background image

 

 

Operating Instructions 

Pressure Controls PS4 Versions  

released for R290 / R1270 

 

 

 

Emerson Climate Technologies GmbH 

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany

 

Date: 19.07.2019 

PS4-ATEX_OI_R06_ML_865178.docx

 

General information: 

The Pressure Controls 

PS4-…ATEX

  are intended to 

monitor the pressure and to act as a safety device.  

 

The listed products are electrical operated switches 
with  ignition source and are in compliance with 
EN 60079 /  directive  2014/34/EU  therefore  rated / 
marked as: 

 II 3G ExnA IIA T2Gc U

 

 
PS4-…ATEX  must be installed in an appropriate 
housing to protect them from mechanical damage or 
shock. 
 

 Safety instructions: 

 

Read operating instructions thoroughly. Failure 
to comply can result in device failure, system 
damage or personal injury. 

 

According to EN 13313 it is intended for use by 
persons having the appropriate knowledge and 
skill. 

 

Flammable refrigerants require special handling 
and care due to its flammability. Sufficient 
ventilation is required during service of the 
system. Contact with rapidly expanding gases can 
cause frostbite and eye damage. Proper 
protective equipment (gloves, eye protection, etc.) 
has to be used. 

 

In a severely contaminated system, avoid 
breathing acid vapors and avoid contact with 
skin from contaminated refrigerant / lubricants. 
Failure to do so could result in injury. 

 

Ensure that the system is correctly labeled with 
applied refrigerant type and a warning for 
explosion risk. 

 

Make sure that the high pressure switch is 
installed on high pressure side and low pressure 
switch on low pressure side of system. Failure to 
do will result in system without protection 
against high and low pressure and consequently 
risk of explosion and human injury. 

 

Do not release any refrigerant into the 
atmosphere! 

 

Do not exceed the specified maximum ratings for 
pressure, temperature, voltage and current. 

 

Before opening any system make sure pressure in 
system is brought to and remains at atmospheric 
pressure. 

 

Ensure that the system piping is grounded. 

 

Before installation or service disconnect voltage 
from system and device. 

 

Observe and avoid mechanical damage  of 
housing in order to maintain protection class. 

 

Ensure that design, installation and operation 
are according European ATEX Directive, as well 
as the according national standards / regulations 
are respected. 

 
Installation (Fig. 1): 

 

PS4-…ATEX pressure controls  should not be 
exposed to gas pulsations. When pulsations can be 
expected, use a pulsation damper or a capillary tube 
connection (min. 1m). 

 

Mounting directions  per  Fig. 1  in order to prevent 
the collection of contaminant in pressure sensing 
element.

 

 

 

 

Fig. 1

 

 

Brazing (Fig. 2): 

 

Perform and consider the brazing joint as per 
EN 14324. 

 

Before and after brazing clean tubing and brazing 
joints. 

 

Minimize vibrations in the piping lines by 
appropriate solutions. 

 

 

Fig. 2

 

 

Pressure test: 

 

After completion of installation, a pressure test must 
be carried out according to EN 378 for systems which 
must comply with European pressure equipment 
directive 2014/68/EU. 

 

The max. system test pressure shall be 30 bar for low 
pressure side and 41 bar for high pressure side. 

 Warning: 

 

Failure to do so could result in loss of refrigerant 
and personal injury. 

 

The pressure test must be conducted by skilled 
persons with due respect regarding  the danger 
related to pressure

 

Tightness test: 

Conduct  tightness  test  according to EN 378-2  with 
appropriate equipment and method to identify tightness 
of external joints. The allowable leakage rate must be 
according system manufacturer’s specification.  
 

 Electrical connection: 

 

Entire electrical connections have to comply with 
local regulations. 

 

Ensure that the cables are mounted without 
tension; always leave the cable a bit loose. 

 

Ensure that cables are not mounted near sharp 
edges.  

 

Do not bend or mechanically stress the cable 
outlet, maintain a clearance of 20 mm to 
neighboring parts. 

 Operation: 

 

Perform a functional test of electrical circuit 
before charging the system with refrigerant. 

 

 Service / Maintenance: 

 

Defective PS4-…ATEX  must be replaced; they 
cannot be repaired. 

 

Disconnect electrical power before service. 

 

The lowest pressure inside system must be at least 
0.4 bar higher than ambient pressure at any time. 
Failure to do so could accumulate air inside the 
system and create an explosive mixture over time. 

 

Before any debrazing  ensure that the flammable 
refrigerant is pumped out of the system and the 
room around the system is well vented so no 
refrigerant left. 

 
Technical Data of PS4-...ATEX: 

Max. allowable working 
pressure PS 

(see table below) 

Test pressure PT 

(see table below) 

Protection class (EN 
60529) 

IP67 

Temperatures 

Ambient (housing) 

Storage / transportation 

Medium 

 

-30°C…+65°C 
-30°C…+80°C 

-35°C…+135°C 

Released / compatible for

 

 

R290, R1270

 

 

Electrical rating 

50mA

max

. at 24VDC 

max

 

Function 

Pressure limiter, type 

approval EN 12263, 

PSL/PSH 

Pressure controls PS4-…ATEX are factory preset to 
specific switch points (see label). The set points 
cannot be modified. 
Type of electrical contact 

Single pole single throw 

(SPST) 

Marking 

-

 

ENEC05 and CE

0035

  according to PED 

2014/68/EU 

-

 

 

II 3G ExnA IIA T2Gc U 

 

Only PS4-…ATEX  types, listed in the following 
table, are released for use with flammable 
refrigerants!  

Type          Settings 

Part No. 

PS 

(bar) 

PT 

(bar) 

PS4-W1-0.2/1.4 bar ATEX 

808306 

22.7 

25 

  808308* 

PS4-W1 0.6/1.8 bar ATEX 

808301 

22.7 

25 

  808303* 

PS4-W5 0.6/1.8 bar ATEX 

808312 

22.7 

25 

  808311* 

PS4-W1 18/24 bar ATEX 

808305 

37 

41 

  808304* 

PS4-W1 20/26 bar ATEX 

808300 

37 

41 

  808302* 

PS4-W5 20/26 bar ATEX 

808310 

37 

41 

  808309* 

*) Singlepack 

 
 
 
 
 
 
 

!

!

!

!

!

Reviews: