1592002810 XH360L-V GB  r1.0 10.09.2015 

                           XH360L – XH360LV 

1/5 

XH360L-V 

TEMPERATURE AND HUMIDITY CONTROLLER 

FOR SEASONING-MATURING CABINETS 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot 
be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 

ensuring the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not  expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

The 

XH360L,

 

38x185 

format and the 

XH360V,

 

100x64 

format, are microprocessor controllers, suitable 

for applications on medium or low temperature refrigerating units. They have 6 output relays to control 
compressor, heating elements, defrost/extractor fan, fan, de-humidifier/light and humidifier. They have 2 
NTC inputs one for thermostat the other one for defrost. It’s also present a 4÷20mA input for humidity. 
There  is  one  digital  input  (free  contact)  configurable  by  parameter.  An    output  allows  the  user  to 
programme the parameter list with the 

“Hot Key”.

 

3.

 

TEMPERATURE REGULATION 

The temperature regulation is performed through neutral zone using compressor and heater output 
relays. 

Set point

OFF

ON

 

• 

Heating

 output: CUT IN is “SET_T-dbt”, CUT OUT is when the temperature reaches the set point. 

• 

Compressor

 output CUT IN is “ SET_T +dbt”, CUT OUT is when the temperature reaches the set 

point. 

3.1

 

DEFROST  

During defrost the temperature control is disabled. 
 

If  the  second  relay  is  configured  as  defrost:  oA2=dEF

 

(XH360L  terminals  9-10-11,  XH360V 

terminals 6-7) 

then two defrost modes are available through the “

tdF

” parameter: defrost with electrical 

heater  (tdF=rE)  or  hot  gas  (tdF=  in).  The  defrost  interval  is  control  by  means  of  parameter  “

EdF

”: 

(EdF=in) the defrost is made every “

IdF

” time, (EdF=Sd) the interval “IdF” is calculate through Smart 

Defrost algorithm (only when the compressor is ON). At the end of defrost dripping time is started, set 
by “

Fdt

” parameter.  

To 

disable 

the defrost set the 

MdF

 parameter to 

zero

 

 

If  oA2 is different from dEF, defrost is made only by stopping compressor  (tdF=rE). 
To disable 

 defrosts set 

MdF=0. 

 
Humidity regulation during defrost depends on the 

Hud 

parameter. 

With  

Hud=no

 humidity regulation is disabled.  

Con 

Hud=yES

 humidity regulation is performed also during defrost. 

 

4.

 

HUMIDITY REGULATION 

The humidity regulation is performed through neutral zone, by humidifying dehumidifying actions. 
Humidity control can be disabled setting the 

SET_RH to “nu”

 value. In this case only the temperature 

control is perform. 

4.1

 

HUMIDIFYING ACTION 

The  humidifying  action  is  done  enabling  the  humidifier  relay  when  the  humidity  is  lower  than  the 
“SET_RH-dbH” value. 
The relay is switch off when humidity reaches the set values. 
 

4.2

 

DEHUMIDIFYING ACTION WITHOUT DEHUMIDIFIER RELAY, OA1 DIFFERENT FROM DEH 

(XH360L TERMINALS 3-4, XH360V TERMINALS. 11-12) 

In this case the dehumidifying action is performed by setting the following parameters in this way: 

tHu = c-H kind of dehumidifying by means of heating and compressor relays 

oA1 different from dEH (XH360L terminals 3-4, XH360V terminals. 11-12):  

The heating and compressor outputs are activated together when humidity is higher than dbH 
value. Outputs are disabled when humidity comes back to the SET_RH value. 

 

4.2.1  Relation between cooling, heating and dehumidifying 

1.

 

If is simultaneously present a request of cooling (temp>SET_T+dbt) and dehumidifying (RH > 
dbH):  the  cooling  action  has  the  priority  over  the  dehumidifying  action:  only  the 
compressor relay is energised till the SET_T is reached at this point also the heating relay is 
enabled. 

  
2.

 

If is simultaneously present a request of heating (temp< SET_T-dbt) and dehumidifying (RH > 
dbH):  the  dehumidifying  action  has  the  priority  over  the  heating  action:  both  the 
compressor and the heating relays are energised till the humidity set is reached at this point only 
the heating relay is enabled. 

 

4.3

 

DEHUMIDIFYING ACTION WITH DEHUMIDIFIER RELAY, OA1 = DEH – (XH360L 

TERMINALS 3-4, XH360V TERMINALS. 11-12) 

The configurable relay is used, 

(

XH360L terminals 3-4, XH360V terminals. 11-12

setting the parameter 

oA1 =dEH.

 

NOTE: 

the LIGHT button is not more available; 

Two kinds of de-humidifying are available: 

4.3.1  Dehumidifying action with ONLY de-humidifier relay 

By setting the parameter 

tHu 

db

 the de-humidifying action is performed by enabling the de-humidifier 

relay when the humidity is higher than SET_RH

 

+  dbH. 

The relay is switch off when humidity comes back to the SET_RH value. 

 

4.3.2  Dehumidifying action with de-humidifier and compressor relays 

By  setting  the  parameter 

tHu 

cHu

  the  de-humidifying  action  is  performed  by  enabling  the  de-

humidifier and compressor relays together. when the humidity is higher than SET_RH

 

+  dbH. 

The relays are switched off when humidity comes back to the SET_RH value. 
 
If  is  simultaneously  present  a  request  of  cooling  (temp>SET_T+dbt)  and  dehumidifying  (RH  > 
dbH): the cooling action has the priority over the dehumidifying action: only the compressor 
relay is energised till the SET_T is reached at this point also the de-humidifier is enabled. 

5.

 

 FA NS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC=C-n

   fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

FnC= O-n

 fans will run continuously, but not during defrost  

FnC=C-y

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC=O-y

   fans will run continuously also during defrost 

6.

 

EXTRACTOR FAN 

6.1

 

EXTRACTOR FAN CYCLES 

The second relay (XH360L terminals 9-10-11, XH360V terminals 6-7) is configured as extractor 

fan, oA2= ESt, then it is possible to make extraction cycles, both manually and automatically. 

 

 
Extraction cycle can be activated both manually by pushing the UP key for 3s, and automatically by the 
internal time 

rFi. 

Cycle duration is set by the 

rFd 

parameter. The cycle can be stopped also by key.  

 
If  

rFI

 = 0 only manual cycle can be activated. 

 
If  

rFd

 = 0 the cycle is stopped only by pushing the key. 

7.

 

MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE. 

 

Dripping

Running

Stopping

Running

Stopping

 
The diagrams displays a typical maturing cycle with the starting dripping phase. 

DRIPPING PHASE

 lasts for the “

dri

” time, without  humidity control, temperature set is SETG 

RUNNING PHASE

 lasts for the 

“on”

 time, both temperature and humidity are controlled.  

STOPPING PHASE

 lasts for the 

“off”

 time, without any control of temperature and humidity.  

The end of the stopping phase is signalled by the internal buzzer and by the  “End” message on the 
display. 

After 

the 

STOPPING PHASE

 the behaviour of the controller depends on the parameter 

trc, 

 according 

to the following settings: 

trc

 = 

co 

controller maintains the set points of the running phase 

trc

 = 

in 

controller stop the regulation at all. 

trc

 = 

cL 

controller performs the running and stopping phase till is stopped manually. 

trc

 = 

cLE 

 as (

trc

 = 

cL

) plus at the end of each cycle the 

End

 label is displayed and the buzzer 

is switched on. 

Summary of Contents for Dixell XH360L-V

Page 1: ...INALS 3 4 XH360V TERMINALS 11 12 In this case the dehumidifying action is performed by setting the following parameters in this way tHu c H kind of dehumidifying by means of heating and compressor relays oA1 different from dEH XH360L terminals 3 4 XH360V terminals 11 12 The heating and compressor outputs are activated together when humidity is higher than SET_RH dbH value Outputs are disabled when...

Page 2: ...the setting of the running cycle temperature SET_T humidity SET_RH or remaining time CLOCK 1 Push twice the corespondent key the setting value of the current phase dripping or running will be displayed 2 Modify it using the UP and DOWN keys 3 Confirm the value using the corespondent key temperature SET_T humidity SET_RH or remaining time CLOCK NOTE the changes made will be memorised So the next cy...

Page 3: ... the compressor is running even non consecutively SdF Set point for SMARTFROST 30 30 C 22 86 F evaporator temperature which allows the IdF counting interval between defrosts in SMARTFROST mode dtE Defrost termination temperature 50 0 110 0 C 58 230 F Enabled only when the evaporator probe is present sets the temperature measured by the evaporator probe which causes the end of defrost IdF Interval ...

Page 4: ...n a 150x31 mm hole and fixed using two screws 3 x 2mm To obtain an IP65 protection grade use the front panel rubber gasket mod RG L Instrument XH360V shall be mounted on vertical panel in a 72x56 mm hole and fixed using screws 3 x 2mm To obtain an IP65 protection grade use the front panel rubber gasket mod RG V The temperature range allowed for correct operation is 0 60 C Avoid places subject to s...

Page 5: ...t holding in stop regulation cL restart the first phase End message cLE restart the first phase tdF rE Pr2 Defrost type rE rT in EdF in Pr2 Defrost mode In Sd SdF 0 0 Pr2 Set point for SMART DEFROST 30 30 C 22 86 F dtE 8 0 Pr2 Defrost termination temperature 50 0 110 C 58 230 F Label Value Menu Description Range idF 6 Pr1 Interval between defrosts 1 120 h MdF 20 Pr1 Duration of defrost 0 250 min d...