Access Control Interface Module D9210B

Operation and Installation Guide

Summary of Contents for D9210B

Page 1: ...Access Control Interface Module D9210B Operation and Installation Guide ...

Page 2: ...D9210B D9210B Operation and Installation Guide 32206G Page 2 2002 Bosch Security Systems ...

Page 3: ...12 2 6 2 Other Listings and Approvals 12 3 0 Installation 13 3 1 System Planning 13 3 2 Procedure 13 3 2 1 Step 1 Mounting the Enclosure and Installing the D9210B 13 3 2 2 Step 2 Pulling and Marking the Wires 14 3 2 3 Step 3 Mounting 16 3 2 3 1 D9210BLC 16 3 2 3 2 D9210B 16 3 2 3 3 D9210BC 16 3 2 4 Step 4 Door Contact Onboard Point Terminals 9 and 10 16 3 2 5 Step 5 Door Lock Terminals 2 3 and 4 1...

Page 4: ...ings 19 Figure 5 Power Supply and SDI Connections 20 Figure 6 D9210B Door Release Application Connections 23 Tables Table 1 D9210B Operation and Installation Guide Document Organization 5 Table 2 Other Literature Referenced 5 Table 3 D9210B Diagnostic and Status LEDs 9 Table 4 Typical Wire Planning Chart for the D9210B 14 Table 5 Point Tolerance Voltages 16 Table 6 Door Lock Strikes 17 Table 7 UL ...

Page 5: ...cations Table 1 D9210B Operation and Installation Guide Document Organization 1 2 Other Literature Referenced Throughout this document references will be made to other documentation For a more complete and detailed description of the D9210B Access Control Interface Module see the following table that lists the complete part number for ordering purposes Name of document P N D9210B Program Entry Gui...

Page 6: ...f not installed in accordance with the manufacturer s instructions it may cause interference to radio communications It has been tested and found to comply with the specifications in Subpart J of Part 15 of FCC Rules for Class B Computing Devices If this equipment causes interference to radio or television reception which can be determined by turning the equipment on and off the installer is encou...

Page 7: ... zone input on the D9210B is used for the door contact that is physically mounted on the door to which the strike is connected The input can be configured for shorts opens on faults but is normal only when the 1000 k Ω resistor is in the circuit Unsupervised tamper input The unsupervised tamper input is normal when open Upon a short the point number assigned to the supervised zone is reported as a...

Page 8: ...ss Levels Armed State rights Users can be prevented from access depending upon the armed state of the area that the D9210B is assigned to M indicates the user has access no matter what the armed state P indicates the user has access as long as the Area is perimeter armed or disarmed and D indicates the user only has access when the area is completely disarmed Disarm Access Level Users are allowed ...

Page 9: ...al Blocks Diagnostic and Status LEDs PROM DIP Switch Relay Figure 1 D9210B Access Control Interface Module LED Action State Operational Monitor Green LED blinks on and off System is operational LED is on or off solid System is off or not operational D0 Reader Green LED rapidly blinking Card data executing LED is off No card data is being received D1 Reader Yellow LED rapidly blinking Card data exe...

Page 10: ...Unlocked with door point text Door Locked with door point text Alarm Point with door point text Trouble Point with door point text Missing Point with door point text Please Close Door with door point text 2 4 Materials Included Bosch Security Systems ships the D9210B Access Control Interface module pre assembled from the factory with a power supply in its own can or as a unit less can You will rec...

Page 11: ...unting screws and fasteners Two additional modules can be mounted using the D136 brackets Bosch Security Systems recommends that you use a separate power supply for the D9210Bs to isolate them from other SDI devices D9210BC The D9210BC is a complete unit mounted on a mounting skirt D9201M with a 12 VDC 2 5 A power supply and 1 D9210B It can be installed with another D9210BLC in a single D8103 D810...

Page 12: ...Access Control System Local Police Connect Central Station or Proprietary Burglar Alarm System and a Commercial Fire Alarm System In addition to the manual refer to the D7412 D9412 installation documentation regarding Burglar Alarm Grades and Fire Alarm services supported The D9210B is a Signaling Device Subassembly also suitable as a Burglar Alarm Unit Accessory Subassembly and Access Control Uni...

Page 13: ...9210B may be remoted up to 5000 ft 1524 m Consider placing the enclosure where a technician can gain easy access for troubleshooting the unit and where wiring can be routed easily Preparing Knockouts The D9210B requires six primary wire runs to be routed to the enclosure see Table 4 Typical Wire Planning Chart for the D9210B p 14 To identify the proper knockouts required determine from which direc...

Page 14: ... 18 AWG quad 5000 ft 1 524 m SDI A Green B Yellow Pwr Red Black RTE power input Tag B 0 25 in 6 4 mm 4 22 AWG quad Green Black REX power input Tag C 0 25 in 6 4 mm 4 22 AWG quad Yellow Black Strike power Tag D 0 375 in 9 5 mm 2 16 18 AWG zip Red Door contact Tag E 0 125 in 3 2 mm 2 22 AWG 500 feet 152 m White Reader Tag F 0 375 in 9 5 mm 6 22 AWG conductor 500 feet 152 m 12 VDC Red 5 VDC Orange CO...

Page 15: ...re DC OUTPUT black white yellow green SDI PWR SDI A SDI B SDI COM Security Panel black EMERGENCY EGRESS DOOR DOOR CONTACT NORMAL E O L IN CIRCUIT 1K E O L RTE REX NORMAL OPEN white green red brown 12 VDC BUZZER 12 VDC READER yellow TAMPER SWITCH NORMAL OPEN black 12 VDC DOOR STRIKE Some jurisdictions will not allow the use of Emergency Egress as your sole means of escape If this feature is used it...

Page 16: ... provided around the sides of the enclosure 4 2 The unit can be added to a D9210BC by matching the three plastic mount anchors to the available three hole foot prints below the factory installed D9210B 3 To secure the unit use the three 8 3 4 in screws provided 3 2 4 Door Contact Onboard Point Terminals 9 and 10 Voltage VDC Description 0 1 2 Loop shorted 1 8 Coming from a shorted condition the D92...

Page 17: ...tallation 3 2 6 Request to Enter RTE Terminals 11 and 12 Description When Terminal 11 is momentarily shorted to Terminal 12 the strike is activated and the door point is shunted Shunt Only An option is provided that only shunts the point when this input is momentarily shorted To activate the shunt but not the strike program RTE Shunt Only as YES 3 2 7 Request to Exit REX Terminals 13 and 12 Descri...

Page 18: ...mity cards 26 bit D8224 5 80 mA Proximity slim Gray N A D8236 proximity cards 26 bit D8229 5 120 mA Keypad reader N A N A 26 bit 12 V power from D9210B source Table 7 UL Listed Compatible Readers for the D9210B Readers can be mounted up to 500 ft 152 m from the D9210B module A typical reader connection is shown in Figure 2 Wiring Diagram for Typical D9210B Installation p 15 Terminal 1 12 VDC The r...

Page 19: ... possible be consistent when numbering doors control centers and areas This will help when programming a system with more than one door Example Assign Door 1 to Area 1 and Control Center 1 The D9210B dipswitch with factory default settings all ON is shown in Figure 4 Table 8 shows the serial device reporting address settings for each door controller Table 8 also shows dipswitch settings for Test a...

Page 20: ...upply UL Listed for Fire DC OUTPUT red black Security Panel SDI PWR SDI A SDI B SDI COM white yellow green black 2 LCKN C SDI PWR 1 PWR D9210B Security Panel 3 LCKCOM 4 LCKN O 5 COM 6 SDIA 7 SDIB 8 T 9 ZNCOM 10 ZN Note In installations where powering the D9210B with the security panel is impractical a 12 VDC power supply can be substituted SDI A SDI B SDI COM white yellow green black 24 VDC AUX Po...

Page 21: ...e Using the Control Center verify the point is normal when the door is closed the point goes off normal when the door is opened and a shunt is not applied and that the point stays normal upon opening the door on a valid access granted Strike Read a valid token to activate the strike If tokens have not been added use the Door Control Door Unlock mode to cycle the strike In addition you will cycle t...

Page 22: ...D9210B Installation D9210B Operation and Installation Guide 32206G Page 22 2002 Bosch Security Systems Notes ...

Page 23: ... shown in Figure 6 Program Point Index in the POINTS handler as Supervisory with Point Response as A Supervisory on Open and Trouble on Short The power supply end of line relay and the D9210B must be in the same enclosure or adjacent enclosures connected via conduit not longer than 20 ft 6 m D9210B AUX POWER UL Listed for Fire POPIT RELAY DOOR A MAGNETIC DOOR HOLDER 1 PWR 2 LCKN C 3 LCKCOM 4 LCKN ...

Page 24: ...D9210B Operation D9210B Operation and Installation Guide 32206G Page 24 2002 Bosch Security Systems Notes ...

Page 25: ...trike is latched to allow access Unlocked Green to Red to Green Access Denied Red Valid token format not added Locked Red to Green to Red pattern repeats twice Red Valid token but level is turned off Locked Red to Green to Red pattern repeats twice Red No access allowed regardless of level because door is secured Secured Red to Green to Red pattern repeats three times Custom Function Red Valid tok...

Page 26: ...D9210B Troubleshooting D9210B Operation and Installation Guide 32206G Page 26 2002 Bosch Security Systems Notes ...

Page 27: ...r input 1 kΩ pull up V in 1 8 V on 3 2 V off 9 ZNCOM Common input for on board point 1K Ω termination resistor between T9 and T10 required 1 0 ZN Positive Input for on board point 1 1 RTE Input from Request to Enter RTE momentary short device open collector input 1kΩ pull up V in 1 8 V on 3 2 V off 1 2 COM Common input for REX RTE devices 1 3 REX Input from Request to Exit REX momentary short devi...

Page 28: ...2002 Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 USA Customer Service 800 538 5807 Technical Support 888 886 6189 32206G Operation and Installation Guide 10 02 D9210B Page 28 of 28 ...