330100 INSTRUCTION SHEET

Installation & Maintenance Instructions for ECP/NCP Model “E” 
U-Line® Plugs

RETAIN THIS INSTRUCTION SHEET FOR FUTURE REFERENCE. For safe installation and operation, please read these instructions 
carefully and with full understanding.

Compliance & Ratings

UL 1203

Class I, Group B, C; Class II, Group F, G; Class III

Electrical Ratings

Maximum Voltage:

 125 V or 250 V;  

Current:

 15 A or 20 A; 

Configuration:

 2W, 3P

Applications

• Locations where receptacles are used with stationary or portable electrically operated devices such as lighting systems, conveyors,

heaters, motor-generator sets, air conditioners compressors, and pumps.

• Locations where damp or corrosive conditions are encountered.

• Class I classified areas such as petrochemical plants, petroleum refineries, paint and chemical plants or any location where

ignitable vapors or gases are present.

• Class II locations such as process industries where there are dust hazards from handling such products as flour, grain, and starch

or any location where ignitable amounts of dust are present or amounts which  would otherwise affect performances.

Installation

WARNINGS

• Electrical power must be turned OFF before and during installation and maintenance. Failure to do so may result in serious or fatal

injuries due to electrocution.

• Use cable diameters ranging from 0.538 to 0.639 inches. Failure to do so may result in overstressed wire terminations, which may

cause the conductors to pull out of the contacts and cause serious/fatal injuries due to electrocution.

• Care must be taken not to cut into the individual conductor insulation when removing the outer cable jacket and to not damage the

conductors when removing individual wire insulation. Failure to do so will seriously degrade the electrical properties of the cable
and may produce overheating/electrical hazard leading to electrocution.

CAUTION

Before starting the installation, ensure the plug assembly is suitable for the intended location according to the National Electrical Code 
or Canadian Electrical Code. If the plug assembly is not suitable, serious damage and injuries may result. Owners are responsible for 
damages or injuries if these rules are not followed.

NOTICE

The plug should be wired with three-conductor, rubber-covered  #12 AWG – #14 AWG Type SO or SOOW Cords with copper 
conductors only.

FIGURE 1

Summary of Contents for Appleton U-Line ECP-1523

Page 1: ...unts of dust are present or amounts which would otherwise affect performances Installation WARNINGS Electrical power must be turned OFF before and during installation and maintenance Failure to do so may result in serious or fatal injuries due to electrocution Use cable diameters ranging from 0 538 to 0 639 inches Failure to do so may result in overstressed wire terminations which may cause the co...

Page 2: ...g strap terminal with grounding strap WHITE wire to lug terminal with WHITE DOT Other two wires to remaining lug terminals BLACK wire to remaining lug terminal Tighten the terminal screws to a torque of 15 in lb 7 Slide insulator clamp down the cord and position over terminals The insulator clamp has two slots which engage with the arc barrier walls providing proper orientation Continue to slide t...

Page 3: ...E If any part of the plug appears to be missing broken or show signs of damage discontinue use immediately This condition could cause serious or fatal personal injury due to electrocution and or equipment damage Repair with the proper Appleton replacement part s before continuing service During the inspections perform the following steps 1 Inspect all contact wire terminals for tightness and retor...

Page 4: ...numbers ECP 20232 and NCP 20232 are for use with the following receptacles Cat No followed by M indicates malleable iron receptacle in non hazardous areas EFS150 20232 EFSC150 20232 EFSB150 2023 EFSCB150 20232 EFS250 20232 EFSC250 20232 EFS175 20232 EFSC175 20232 EFSB175 20232 EFSCB175 20232 EFS275 20232 EFSC275 20232 EFS110 20232 EFSC110 20232 ECCL 20232 ECH20232 EFS210 20232 EFSC210 2023 EFSR 20...

Page 5: ...523 NCP 2023 NCP 1523 125 V 20 A 1hp 125 V 20 A 1hp EFSC250 2023 UGR10 2023 ENRC 12201 2 1 2 2 125 V 20 A 1hp 125 V 15 A 1hp ECP 2023 ECP 1523 NCP 2023 NCP 1523 125 V 20 A 1hp 125 V 20 A 1hp EFSC275 2023 UGR11 2023 ENRC 22201 2 3 4 2 125 V 20 A 1hp 125 V 15 A 1hp ECP 2023 ECP 1523 NCP 2023 NCP 1523 125 V 20 A 1hp 125 V 20 A 1hp EFSC210 2023 UGR12 20231 ENRC 32201 2 1 2 125 V 20 A 1hp ECP 2023 NCP ...

Page 6: ...ng service WARNING ELECTRICAL Electrical power must be turned OFF before and during installation and maintenance Failure to do so may result in serious or fatal injuries due to electrocution WARNING WIRING Plug and cord connectors are rated for use with Type SO cord with copper conductors ONLY Except as expressly provided by Appleton Grp LLC Appleton Appleton products are intended for ultimate pur...

Reviews: