AC Power
For 

Business-Critical Continuity™

Liebert

®

 MicroPOD

 230V

User Manual

Summary of Contents for Liebert MicroPOD MP2-210K

Page 1: ...AC Power For Business Critical Continuity Liebert MicroPOD 230V User Manual ...

Page 2: ......

Page 3: ...ON 8 7 1 Transfer to Maintenance Bypass 8 7 2 Transfer to UPS 8 8 0 SPECIFICATIONS 9 9 0 TROUBLESHOOTING 10 9 1 Product Warranty Registration 10 FIGURES Figure 1 UPS mode of operation 3 Figure 2 Mains Maintenance Bypass mode 3 Figure 3 Liebert MicroPOD connections 4 Figure 4 Attaching Liebert MicroPOD to the UPS with securing brackets 5 Figure 5 Liebert MicroPOD mounting bracket location 6 Figure ...

Page 4: ...ii ...

Page 5: ...eceptacle contact a qualified electrician or your local dealer or Emerson representative for assistance Route power supply cords so they are not walked on or pinched in anyway WARNING Do not attempt to service this product yourself Opening or removing the cover may expose you to dangerous voltages even when the AC cord is disconnected from the electrical outlet Refer all servicing to qualified ser...

Page 6: ...t Consult the manual for additional information MAINS MAINS lamp indicates local power is available and the load may be transferred to bypass the UPS UPS UPS lamp indicates UPS power is available and the load may be transferred to the UPS to provide computer grade power to the load i ...

Page 7: ...oned power to the load as shown in Figure 1 Figure 1 UPS mode of operation In Mains mode power is routed around bypassing the UPS system see Figure 2 Mains power is supplied directly to the load through the Liebert MicroPOD Figure 2 Mains Maintenance Bypass mode The UPS may be turned off and removed without affecting the load See Figure 3 Figure 3 Liebert MicroPOD connections NOTE Battery backup a...

Page 8: ...e two Liebert MicroPOD securing brackets optional for Liebert GXT series UPS to the rear of the UPS see top of Figure 4 You will need a long M3 Phillips head screwdriver for this procedure the torque is 7 in lb or 0 79 Nm The Liebert MicroPOD brackets have a hole to allow the screwdriver to reach the screw 6 Next attach the Liebert MicroPOD to the securing brackets see Figure 4 The Liebert MicroPO...

Page 9: ...MicroPOD face it in that direction then attach the brackets to the Liebert MicroPOD with the screws provided 5 Consult your rack enclosure manufacturer s recommendations for specific rack mounting hardware that will be required 6 The holes on the rack mount bracket are notched for easy installation Tighten the Liebert MicroPOD securely to the rails and then follow the startup directions for the Li...

Page 10: ...oPOD is illuminated If so transfer the rotary switch from MAINS to UPS The load is now being supplied with conditioned power through the UPS 8 Before any operation or procedure always verify that both the UPS lamp green and the Mains lamp amber are illuminated before changing the rotary switch CAUTION This UPS must be installed by properly trained and qualified personnel and wired in accordance wi...

Page 11: ...s power is not present this lamp will be off and the UPS will supply battery backup power to connected loads 6 2 UPS Indicator Lamp This green lamp is illuminated when output power is available from the UPS see Figure 6 It sig nals that it is safe to transfer connected loads from mains power back to UPS output power Figure 6 Indicator lamps on Liebert MicroPOD Green lamp Output power available fro...

Page 12: ...PS off 4 Disconnect the two cables connecting the UPS to the Liebert MicroPOD 5 The UPS is prepared for servicing 7 2 Transfer to UPS To transfer to UPS from maintenance bypass mains use the following steps 1 Reconnect the UPS to the Liebert MicroPOD Start the UPS according to the instructions in the UPS user manual 2 Verify that UPS lamp green on the Liebert MicroPOD is illuminated If so transfer...

Page 13: ... Specifications AC Input EN60320 C14 receptacle EN60320 C20 receptacle EN60320 C20 receptacle Connection to UPS Input EN60320 C13 receptacle EN60320 C19 receptacle EN60320 C19 receptacle Connection to UPS Output EN60320 C14 receptacle EN60320 C20 receptacle EN60320 C14 receptacle Output Receptacles Protection 4 EN 60320 C13 with 10A circuit breaker 4 EN 60320 C13 with 10A circuit breaker 2 EN 6032...

Page 14: ... to mains Refer to Liebert MicroPOD installation instructions in this manual 4 1 Installation on a Liebert GXT UPS and 4 2 Rack Mount Installation UPS Available lamp green not illuminated UPS output power not present Turn on UPS Refer to UPS user manual UPS input and or output cord not connected to Liebert MicroPOD Refer to Liebert MicroPOD installation instructions in this manual 4 1 Installation...

Page 15: ......

Page 16: ... change without notice Liebert is a registered trademark of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS Server Cabinets liebert upstech emerson com 800 222 5877 Outside North...