PRECAUTIONS 

16E09-101

Universal Electronic Temperature Control

PART NO. 37-6857G

Replaces 37-6857F

1016

INSTALLATION AND

OPERATION INSTRUCTIONS

DESCRIPTION 

The 16E09-101 is a single stage electronic temperature con-
trol, with a Nema 1 rated enclosure, and can be used for most 
applications within the temperature control range of -40° to 
220°F, (-40° to 104°C). The control has an SPDT (Single Pole 
Double Throw) output load relay.
The control has user options to control differential, anti-short 
cycle delay, set back, offset, alarms and more. It includes an 
NTC (Negative Temperature Coefficient) thermistor tempera-
ture sensor, and can be used with certain other NTC or PTC 
(Positive Temperature Coefficient) thermistors that meet the 
specified resistance vs. temperature specifications. See the 
tables on page 7.
The control can fit many applications, which range from 
refrigeration to heating due to the wide temperature range of 
the control stated above. Typical applications include walk-
in freezers, beverage coolers, supermarket display cases 
for flowers, produce, meats, convenience store refrigerated 
cases, food warmers, boiler control, and certain industrial 
applications. 

Save these instructions for future use!

WARNING

!

16E09-101 Optional Accessories / Service Items:

Immerson Well  .................................................... F89-0286
Replacement 7.5' NTC Remote Sensor .............. F136-0114
Well Heat Transfer Compound ............................. F145-0163

  Failure to read and follow all instructions carefully before 

installing or operating this control could cause personal 
injury and/or property damage.

  To  prevent  electrical  shock,  personal  injury  and/or 

equipment damage, disconnect electric power to system 
at main fuse or circuit breaker box prior to installation 
or service.

  To  prevent  scald  injury,  do  not  use  this  control  to 

heat  water  for  bathing,  washing,  hot  tub  or  similar 
applications.

  Where  failure  of  this  control  may  result  in  personal 

injury and/or property damage, additional alarms or limit 
controls must be installed.

  This control is a temperature control and is not to be 

used as a temperature limit control.

Summary of Contents for 16E09-101

Page 1: ...applications which range from refrigeration to heating due to the wide temperature range of the control stated above Typical applications include walk in freezers beverage coolers supermarket display cases for flowers produce meats convenience store refrigerated cases food warmers boiler control and certain industrial applications Save these instructions for future use WARNING 16E09 101 Optional A...

Page 2: ...E REFER TO PAGE 6 STATUS INDICATOR LED LIT WHEN CONTROLLED LOAD IS ENERGIZED ON SEE NOTE TEMPERATURE UP BUTTON TEMPERATURE DOWN BUTTON MENU BUTTON PRESS TO ENTER MENU MODE REFER TO PAGES 4 5 SW1 Refrigeration Cool Heating Heat Switch SW1 must be set for system mode as shown To prevent electrical shock and or equipment dam age disconnect electric power to system at main fuse or circuit breaker box ...

Page 3: ... optional connection to customer alarm equipment Binary Input Gold Plated Contacts 24 VAC Block not used TH Thermostat Hot TR Thermostat Return NTC Temperature Sensor PTC Temperature Sensor Fig 3 Line Voltage Application Power Stealing 120 VAC Hot Neutral L1 L2 208 240 VAC Voltage Input Load Power Stealing Power Stealing is an electronic design within the control that can eliminate the need to con...

Page 4: ...s how the set point temperature will operate the load terminal CI indicates the setpoint temperature will be the Cut In temperature CO indicates the temperature will be the Cut Out temperature See Operation section SOF Sensor Operation Failure Cool Heat 1 0 0 or 1 None Cooling Selects the operation of the Control Load relay in the event of a sensor failure in Cool mode 1 default will cause the loa...

Page 5: ...l Set Point SP Cut In Differential 5 Setpoint temperature 40 Temperature Range 40 Setpoint Cut Out 45 SW1 Cool Set Point SP Cut Out Differential 5 Setpoint temperature 40 Temperature Range HEAT To use as a Heating control SW1 must be set to Heat The flame icon will display If control is in Heat mode and Set Point is selected as the Cut Out Temperature Operating Setpoint Differential Range Temperat...

Page 6: ... should be given to these events to prevent a false alarm If the control set back feature is used to change the setpoint the delay period set in AL should consider the time it takes for the system to reach the set back temperature to avoid a false alarm Power Loss If the temperature control experiences an input power failure the control will close the alarm relay before total power of the control ...

Page 7: ...Resistance KΩ 140 60 2 49 149 65 2 09 158 70 1 76 167 75 1 48 176 80 1 26 185 85 1 07 194 90 0 92 203 95 0 79 212 100 0 68 221 105 0 59 Temperature F C Resistance KΩ 40 40 613 31 35 640 22 30 668 13 25 697 4 20 727 5 15 758 14 10 789 23 5 822 32 0 855 41 5 889 Temperature F C Resistance KΩ 50 10 924 59 15 960 68 20 997 77 25 1035 86 30 1074 95 35 1113 104 40 1153 113 45 1194 122 50 1236 131 55 127...

Page 8: ... line 1 888 725 9797 www white rodgers com www emerson com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co TROUBLESHOOTING Temperature differential is wider than set Temperature change of customer s unit is fast and the Anti Short Cycle delay setting may be overriding the call to activate the heat or cool Solution lower Ant...

Page 9: ... descongelación o cualquier otro dispositivo con la función de alarma activada Esto produciría una falsa alarma Si la función de alarma está activada conecte según el diagrama de Non Power Stealing El diferencial de temperatura es más amplio que el ajustado El cambio de temperatura de la unidad del cliente es rápido y el ajuste de demora anti ciclo corto podría estar anulando la llamada para activ...

Page 10: ... DE TEMPERATURA VS RESISTENCIA PTC según sea necesario La polaridad no es importante Si ex tiende la longitud del cable verifique que la temperatura sea precisa y utilice los ajustes de compensación de temperatura ambiente OFS del menú para compensarla en caso de que sea necesario más de 50 pies y el cable deberá tener un calibre de 18 AWG o un diámetro más grande Asegúrese de que la sonda conecta...

Page 11: ...rio cambie la opción de menú LP a On Al salir del menú cuando se guarden los ajustes las teclas o y quedarán desactivadas del uso normal Para desbloquear el teclado presione y manténgalo presionado durante 5 segundos La pantalla cambiará y mostrará LP On Presione o por un momento para cambiar el ajuste a Off y luego presione durante algunos instantes El control volverá a su funcionamiento normal y...

Page 12: ...la temperatura de referencia se selecciona como temperatura de desconexión Rango operativo de Temperatura Diferencial temperatura de referencia más Ejemplo 40 Temperatura de referencia Temperatura de desconexión 45 SW1 Enfriamiento Temperatura de referencia SP Temperatura de desconexión Diferencial 5 Temperatura de referencia 40 Rango de temperatura CALOR HEAT Para usar como control de calefacción...

Page 13: ...ado Off On u Off del panel frontal OFS Compensación de 0 4 3 2 1 0 temperatura ambiente 1 2 3 4 Opción Ajuste Opciones del de Presione o menú Descripción fábrica para seleccionar Observaciones Enfriamiento Selecciona el funcionamiento del relé de carga de control en caso de una falla del sensor en el modo Frío 1 ajuste predeterminado hace que los contactos de carga del relé se cierren y si el sens...

Page 14: ...e alarma Para la conexión opcional al equipo de alarma del cliente NTC Coeficiente de temperatura negativo PTC Coeficiente de temperatura positivo NOTA Sólo es posible conectar un sensor PTC o NTC El sensor debe cumplir con las especificaciones de temperatura vs resistencia indicadas Power Stealing Power Stealing es una característica electrónica del control que elimina la necesidad de conectar un...

Page 15: ...6 LED INDICADOR DE ESTADO SE ENCIENDE CUANDO LA CARGA CONTROLADA ESTÁ ENERGIZADA ON VEA LA NOTA BOTÓN DE INCREMENTO DE TEMPERATURA BOTÓN DE REDUCCIÓN DE TEMPERATURA BOTÓN DE MENÚ PRESIONE PARA INGRESAR EN EL MODO DE MENÚ REFIÉRASE A LAS PÁGINAS 4 Y 5 SW1 Enfriamiento Cool Calefacción Heat El interruptor SW1 debe ajustarse para el modo de funcionamiento del sistema como muestra la figura Para evita...

Page 16: ...ras carnes en super mercados exhibidores refrigerados en tiendas de conveniencia calentadores de comida control de calefactor y ciertas aplica ciones industriales ADVERTENCIA Lea y siga con atención todas las instrucciones antes de instalar o utilizar este control para evitar lesiones personales y o daños materiales Para evitar descargas eléctricas lesiones personales y o daños al equipo desconect...

Reviews: