background image

 

Fire Alarm Systems | FPC-7034 IDC expander, 4-point

FPC-7034 IDC expander, 4-point

 

www.boschsecurity.com

 

 

 

 

 

 

 

 

u

Adds four Class B or two Class A initiating circuits
to the FPD‑7024 FACP

u

For use with normally‑open (NO) or normally‑closed
(NC) alarm contacts

u

Compatible with two‑wire or four‑wire smoke
detectors

u

Up to 20 two‑wire smoke detectors per circuit

u

Easy installation due to plug‑in design and screw
terminal circuit connections

The FPC‑7034 Four-point Expander doubles the
number of alarm initiating device circuits on the
FPD‑7024 Fire Alarm Control Panel (FACP). These
circuits are identical to the circuits on the FACP.
This plug‑in module is automatically recognized by the
control panel's firmware when power is restored to
the system.

Certifications and approvals

Region

Regulatory compliance/quality marks

USA

UL

UL 864, Control Units and Accessories

for Fire Alarm Systems

FM

FPC-7034

CSFM

see www.boschsecurity.com (the Bosch

website)

FDNY-

CoA

6173

Installation/configuration notes

Compatible Products

The FPC‑7034 is compatible with the FPD‑7024 FACPs.

For a list of compatible smoke detectors, see the FPD

7024 Smoke Detector Compatibility List Technogram.

Notice
When four‑wire smoke detectors are used, power
must be supplied to the detectors from either the
control panel or an external power source.

Mounting Considerations

The FPC‑7034 mounts on the FPD‑7024 control board,
just to the right of the keypad. Use the four nylon
stand‑offs supplied with the expander.

Initiating Circuit Wiring

Circuit connection for the expansion initiating circuits
is identical to the on‑board circuit configuration. For
wiring details, see the FPD‑7024 Installation Guide.
Install a supplied EOL resistor at the end of each
wiring run.

Parts included

Quantity

Component

1

Four-loop expander board

4

2.21 kΩ End‑of‑Line (EOL) resistors (P/
N: 25899)