background image

 

 

 

PACSystems™ RX3i Central Processing 

Unit IC695CPE302

 

Quick Start Guide  

GFK-3038B 
Sept 2019  
 

Summary of Contents for IC695CPE302

Page 1: ...PACSystems RX3iCentralProcessing UnitIC695CPE302 QuickStartGuide GFK 3038B Sept2019 ...

Page 2: ... Ethernet Port 5 Serial Port 6 Removable Data Storage Devices RDSDs 6 Energy Pack 7 Light Emitting Diode Indicators LEDs 7 Hardware Installation 10 Initial Checks 10 Installation Location 10 InstallationinHazardous Areas 11 Class 1 Divison 2 Groups ABCD 11 ATEX Zone 2 12 Module Installation 12 Module Initial Startup 13 Initial Configuration 14 ...

Page 3: ...ovisioning mode Supports the new PAC Security tool available for certificate trust management of clients and servers Contains 5 Mbytes of user memory and 5 Mbytes of non volatile flash user memory Supports Battery less retention of user memory Configured with an Energy Pack IC695ACC400 to power the CPU long enough to write user memory to non volatile storage NVS on system power loss Equipped with ...

Page 4: ...refer to the PACSystems RX3i TCP IPEthernet Communications User Manual GFK 2224 Supports OPC UA Supports Ethernet Global Data Class 1 Supports HART Pass Through Time synchronization to SNTP Time Server on Ethernet network when used with arack based Ethernet module IC695ETM001 version 5 0 or later Enhanced ability to display serial number and date code in PME s Device Information Details Ability to...

Page 5: ...SD Off Disables RDSD data transfer Download Stores application from RDSD to CPU Run Mode Switch A three position switch which operates as follows Switch Position CPU and Sweep Mode Memory Protection Run I O Enable The CPU runs with I O sweep enabled User program memory is read only Run Output Disable The CPU runs with outputs disabled User program memory is read only Stop The CPU is not allowed to...

Page 6: ...yfails the CPU date andtime is reset to12 00AM 01 10 2000at startup The CPU operatesnormallywithafailed or missing RTC battery onlythe initial CPU Time of day TOD clockinformation willbe incorrect Figure 1 Real Time Clock Battery EthernetPort The embeddedEthernetinterface supportscommunicationswiththe Machine Editionprogrammingsoftware usingthe proprietarySRTP protocol The CPE302CPU providestwoSRT...

Page 7: ...32serial connectionstothe CPE302 RemovableDataStorageDevices RDSDs The CPE302providesthe abilitytotransfer applicationstoandfroman RDSD USBcompatible device suchasamemorystick smart phone digital cameraor MP3device Once the dataiscopiedtothe RDSD it canbe writtentootherRX3i CPE302CPUswithnoprogrammersoftware needed The RDSD interface requiresauser suppliedflashmemorydevicethat complieswiththe USB2...

Page 8: ...elow Light EmittingDiodeIndicators LEDs OK indicatesmodule readinesstoperformnormaloperations Green ON steady CPU passed power up diagnostics functioning properly OFF Power is not applied or CPU has a problem which may be indicated by RN and EN blink pattern Green blinking CPU in Stop Halt state possible watchdog timer fault Refer to the fault tables Ifthe programmer cannot connect cycle power wit...

Page 9: ...t scan is disabled CM indicatesactivityonthe serial communicationsport Green blinking Signal activity on the COM1 port OFF No activity on COM1 port IO FORCE indicatesoverrideonabit reference Amber ON steady Override active on at least one bit reference OFF No overrides applied STATUS indicatesEnergyPackstatus OFF EnergyPacknot connected Green blinking EnergyPackcharging not yet charged above the m...

Page 10: ... be replacedsoon Green ON steady EnergyPackis charabove itsminimum operatingvoltage SYS FLT indicatespresence ofafatalfault OFF Nofatalfaults Red ON CPU isinStop Faultedmode because a fatalfault has occurred RDSD indicatessignal activityonthe RDSD COM2 USBport Green blinking COM2port activity OFF NoCOM2port activity ...

Page 11: ...ouldneedtocontact Customer Care during the warrantyperiod Allshippingcontainersandallpackingmaterialshould be savedshould it be necessarytotransport or shipanypart ofthe system Verifythat allcomponentsofthe systemhave beenreceivedandthat they agree withyour order Ifthe systemreceiveddoesnot agreewithyour order contact Customer Care Installation Location Thisproduct isintendedfor use withthe RX3isy...

Page 12: ...t isan open type device andismeant tobe installed inan enclosure suitable for the environmentthat isonlyaccessible withthe use ofatool Suitable for use inClassI Division2 GroupsA B C andD HazardousLocations or nonhazardouslocationsonly Warning EXPLOSION HAZARD SUBSTITUTION OFCOMPONENTS MAYIMPAIRSUITABILITYFORCLASSI DIVISION2 Warning WHEN IN HAZARDOUS LOCATIONS TURN OFFPOWER BEFORE REPLACING ORWIRI...

Page 13: ...and CPU Reference Manual GFK 2222 1 Remove the pull tabfromthe RealTime Clock RTC battery locatedon the backof the CPE302 2 Remove power fromthe RX3i rackand installthe CPE302 The CPE302may be installedinany slot in the RX3iMainrack except the highest numberedslot or slot 0 3 Holdingthe module firmly align the module withthe correct slot and connector then swingthe module downuntilthe module s con...

Page 14: ...fromthe connectoronthe bottomofthe EnergyPackto d the correspondingconnectoronthe bottomof CPE302 6 If required connect theCPE302tothe Ethernet network 7 Applypower tothe rack Note Whenthe EnergyPackispoweredupfor the firsttime or is ina systemthat has beenpowereddownlongenoughto completelydischarge the EnergyPack it mayrequire afew secondsfor it tocharge toitsoperatinglevel The CPU s STATUSLED wi...

Page 15: ...rface youwillprobablyneed toassignit anew IP address Toconfigure the embeddedEthernet interfacein Machine Edition expandthe CPU slot todisplaythe Ethernet daughterboard The Settingstabfor the embeddedEthernet module containsIP Address Subnet Maskand GatewayIP Address see the followingdiagram Consult your networkadministratorfor thepropervalues for these parameters Figure 3 Configuration of the Eth...

Page 16: ...nine pin male D connector b Connect tothe module s Ethernet port usingthe factory loadedIP address 192 168 0 100 Note Thisaddressis intendedonly for initialconnectioninorder tocomplete the configuration After the initialconfiguration download must be changed before connectingtothe Ethernet network Whenyou store ahardware configuration withadifferent IP address the temporaryIP addressislost it is n...

Page 17: ...RX3i CPUProgrammer sReference Manual GFK 2950 PACSystemsRX3i System Manual GFK 2314 PACSystemsRX3i IC695CPE302 CPUImportantProduct Information GFK 2714 PACSystemsRX3i TCP IPEthernet Communications User Manual GFK 2224 User manuals product updatesandother informationsourcesare available onthe Support website https www emerson com en us support ...

Page 18: ...ustrial automation controls All Rights Reserved We reserve the right to modify or improve the designs or specifications of the products mentioned in this manual at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson product remains solely with the purchaser 2019 Eme...

Reviews: