Ελληνικά Dutch 中文 3 4 2 Central Controller Address Setting Set the address of this controller Only procedure 4 is displayed at initial setting 1 Tap the MENU button 2 Tap the Installer Setting 3 Tap the Central Controller Address Setting 4 Tap the address list 00 15 When 2 or more controllers are installed in the system set the address ...

Page 34: ...ed address is not deleted Note 3 4 3 1 Address Number Registration Register the indoor units in the specified refrigerant system range 1 Set the item and tap the Register button No Item Description Refrigerant System Range Inputs Refrigerant System Range to be registered for indoor unit Initial value 00 99 Setting of Network Priority Mode Selects from Priority Mode or Normal Priority Mode Performs...

Page 35: ...mallest unregistered number of 1 to 50 2 Register the indoor unit Refer to 3 4 3 3 3 4 3 3 Registration For registration Confirmation mode and Delete mode are available Confirmation mode 1 When R C G is tapped the indoor unit addresses belonging to R C G are displayed Delete mode 2 There is a Select Delete button on the Confirmation of Registration Indoor units screen When Select Delete button is ...

Page 36: ...ng 3 Tap the Remote Setting 4 Set the item and tap the OK button No Item Description Wired LAN Selects whether LAN connection is used or not Refer to 3 4 5 1 Network Setting Sets the network when LAN connection is used Refer to 3 4 5 2 3 User ID Sets the user ID Max 20 characters for remote login when LAN connection is used 4 Password Sets the user password Max 20 characters for remote login when ...

Page 37: ...ess Sets IP address of remote terminal 2 Subnet Mask Sets Subnet mask of remote terminal 3 Default Gateway Sets Default Gateway of remote terminal 4 Primary DNS Inputs Primary DNS Domain Network Service of remote terminal 5 Secondary DNS Inputs Secondary DNS Domain Network Service of remote terminal Input 0 to 255 at 3 4 6 External Input Setting Perform the external input setting 1 Tap the MENU bu...

Page 38: ...1 Mail Setting 1 Set the item and tap the OK button No Item Description Error notification Sets Enable or Disable of mail notification when an error occurs 2 Email Address Sets the mail address destination when Error notification or Room temperature notification is sent 3 Transmission Test Performs Transmission test to send the notification mail Transmission result display Failed sending mail Mail...

Page 39: ... prevent you from forgetting to turn off 1 Tap the MENU button 2 Tap the Installer Setting 3 Tap the Timer Setting 4 Set the item and tap the OK button No Item Description Auto Off Timer Sets Enable or Disable of the timer When Enable is selected 2 to 5 are enabled 2 Operation Stop Time Sets Operation Stop Time in 10 minutes unit 30 240 min 3 Time Range Selects Time Range Range Spec Continuous 4 S...

Page 40: ...l be deleted and returned to the factory default setting by this function Please use this function with great caution 1 Tap the MENU button 2 Tap the Installer Setting 3 Tap the Initialization 4 When initializing this controller tap the OK button Wait for a while without turning off the power After the initial setting screen appears set according to the wizard Refer to 1 5 2 3 1 ...

Page 41: ...nce that there are no malfunctions of the air conditioner Be sure that the airflow from the air conditioner will not cause any adverse effects Objects may fall down causing personal injury fire or damage to property If you know that there are people in the vicinity of the air conditioner inform them in advance that you will be operating and stopping it from a distant location Sudden operation or s...

Page 42: ... 3 Monitoring screen for remote control is displayed 4 2 Monitor Tablet Screen 4 2 1 Monitoring screen 1 Check the checkbox of R C G to be changed for the setting No Item Description Menu button Selects the process Monitor Refer to 4 2 Change Password Refer to 4 3 Unit display order Refer to 4 4 Environment Setting Refer to 4 5 Select All Selects Checks all R C G 3 Operation Sets the operation Ref...

Page 43: ...is Custom Auto Applied indoor unit and non applied outdoor unit cannot be mixed Fan Speed Sets the air volume Air Flow Direction Sets the air flow direction for vertical and horizontal directions Clear All button Resets the screen and returns to the original status Send button Sends the setting contents to the Central Controller 4 3 Change Password Set the password 1 Set the password Input the fol...

Page 44: ...En 44 4 5 Environment Setting Set the temp unit for this system display 1 Select ºC or ºF of temp unit and tap it ...

Page 45: ...nformation Error message or Refrigerant leakage is displayed on the screen Contact the service department as necessary Error information is displayed Confirm the error location For the error code concerning indoor unit and outdoor unit refer to the manual of each unit Indoor unit Error code Address Model Name Group Name R C G Name Outdoor unit Error code Address Model Name Name Fixed to Outdoor Un...

Page 46: ...h the controller cannot be operated When the release notification is received from external input release Emergency Stop 5 2 2 When a signal is received from VRF system When a signal is received from VRF system the following message is displayed at the forefront of the screen Operation suspended An external signal for emergency stop has been detected from the another VRF device during which the ce...

Page 47: ...e temperature range C F 0 to 40 32 to 104 Usage humidity range 0 to 85 no condensation Storage temperature range C F 20 to 70 4 to 158 Storage humidity range 0 to 85 no condensation Dimensions H W D mm in 134 6 216 2 37 9 5 5 16 8 1 2 1 1 2 Weight g oz 800 28 2 The liquid crystal panel is manufactured using high precision technology but there may be 0 01 or less mixing pixels or continuously light...

Page 48: ......

Reviews: