background image

Fire Alarm Systems | FLM‑325‑IM Contact Module

The FLM‑325‑IM Contact Module provides a variety of fire
alarm functions, such as monitoring manual pull stations,
waterflow devices, or other dry contact fire alarm
activation applications. The module allows for alarm,
trouble, and supervisory conditions. The module is
mounted inside of a single‑gang back box and is normally
out of view.

System Overview

The FLM‑325‑IM Contact Module allows compatible fire
alarm control panels (FACP) to supervise Form A or B dry
contact devices in a polling circuit. The module has an
eight‑bit microprocessor and communicates with the
control panel (both power and data) over a two-wire
polling circuit. The initiating device circuit (NFPA Style B)
connected to the module can have up to 20 normally-open
(NO) dry contact devices. Each module can monitor one
normally-closed (NC) device (NC devices must be non-
alarm applications).

Certifications and Approvals

Region

Certification

USA

UL

UOXX: Control Unit Accessories, System
(ANSI/UL 864)

Installation/Configuration Notes

The following products are compatible with the
FLM‑325‑IM Contact Module:

Category

Product ID

Product Description

Control Panels: FPA‑1000 

Series

Analog addressable fire panels

Pull Stations

FMM‑325A

Analog addressable manual pull 

station (single action)

FMM‑325A‑D

Analog addressable manual pull 

station (double action)

Programmers:

D5070

Analog device programmer

FLM‑325‑IM Contact Module

Digital data communications and power provided over

a two-wire circuit

Advanced digital communications protocol

compatible

Class B circuit for dry contact devices

Module address programming (1-254) with the D5070

Analog Device Programmer

www.boschsecurity.com