Surge Protective Devices

IE Series

Summary of Contents for IE Series

Page 1: ...Surge Protective Devices IE Series ...

Page 2: ...IE Series Page B ...

Page 3: ...sible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE NOTICE is used to address practices not relate...

Page 4: ... This equipment must be effectively grounded per all applicable codes Use an equipment grounding conductor to connect this equipment to the power system ground Do not supply more than 24VDC 24VAC and no more than a current of 2A to contacts Confirm that the Surge Protective Device voltage rating on the module or nameplate label is not less than the operating voltage Failure to follow these instruc...

Page 5: ... secure 4 Connect the supply cables to the line side of the device 5 Complete the circuit by connecting cables from the load of the device to the protected equipment Note A dry contact connection is available 6 Check that all connections are secure Remove all tools and discarded hardware from the unit 7 Replace the barrier cover door and or trim to the equipment 8 Equipment may be re energized aft...

Page 6: ... Maximum Continuous Operating Voltage MCOV 150V L N L G N G 320 L L Frequent Response Normal Mode forward reverse 100 kHz to 50 MHz 90 dB Max Common Mode forward reverse 5 kHz to 50 MHz 60 dB Max Transient Reduction IEEE C62 41 All Voltage configurations are single phase 2 wire ground Typical Category A Ringwave 6 kV 200 A 100 kHz 60 V peak Typical Category B Ringwave 6 kV 500 A 100 kHz 100 V peak...

Page 7: ...s DIN rail or surface mount Line Neutral Ground 18 12 AWG 4 lb in 0 45 N m 32 F to 77 F 0 C to 25 C IE103 IE105 IE110 IE120 14 10 AWG 7 lb in 0 45 N m IE203 IE205 12 10 AWG IE210 IE220 1 Contains no serviceable parts Figure 1 DIN Rail Installation and Removal Figure 2 DIN Clips Note DIN Rail clips can be positioned for vertical or horizontal installation ...

Page 8: ...quipment PPE and follow safe electrical work practices See NFPA 70E CSA Z462 or NOM 029 STPS Failure to follow these instructions will result in death or serious injury Indicator Status ON The device is installed correctly and the line side has power Indicator Status OFF Check connections verify that the line voltage is at the point of connection if all is correct then replace the device Dry Conta...

Page 9: ... 77 7 4 06 103 1 3 83 in 97 2 mm 3 06 in 77 7 mm 4 06 in 103 1 mm Catalog Numbers Weights lb kg IE103 0 94 lb 0 42 kg IE105 0 95 lb 0 43 kg IE110 1 2 lb 0 58 kg IE120 1 4 lb 0 64 kg IE203 0 94 lb 0 42 kg IE205 0 95 lb 0 43 kg IE210 1 2 lb 0 58 kg IE220 1 4 lb 0 64 kg ...

Page 10: ... USA 847 268 6651 Warranty Please refer to the Terms Conditions of Sale document While every precaution has been taken to ensure accuracy and completeness in this manual Appleton Grp LLC d b a Appleton Group assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions ...

Page 11: ...IE Series Page 8 ...

Page 12: ...toria T 61 3 9721 0387 Europe ATX SAS Espace Industriel Nord 35 rue André Durouchez CS 98017 80084 Amiens Cedex 2 France T 33 3 2254 1390 China Sales Office Shanghai T 86 21 3338 7000 Canada EGS Electrical Group Canada Ltd 99 Union Street Elmira ON N3B 3L7 Canada T 1 888 765 2226 Middle East Sales Office Dammam Saudi Arabia T 966 13 510 3702 Chile Sales Office Las Condes T 56 2928 4819 India Sales...