Operating instructions 

Temperature Controls Series TS1 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 04.12.2019 

TS1_OI_EN_DE_FR_ES_RU_R09_0715182.docx 

G e n e r a l   i nf o r ma t i o n : 

For application in refrigeration systems and heat 

pumps. 

  S a f e ty   i n s tr u c t i o n s : 

 

Read operating instructions thoroughly. Failure 

to comply can result in device failure, system 

damage or personal injury. 

 

According to EN 13313 it is intended for use by 

persons having the appropriate knowledge and 

skill. 

 

Before opening any system make sure pressure in 

system is brought to and remains at atmospheric 

pressure. 

 

Do not exceed the specified maximum ratings for 

pressure, temperature, voltage and current. 

 

Do not exceed max. bulb temperature. 

 

Before installation or service disconnect all 

voltages from system and device. 

 

Ensure that design, installation and operation are 

according to European and national 

standards/regulations.

 

F u n c t i o n/ T y p e   o f   s w i t c h   (F i g . 1 ) : 

Fig.1a: Automatic reset function 

Fig.1b: Manual reset function for low temp. reset 

Fig.1c: Manual reset function for high temp. reset 

Fig.1d: Bellows heater 82k

, 230V AC/DC on 

devices with temperature sensor type A, E 

Fig.1e: Off-switch, function types B, F, H 

 

TS1 temperature switches are equipped with a SPDT 

snap action contact switching from 1-2 to 1-4 on 

rising and from 1-4 to 1-2 on falling temperature. 

Reaching the preset switch point on rising 

temperature, contact 1-2 breaks while contact 1-4 

makes and vice versa on falling temperature. 

TS1 with manual reset: 

 

Reaching the preset switching point contact 1-4 

breaks (low temp. switch) or contact 1-2 makes 

(high temp. switch) and locks in this position. After 

the temperature has risen or dropped by a fixed 

differential,

 

the switch can be reset by pushing the 

reset button. 

 

TS1 with manual reset are “trip-free”. 

M o u n t i n g   l o c a t i o n / di r e c t i o n :  

Any direction except upside down. 

I n s t a l l a t i o n   a l l   mo d e l s ,   e xc e p t   T S1 -

G / H   ( F i g . 2 a ) : 

 

TS1 controls may be installed by using a mounting 

plate or as a wall-mounted device against a flat 

surface. 

 

For wall-mounted devices, the insulating console 

supplied with controls with sensor type “E” must 

be installed between wall and control to ensure 

proper operation. 

 

For devices with vapor charges “A” and “P” an 

insulating console or other insulating material 

must be used if the wall temperature is close to 

the application temperature to be sensed. 

 

Use universal thread M4 or UNC8-32 mounting 

holes for installation via mounting plate. 

 

Use the standard mounting holes at the backside for 

wall mounting. 

 

Use mounting screws supplied with control. 

 

Mounting screws must not penetrate control 

backside by more than 8 mm to ensure proper 

operation. 

 

In order to achieve protection class IP44, the 

following instructions must be observed: 

-

 

Cover must be closed, and cover screw fastened. 

-

 

Control must be mounted against a flat surface so 

that all openings on the housing backside are 

fully covered. 

I n s t a l l a t i o n   mo d e l s  T S1 - G/ H   ( F i g . 2 b ) : 

 

Prepare cut out section for 85 x 39 mm 

 

Prepare holes for M4 screws 

 

Insert control into slot and tighten screws  

I n s t a l l a t i o n   T e mp e r a t u r e   s e n s o r  

( F i g . 3 ) : 

 

Avoid sharp bends or kinks in capillaries. 

 

Do not allow capillary to rub and abrade against any 

moving surface. Avoid work hardening effects. 

 

A capillary loop of ca. 8 cm diameter should be 

provided in capillary type sensors (A, C, P) below 

the control. 

 

Vapor charges (Sensor types A, E, P): 

 

These sensing elements always sense from the 

coldest point on the capillary, coil, bulb or power 

element head. 

 

Ensure that the control body and the portion of the 

capillary which is not at the sensing location is 

warmer than the sensing location by at least 2 K. 

 

Surfaces mounted controls should use an insulating 

console in order to ensure that control is not affected 

by the temperature of the mounting surface. 

 

At least 30 cm of sensor type “P” should be located 

at the sensing point for proper control. 

Adsorption charge (Sensor type “F”): 

 

This sensing element always responds to the bulb 

temp.  

 

The entire bulb must be in contact with the sensed 

temp. 

 

This charge is slower in response than a vapor 

charge. 

E l e c t r i c a l   c o n ne c t i o n   ( F i g . 4 ) :  

 

Note: Comply with local electrical regulations 

when conducting electrical wiring. Wire size 

must match the electrical load connected to the 

switch contacts. 

 

Feed cables through rubber grommet at switch 

bottom. 

 

Optionally, replace rubber grommet by a standard 

PG 13.5 cable gland. 

 

Connect wires to terminals 1, 2 and 4 by taking into 

account switch functions as shown in Fig. 1a to 1e. 

 

Fasten terminal screws with torque 1.2 Nm. 

 

For electronic applications with low electrical loads 

(voltage  <24 V and  current <50 mA) gold plated 

contacts are recommended. 

S e t p o i n t  a d j u s t me n t   ( F i g . 4 ,   F i g . 5 ) : 

 

TS1 pressure switches come with individually 

adjustable range and differential depending on the 

exact model. 

 

Manual reset switches always has  a fixed 

differential. 

 

Use the adjustment knob, a flat screw driver or a ¼” 

refrigeration (square) wrench to adjust setpoints as 

described below. 

 

Adjust upper setpoint using the range spindle. 

 

Adjust lower setpoint by turning the differential 

spindle: 

 

Upper setpoint – Differential = Lower setpoint 

 

A separate thermometer must be used for exact 

adjustment of the setpoints. The integrated display 

scale can only be used for obtaining approximate 

settings. 

 

Refer to the General Product Guide  for standard 

factory settings. 

 

Minimum differential setting at the end of range do 

differ slightly from the nominal differentials. 

M a n u a l   r e s e t   (F i g . 6 )  

 

Manual reset: press the reset button. 

Note  that the reset is ‘trip-free’, i.e. reset is only 

possible if the temperature has reached its reset 

treshold. 

Off-switch (Fig.1e) 

 

TS1-B/F/H have an off-switch which cuts off the 

line to terminal 1 when in Position “STOP”.

 

C h e c k- o u t   l e v e r   ( F i g . 4 ) 

 

Use the check-out lever to manually override the 

electrical contact position for testing out the system. 

T e c h ni c a l   D a ta :  

Electrical rating  

Heating load (AC1): 

Inductive load (AC15): 

Inductive load (DC13):  

 

Start-up (AC3):  

Motor rating (FLA):  

Locked rotor (LRA): 

 

24A / 230V AC 

10A / 230V AC 

0.1A / 230V DC 

3A / 24V DC 

144A / 230V AC 

24A / 120/240V AC 

144A / 120/240V AC 

Vibration resistance  

4g (10...1000 Hz) 

Protection class 

(IEC 529/EN 60529) 

IP44  

IP30 with Off-Switch 

Ambient temperature 

(housing) 

-50… +70°C 

Storage / transportation 

temperature 

-50…. +70°C 

Temperature sensing range 

-55… +180°C 

Max. bulb temperature 

see product label

 

Dimensions - width x height x depth (mm) 

TS1-A/B/C/D/E/F/R/X/Y 

86 x 75 x 44 

 

TS1-G/H (flush mounting) see Fig. 2b 

cut-out 

front cover 

85 x 39 x73 

106 x 44 

Note: all dimensions without reset button, adjustment 

spindles, off-switch and temperature sensors 

Standards / Markings 

 

 LVD 2014/35/EU  

EN 60947-1; EN 60947-5-1; EN 60730-2-9 

UL/CSA: for TS1-A/B/C/D/R/X/Y 

 

T y pe   c o d e : 

TS1 - 

 

 

 

e.g. TS1-A 4 F

 

  Function / Housing variant 

A = Wall mounting, top adjustment 

B = Wall mounting, top adjustment, off-switch 

C = Frost monitor, auto reset, top adjustment 

D = Frost monitor, manual reset, top adjustment 

E = Wall mounting, front adjustment 

F = Wall mounting, front adjustment, off-switch 

G = flush mounting 

H = flush mounting, plus off-switch 

R = Wall mounting, top adjustment, manual reset 

X = Same as A except for external adjustments 

Y = Same as D except for external adjustments 

Note: Function types D, R   with Temperature Ranges 

0…4 have a manual reset for falling temperature, with 

Ranges 5 – 9 for rising temp. 

  Temperature range

 

ranges 0 … 9 refer to product label or catalogue data 

 

Temperature sensor type 

A = Vapor charge, 2 m, capillary 

E = Vapor charge, 0 m, coil 

F = Adsorption charge, 2 m, bulb 

P = Vapor charge, 2 m capillary  

      (frost monitors Function C/D: 6 m) 

 

 

 

Summary of Contents for Alco Controls TS1 Series

Page 1: ... at least 2 K Surfaces mounted controls should use an insulating console in order to ensure that control is not affected by the temperature of the mounting surface At least 30 cm of sensor type P should be located at the sensing point for proper control Adsorption charge Sensor type F This sensing element always responds to the bulb temp The entire bulb must be in contact with the sensed temp This...

Page 2: ...tur das Fühlersystem beeinträchtigt Bei Fühlertyp P mindestens 30 cm als Kontaktfläche an der Messstelle vorsehen Adsorptionsfüllung Fühlertyp F Dieser Fühler reagiert immer auf die Patronentemperatur Die Patrone muss ganzflächig der zu messenden Temperatur ausgesetzt sein Adsorptionsfüllungen reagieren langsamer als Dampffüllungen E l e ktr i sc he r Ansc hl uss F ig 4 Wichtig Für den gesamten el...

Page 3: ...e la surface de paroi Sur les modèles avec train type P au moins 30 cm de capillaire doivent être placés dans l enceinte à contrôler pour un fonctionnement correct Charge à adsorption train type F Le train thermostatique réponds toujours à la température du bulbe Le bulbe entier doit être en contact avec l élément dont la température est à contrôler Le temps de réponse de ce type de charge est plu...

Page 4: ...ción del capilar que no esté en el lugar sensitivo tengan una temperatura al menos 2K más alta que la que se desea medir Debe usarse un aislante de cónsola para evitar que la caja del control se vea afectada por la temperatura de la superficie donde se apoye Situar al menos 30 cm del sensor de tipo P en el lugar de localización de la temperatura Carga de adsorción Sensor tipo F Siempre responde a ...

Page 5: ...ые на ней реле необходимо использовать изолирующие кронштейны Для правильной работы датчик типа P должен находиться не менее чем на 30см в месте измерения Абсорбционная заправка Датчик типа F Данные чувствительные элементы всегда реагируют на температуру термобаллона Термобаллон должен полностью находиться в контакте с измеряемой поверхностью Данная заправка срабатывает медленнее чем заправка паро...

Page 6: ...rung Passe fils prensa de goma Вход Эл кабеля Ground screw Schutzleiteranschluss Vis de masse Conductor de tierra Заземление Fig Рис 5a Fig Рис 5b 1 2 3 4 5 6 upper Setpoint Oberer Schaltpunkt Point de consigne haut Valor más alto Верхняя уставка lower Setpoint Unterer Schaltpunkt Point de consigne bas Valor más bajo Нижняя уставка Differential ϑ constant Differenz konstant Différentiel constant d...

Reviews: