background image

Installation Instructions

for the

DS9432/DS9432B Eight Input Remote Module

1.0  Description

The DS9432/B is an Eight Input Remote Module that provides a
means of addressing up to eight input loops of conventional
contacts to the multiplex bus of the DS9400 Series Fire Alarm
Control/Communicator.

2.0 Specifications

• Control Panel Requirements

: The DS9432/B is designed to

work with the Detection Systems DS9400 Series Fire Alarm
Control Communicator. Version 2.0 software or higher is required
in the DS9400. The DS9400 can support up to 30 DS9432/B
modules. One DS9431 Multiplex Expansion Module is required
in the system to use the DS9432/B Eight Input Remote Module.

Current Draw (from option bus power):

 8 mA Standby and Alarm

Current Draw (from multiplex bus loop):

 10 mA Standby and

Alarm

Total Current Draw for Battery Standby Calculation and Alarm:

18 mA Standby and Alarm

• Minimum Bus  Voltage For Operation:

 8 VDC peak

Wiring:

 Refer to the 

DS9400M Reference Guide

 (P/N:  44578) for

the panel’s multiplex expansion module for multiplex wiring
requirements. The length of the wire connected to the loop inputs
on the DS9432/B must be less than 250 ft. (76 m) per loop.

• The recommended minimum wiring to the control is standard #18

(1.2 mm). 

Do not use shielded or twisted pair cable

.

For UL Listed fire applications, minimum #18 AWG (1.2

mm) wire is required.

3.0  Installation

P3 of the DS9432 is for European applications only. Do

not put a jumper here.

P2 of the DS9432 allows the tamper switch to be bypassed with a
jumper when testing or servicing.

Remove  jumper P2 when testing or servicing has been

completed.

3.1 DS9432 Installation

Use the mounting holes (upper left and lower right corners) to
mount. It can be mounted inside or outside of the control enclosure.

Route wiring as necessary from the DS9431 in the control enclosure
and from the remote devices to the DS9432.
Connect wiring as shown in Figure 2.

Be sure all wiring is unpowered before routing.

If the wiring is to enter through the rear of the enclosure, open the
DS9432's rear wire entrance. If the wiring is to run along the surface
of the enclosure, open the DS9432's surface wire entrance. See Figure
2.

3.2 DS9432B Installation

The DS9432B will come partially preassembled with the circuit board
attached to the mounting skirt.

Mounting Holes

Attach Mounting Skirt Here

Figure 1:  DS9432B

Select a mounting location for the DS9432B.

Using the enclosure as a template, mark the mounting holes on the
mounting surface and make an opening for the unit’s wiring.

Next, attach the mounting skirt (with the circuit board attached) to
the enclosure (hardware provided). Then complete all wiring (see
Section 4.0).
Once installation and wiring is completed, attach the enclosure
cover and secure with the screws (provided).

Summary of Contents for DS9432B

Page 1: ... Listed fire applications minimum 18 AWG 1 2 mm wire is required 3 0 Installation P3 of the DS9432 is for European applications only Do not put a jumper here P2 of the DS9432 allows the tamper switch to be bypassed with a jumper when testing or servicing Remove jumper P2 when testing or servicing has been completed 3 1 DS9432 Installation Use the mounting holes upper left and lower right corners t...

Page 2: ...Drill Test History Reset Silence Trouble Silenced Power Alarm 2 3 4 5 6 7 8 POWER 12V Power 12V Power EOL Resistor P N 28010 Smoke Detector Smoke Detector EOL Relay Bus Power may be connected to RA or RB on the FACP Option Bus terminal strip Power may be connected to BA or BB on the FACP Option Bus Bus and Bus are connected to MUX A terminals for addresses 9 128 MUX B terminals are for addresses 1...

Page 3: ...44578 for zone programming information 5 2 DIP Switch Settings The DIP switches select which points will be activated by the loop inputs Set the DIP switches as shown in Table 1 No two DS9432 Bs should be set the same The input loops of the DS9432 B correspond to the points of the control as shown in Table 2 ON OFF Figure 4 DIP Switch Orientation 1 2 3 4 5 6 7 8 POWER BUS Locking tab Surface Wire ...

Page 4: ...ints 201 208 Points 193 200 Points 185 192 Points 177 184 Points 169 176 Points 161 168 Points 153 160 Points 145 152 Points 137 144 Points 129 136 Points 121 128 Points 113 120 Points 105 112 Points 97 104 Points 89 96 Points 81 88 Points 73 80 Points 65 72 Points 57 64 Points 49 56 Points 41 48 Points 33 40 Points 25 32 Points 17 24 Points 9 16 Input Loop 241 233 225 217 209 201 193 185 177 169 ...

Reviews: