 LCP100 Local Control Panel

Contents

Introduction

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Scope of Manual

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Description

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Specifications

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Educational Services

2

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Hazardous Area Classifications and Special

Instructions for “Safe Use” and Installation
in Hazardous Areas

5

. . . . . . . . . . . . . . . . . . . . . . . .

Mounting

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Connections

5

. . . . . . . . . . . . . . . . . . . . . . . .

Pre‐Setup Testing

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Setup

25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Principle of Operation

25

. . . . . . . . . . . . . . . . . . . . . . . .

Maintenance

26

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Troubleshooting

26

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Parts Ordering

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Parts List

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Common Parts

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 1. Fisher LCP100 Local Control Panel, with
FIELDVUE DVC6200 SIS Digital Valve Controller
and Bettis

 Actuator

X0247

Introduction

Scope of Manual

This instruction manual includes installation and maintenance information for the Fisher LCP100 local control panel
(figure 1). This device is used with Fisher FIELDVUE™ instruments in Safety Instrumented Systems (SIS). Refer to the
DVC6200 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions instruction manual
(

D103557X012

) or the DVC6000 SIS Digital Valve Controllers for Safety Instrumented System (SIS) Solutions

instruction manual (

D103230X012

) for additional information.

Unless otherwise noted, the information in this instruction manual applies to both DVC6200 SIS and DVC6000 SIS
digital valve controllers. For simplicity, the DVC6200 SIS model name will be used throughout.

Instruction Manual

D103272X012

LCP100 Local Control Panel

August 2017

Summary of Contents for Fisher LCP100

Page 1: ...Scope of Manual This instruction manual includes installation and maintenance information for the Fisher LCP100 local control panel figure 1 This device is used with Fisher FIELDVUE instruments in Safety Instrumented Systems SIS Refer to the DVC6200 SIS Digital Valve Controllers for Safety Instrumented System SIS Solutions instruction manual D103557X012 or the DVC6000 SIS Digital Valve Controllers...

Page 2: ...ns contact your Emerson sales office or Local Business Partner Description The LCP100 local control panel is used with the HARTr communicating DVC6200 SIS digital valve controller This panel is used to manually open and close a safety shutdown valve The LCP100 also provides a manual reset feature as well as a button for initiating a partial stroke test Specifications Typical specifications for the...

Page 3: ... 0 1 2 Ex e mb ib IIC T4 Gb Zone 1 2 Ex ic IIC T4 Gc Zone 2 Ex tb IIIC T71 C Db Zone 21 22 CUTR Ex em ib IIC Zone 1 2 Ex ic IIC Zone 2 Electrical Housing IP66 Electromagnetic Interference EMI Meets EN 61326 1 2013 Immunity Industrial locations per Table 2 of EN 61326 1 Standard Performance is shown in table 2 below Emissions Class A ISM equipment rating Group 1 Class A Connections Conduit 3 4 NPT ...

Page 4: ...0 to 2000 MHz 3V m with 1 kHz AM at 80 2000 to 2700 MHz 1V m with 1 kHz AM at 80 A I O signal control Burst fast transients IEC 61000 4 4 1 kV I O lines 2 kV DC power lines A Surge IEC 61000 4 5 1 kV I O lines 2 kV DC power lines A Conducted RF IEC 61000 4 6 150 kHz to 80 MHz at 3 Vrms with 1 kHz AM at 80 A Specification limit 1 of span 1 A No degradation during testing B Temporary degradation dur...

Page 5: ...oval certification information Mounting Refer to figure 2 for dimensional information The LCP100 local control panel has four 4 mounting holes for on site mounting of the device The LCP100 must be installed so that the wiring connections are on the bottom to prevent accumulation of moisture inside the box Electrical Connections WARNING Select wiring and or cable glands that are rated for the envir...

Page 6: ...C DVC6200 SIS then LCP100 Point to Point 15 Multi Drop 16 Ex ia IIB Ex tb IIIC LOOP DVC6200 SIS then LCP100 Point to Point 17 Multi Drop 18 LCP100 then DVC6200 SIS Point to Point 19 Multi Drop 20 Note For intrinsically safe applications the LCP100 forms an intrinsically safe explosion protection system when used with intrinsically safe associated apparatus a barrier or with any other intrinsically...

Page 7: ...ER SWITCH SELECTION REFER TO WIRING DIAGRAMS IN THE FOLLOWING FIGURES FOR CORRECT WIRING CONNECTIONS LABEL IDENTIFIES TERMINALS USED WHEN POWER SELECTOR SWITCH IS SET TO 24VDC NOTE THAT MIDDLE TERMINAL IS NOT USED WITH THIS SETTING TERMINAL CONNECTIONS USED WHEN 24VDC POWER SWITCH IS SELECTED LABEL IDENTIFIES POWER SELECTOR SWITCH SETTING LEFT 24VDC RIGHT LOOP ELECTRICAL ENTRY 3 4 NPT OR M20 LCP10...

Page 8: ...e mb ib IIC Ex tb IIIC LOOP DVC6200 SIS then LCP100 Point to Point 2 LOGIC SOLVER OUTPUT 8 20 mA USER SUPPLIED 1 NOTES 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 FOR FLAMEPROOF EXPLOSION PROOF APPROVED DIGITAL VALVE CONTROLLERS INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN THE FLAMEPROOF EXPLOSION PROO...

Page 9: ...oltage Ex e mb ib IIC Ex tb IIIC LOOP DVC6200 SIS then LCP100 Multi Drop LOGIC SOLVER OUTPUT 24VDC USER SUPPLIED NOTES 1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 FOR FLAMEPROOF EXPLOSION PROOF APPROVED DIGITAL VALVE CONTROLLERS INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN THE FLAMEPROOF EXPLOSION PROOF INTEGRITY OF THE DEVICE LC340 LINE CONDITIO...

Page 10: ...x e mb ib IIC Ex tb IIIC LOOP LCP100 then DVC6200 SIS Point to Point LOGIC SOLVER OUTPUT 8 20 mA USER SUPPLIED NOTES 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 FOR FLAMEPROOF EXPLOSION PROOF APPROVED DIGITAL VALVE CONTROLLERS INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN THE FLAMEPROOF EXPLOSION PROOF ...

Page 11: ... Voltage Ex e mb ib IIC Ex tb IIIC LOOP LCP100 then DVC6200 SIS Multi Drop LOGIC SOLVER OUTPUT 24VDC USER SUPPLIED NOTES 1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 FOR FLAMEPROOF EXPLOSION PROOF APPROVED DIGITAL VALVE CONTROLLERS INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN THE FLAMEPROOF EXPLOSION PROOF INTEGRITY OF THE DEVICE LC340 LINE CONDIT...

Page 12: ...C POWER IS AVAILABLE FOR THE LCP100 IT IS NOT NECESSARY TO CONNECT THE LOOP OF THE DIGITAL VALVE CONTROLLER TO THE LOOP OF THE LCP100 DOING SO WILL CAUSE THE LCP100 TO UNNECESSARILY CONSUME 4 mA AT THE EXPENSE OF THE DIGITAL VALVE CONTROLLER 2 FOR FLAMEPROOF EXPLOSION PROOF APPROVED DIGITAL VALVE CONTROLLERS INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN THE FLAMEPROOF EX...

Page 13: ...ABLE FOR THE LCP100 IT IS NOT NECESSARY TO CONNECT THE LOOP OF THE DIGITAL VALVE CONTROLLER TO THE LOOP OF THE LCP100 DOING SO WILL CAUSE THE LCP100 TO UNNECESSARILY CONSUME 4 mA AT THE EXPENSE OF THE DIGITAL VALVE CONTROLLER 2 FOR FLAMEPROOF EXPLOSION PROOF APPROVED DIGITAL VALVE CONTROLLERS INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN THE FLAMEPROOF EXPLOSION PROOF IN...

Page 14: ...oltage Ex ic IIC Ex tb IIIC LOOP DVC6200 SIS then LCP100 Point to Point LOGIC SOLVER OUTPUT 8 20 mA USER SUPPLIED INTRINSICALLY SAFE BARRIER NOTES 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LOOP TERMINALS Ui 27 VDC Ii N A Pi N A Ci 1 1...

Page 15: ...rent or Voltage Ex ic IIC Ex tb IIIC LOOP DVC6200 SIS then LCP100 Multi Drop LOGIC SOLVER OUTPUT 24 VDC USER SUPPLIED INTRINSICALLY SAFE BARRIER NOTES 1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LOOP TERMINALS Ui 27 VDC Ii N A Pi N A Ci 1 1 nF Li 0 mH LC340 LINE CONDITIONER FLD SY...

Page 16: ...ltage Ex ic IIC Ex tb IIIC LOOP LCP100 then DVC6200 SIS Point to Point NOTES 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS USER SUPPLIED INTRINSICALLY SAFE BARRIER LOOP TERMINALS Ui 27 VDC Ii N A Pi N A Ci 1 1 nF Li 0 mH LOGIC SOLVER OUTP...

Page 17: ...rent or Voltage Ex ic IIC Ex tb IIIC LOOP LCP100 then DVC6200 SIS Multi Drop INTRINSICALLY SAFE BARRIER NOTES 1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LOOP TERMINALS Ui 27 VDC Ii N A Pi N A Ci 1 1 nF Li 0 mH LOGIC SOLVER OUTPUT 24 VDC USER SUPPLIED LC340 LINE CONDITIONER FLD SY...

Page 18: ...BLE FOR THE LCP100 IT IS NOT NECESSARY TO CONNECT THE LOOP OF THE DIGITAL VALVE CONTROLLER TO THE LOOP OF THE LCP100 DOING SO WILL CAUSE THE LCP100 TO UNNECESSESARILY CONSUME 4 mA AT THE EXPENSE OF THE DIGITAL VALVE CONTROLLER 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LOOP TERMINALS Ui 27 VDC Ii N A Pi N A Ci 1 1 nF Li 0 mH INTRINSICALLY SAFE ...

Page 19: ...0 IT IS NOT NECESSARY TO CONNECT THE LOOP OF THE DIGITAL VALVE CONTROLLER TO THE LOOP OF THE LCP100 DOING SO WILL CAUSE THE LCP100 TO UNNECESSESARILY CONSUME 4 mA AT THE EXPENSE OF THE DIGITAL VALVE CONTROLLER 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LOOP TERMINALS Ui 27 VDC Ii N A Pi N A Ci 1 1 nF Li 0 mH 24 VDC TERMINALS Ui 27 VDC Ii N A Pi...

Page 20: ...C6200 SIS then LCP100 Point to Point INTRINSICALLY SAFE BARRIER NOTES 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LOOP TERMINALS Ui 30 VDC Ii 226 mA Pi 1 4 W Ci 0 22 mF Li 16 0 mH AUX TERMINALS Ui 30 VDC Ii 452 mA Pi 1 4 W Ci 0 mF Li 0 ...

Page 21: ...IC LOOP DVC6200 SIS then LCP100 Multi Drop GE26881 Sheet 16 INTRINSICALLY SAFE BARRIER NOTES 1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LOOP TERMINALS Ui 30 VDC Ii 226 mA Pi 1 4 W Ci 0 22 mF Li 16 0 mH AUX TERMINALS Ui 30 VDC Ii 452 mA Pi 1 4 W Ci 0 mF Li 0 mH USER SUPPLIED LOGIC...

Page 22: ...P100 then DVC6200 SIS Point to Point NOTES 1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS INTRINSICALLY SAFE BARRIER LOOP TERMINALS Ui 30 VDC Ii 226 mA Pi 1 4 W Ci 0 22 mF Li 16 0 mH AUX TERMINALS Ui 30 VDC Ii 452 mA Pi 1 4 W Ci 0 mF Li 0 ...

Page 23: ...IC LOOP LCP100 then DVC6200 SIS Multi Drop GE26881 Sheet 18 INTRINSICALLY SAFE BARRIER LOOP TERMINALS Ui 30 VDC Ii 226 mA Pi 1 4 W Ci 0 22 mF Li 16 0 mH AUX TERMINALS Ui 30 VDC Ii 452 mA Pi 1 4 W Ci 0 mF Li 0 mH USER SUPPLIED NOTES 1 THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA 2 REFER TO THE DVC6200 SERIES QUICK START GUIDE D103556X012 FOR SCHEMATICS AND ENTITY PARAMETERS LC340...

Page 24: ... the Logic Solver 1 Reduce the current to the DVC6200 SIS to 4 mA for de energize to trip operation Note For a loop powered installation a minimum current of 8 mA is required at the trip state Safety Demand for proper functioning of the pushbuttons and lights 2 Observe that the valve moves to its fail safe state 3 Observe that the red light comes on solid and the yellow light stays off 4 Press the...

Page 25: ...ype and Zero Power Condition select the instrument connected to local control panel LCP100 option D Follow the prompts to complete Device Setup The following parameters will be automatically set under Travel Alerts d Hi Hi Lo Lo Enable Yes d Lo Lo Point 1 d Hi Hi Point 99 d Deadband 0 5 d DVC Power Up Manual Reset D Continue to set up the digital valve controller according the normal set up proced...

Page 26: ...o a trip from the logic solver 2 Depending on the emergency shutdown valve configuration the top button could be labeled Valve Open and the middle button could be labeled Valve Close or vice versa The bottom button will aways be labeled Valve Test 3 Acknowledgment of a PST failure means that the LCP100 will return the blinking green light to solid green The PST alert will still be visible via HART...

Page 27: ...s settings not correctly set 6 Ensure that the Hi Hi Lo Lo Alert settings are 99 and 1 respectively For large rotary valve adjust settings to 98 and 2 and observe Parts Ordering When corresponding with your Emerson sales office or Local Business Partner about this equipment mention the serial number found on the nameplate of the unit WARNING Use only genuine Fisher replacement parts Components tha...

Page 28: ...terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2007 2017 Fisher Controls International LLC All rights reserved Fisher FIELDVUE and Bettis are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solut...