background image

www.Fisher.com

Fisher

 easy-Drive

 RPU-100

Contents

Introduction

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Scope of Manual

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Description

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Educational Services

2

. . . . . . . . . . . . . . . . . . . . . . . . .

Related Documents

2

. . . . . . . . . . . . . . . . . . . . . . . . . .

Product Operation

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Product Interfaces

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Enable / Disable Switch

3

. . . . . . . . . . . . . . . . . . . . . . .

LED Key

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

easy-Drive User Interface

5

. . . . . . . . . . . . . . . . . . . . . . .

Loss Detect

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Status Output

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Product Security

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Mounting

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Wiring

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Replacement

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Removal

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Parts Ordering

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix A - Modbus

16

. . . . . . . . . . . . . . . . . . . . . . . . .

Appendix B - Certificate of Conformance

20

. . . . . . . . .

Figure 1. Fisher easy-Drive RPU-100

X1718

Introduction

Scope of Manual

This instruction manual provides product information including installation for the Fisher easy-Drive
RPU-100. For Fisher easy-Drive actuators refer to the appropriate easy-Drive actuator instruction
manual. 

To avoid personal injury or property damage, it is important to carefully read, understand, and

follow all the contents of this manual, including all safety cautions and warnings.

 If you have any

questions about these instructions, contact your 

Emerson sales office

 before proceeding.

Description

The easy-Drive RPU-100 is a reserve power unit designed to provide backup power to the easy-Drive actuator upon
loss of incoming power. The RPU-100 provides enough power to the actuator to allow the actuator to drive the valve
to the pre-defined loss of power or loss of signal position. The RPU-100 can be ordered with a new easy-Drive assembly
or be retrofit into existing easy-Drive units that have the Gen2 control board.

Instruction Manual

D104551X012

easy-Drive RPU-100

May 2021

Summary of Contents for Fisher easy-Drive RPU-100

Page 1: ...ive actuators refer to the appropriate easy Drive actuator instruction manual To avoid personal injury or property damage it is important to carefully read understand and follow all the contents of this manual including all safety cautions and warnings If you have any questions about these instructions contact your Emerson sales office before proceeding Description The easy Drive RPU 100 is a rese...

Page 2: ... Ex db IIA T6 Gb Approximate Weight 0 5 kg 1 lb Educational Services For information on available courses for the easy Drive RPU 100 as well as a variety of other products contact Emerson Automation Solutions Educational Services Registration Phone 1 641 754 3771 or 1 800 338 8158 E mail education emerson com emerson com fishervalvetraining Related Documents This section lists other documents cont...

Page 3: ... to the actuator for 120 seconds to ensure enough time to complete move and then power down The easy Drive RPU 100 will determine when it is sufficiently charged Charge time will depend on the application and or power used to perform a back up A minimum charge time is enforced Product Interfaces Enable Disable Switch The switch enables or disables the functionality of the RPU When the switch is in...

Page 4: ...y 2021 4 LED Key Figure 3 States of the Fisher easy Drive RPU 100 Power Green Status Blue Attention Yellow Fault Red Normal Operation Charging Providing Power Disabled Recoverable Fault Non Recoverable Fault INDICATES FLASHING LIGHT INDICATES SOLID LIGHT ...

Page 5: ... will wait to verify loss of power before performing a backup operation This time is configurable between 0 05 and 3 00 seconds The default is 0 250 seconds Status Output The status output is a discrete output that indicates the overall status of the RPU 100 If the output is on connection made this indicates the RPU 100 is operational If the output is off additional information can be found in the...

Page 6: ... properly bolted before applying power to the actuator Personal injury or property damage may result from fire or explosion if power is applied to the actuator with the cover removed in a hazardous area D For explosion proof applications install rigid metal conduit and a conduit seal no more than 457 mm 18 in from the actuator Personal injury or property damage may result from explosion if the sea...

Page 7: ...g the motor gearbox bolts and the provided mounting bracket Figure 5 Fisher easy Drive RPU 100 Mounting GE95898_A MOUNTING SCREWS MOUNTING BRACKET WIRING HARNESS 1 Loosen all four motor housing bolts removing the three bolts as shown below 2 Position the bracket on the motor gearbox X1723 Figure 6 ...

Page 8: ...racket in place Note the washers will not be used with the bolts with the mounting bracket X1720 Figure 7 4 Tighten all 4 motor bolts to 15 ft lbs 20 N m using a criss cross pattern while tightening the bolts 5 The RPU 100 will sit down on the mounting bracket then slide toward the motor to lock into place X1725 LOCKS IN PLACE Figure 8 ...

Page 9: ...0 to the easy Drive control board Tighten all terminals to ensure solid mechanical connection Ensure the red wire is connected to the 12 24 VDC Power 8 After wiring connections have been completed install easy Drive actuator upper enclosure per the applicable actuator instruction manual 9 Use the easy Drive configurator to configure the RPU 100 after installation X1722 RED WIRE TO 12 24 VDC POWER ...

Page 10: ...ed Wiring Instructions 1 Ensure power is turned off before connecting the wires 2 Observe local wiring requirements for hazardous location usage 3 Conduit seals within 450 mm 18 inches of the enclosure port are required 4 18 AWG 0 52mm2 to 12 AWG 3 31mm2 wire size required 5 Fuse system to 5A 6 Connect enclosure and analog signal shields 7 Be sure to tighten terminals sufficiently to ensure solid ...

Page 11: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 11 Power 1 Connect 12 or 24 VDC reference to 2 Connect 12 or 24 VDC positive to Figure 12 Wiring RPU 100 Input ...

Page 12: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 12 Figure 13 Wiring Analog Input Figure 14 Wiring Dual Dry Contact ...

Page 13: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 13 Figure 15 Wiring Modbus Input MODBUS A T MODBUS B T Figure 16 Wiring Auxiliary Digital I O ...

Page 14: ...ion Manual D104551X012 easy Drive RPU 100 May 2021 14 Figure 17 Wiring Auxiliary Digital I O 10 V 25 mA max Figure 18 Wiring RPU 100 Status Switch DISCRETE DEVICE SELF POWERED DISCRETE DEVICE EXTERNALLY POWERED ...

Page 15: ... disable position 3 Disconnect power from the RPU 100 4 Disconnect wiring harness from the RPU 100 5 Remove the two mounting screws securing the RPU 100 to the actuator 6 Slide RPU 100 to remove from mounting bracket Installation Refer to Mounting section steps 5 through 9 for installation of new RPU 100 reserve power unit The existing wiring harness can be used to connect to the new RPU 100 Parts...

Page 16: ...5 0 R 0 4 294 967 295 Total number of times since reset the RPU has dropped below the power loss threshold and recovered uint32 Number of Backup Operations 44016 44017 0 R 0 4 294 967 295 Total number of backup operations the RPU has performed since reset uint16 Line Voltage 44018 0 R 0 3500 Value of incoming voltage with 2 implied decimal 0 00 35 00 V uint16 RESERVED 44019 uint16 RESERVED 44020 u...

Page 17: ...59 uint16 RESERVED 44060 uint16 RESERVED 44061 uint16 RESERVED 44062 uint16 RESERVED 44063 uint16 RESERVED 44064 uint16 RESERVED 44065 uint16 RESERVED 44066 uint16 RESERVED 44067 uint16 RESERVED 44068 uint16 RESERVED 44069 uint16 RESERVED 44070 uint16 Modbus address 44071 1 R W 1 247 Slave address of the actuator uint16 Baud Rate 44072 5 R W 4 7 4 4800 baud 5 9600 baud 6 19200 baud 7 38400 baud ui...

Page 18: ...0 R W 0 4 294 967 295 Seconds since January 1 2000 Board Supplier Functional Test Date uint32 System completion date 44125 44126 0 R W 0 4 294 967 295 Seconds since January 1 2000 Final Assembly Test Date uint16 RESERVED 44127 uint16 RESERVED 44128 uint16 RESERVED 44129 uint16 RESERVED 44130 uint16 RESERVED 44131 uint16 RESERVED 44132 uint16 RESERVED 44133 uint16 RESERVED 44134 uint16 RESERVED 441...

Page 19: ... 0000 1000 0000 Operating Normal 128 7 The RPU 100 is operating normally and monitoring for power loss events 0x0040 0000 0000 0100 0000 Charging 64 6 The RPU 100 is charging 0x0020 0000 0000 0010 0000 Providing Backup Power 32 5 Backup power is being provided to the actuator 0x0010 0000 0000 0001 0000 Reduced Capacitance 16 4 Reduced capacitance has been detected Contact your Emerson sales office...

Page 20: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 20 Appendix B Certificate of Conformance continued ...

Page 21: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 21 Appendix B Certificate of Conformance cont ...

Page 22: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 22 ...

Page 23: ...Instruction Manual D104551X012 easy Drive RPU 100 May 2021 23 ...

Page 24: ...are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice E 2021 Fisher Controls International LLC All rights reserved Fisher and easy Drive are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co Emerson Automation Solutions Emerson and the Emerson logo are...

Reviews: