background image

AMAX panel 2000 / AMAX panel 2000 EN

ICP-AMAX-P / ICP-AMAX-P-EN

en

Installation Manual

Summary of Contents for AMAX panel 2000 EN ICP-AMAX-P-EN

Page 1: ...AMAX panel 2000 AMAX panel 2000 EN ICP AMAX P ICP AMAX P EN en Installation Manual ...

Page 2: ......

Page 3: ...systeme GmbH F 01U 241 127 V4 2011 12 1 Graphics GPRS IP IP PSTN TELEPHONE NETWORK CENTRAL MONITORING STATION DX4020 ITS DX4020 G IUI AMAX LCD8 IUI AMAX LED8 BOSCH AMAX panel 2000 OVERVIEW DX3010 BOSCH OPTION BUS ICP AMAX P EN ICP AMAX P B420 or ...

Page 4: ...4 ICP AMAX P ICP AMAX P EN F 01U 241 127 V4 2011 12 Bosch Sicherheitssysteme GmbH ...

Page 5: ...of the System 17 4 User Guide 19 4 1 Arming the System 22 4 1 1 Arming in AWAY mode 22 4 1 2 Arming in STAY mode 23 4 1 3 Forced arming 24 4 2 Disarming the System 24 4 2 1 Disarming with CODE 24 4 2 2 Disarming with wireless control Key 24 4 2 3 Disarming with Key switch 24 4 3 Faults or Tamper conditions 24 4 3 1 System fault or tamper analysis Mode 24 4 4 Walk test mode 25 4 5 Event Memory Reca...

Page 6: ...lt 34 5 5 Date and Time Fail 35 5 6 Communication Failure 35 5 6 1 Communication Failure 1 35 5 6 2 Communication Failure 2 35 5 6 3 Communication Failure 3 35 5 6 4 Communication Failure 4 36 5 7 Tamper Condition 36 5 7 1 On Board Tamper 36 5 7 2 Keypad 1 Tamper 36 5 7 3 Keypad 2 Tamper 36 5 7 4 Keypad lock out 37 5 7 5 Sensor Tamper 37 5 7 6 Zone Tamper 37 5 8 External Fault 38 6 System Function...

Page 7: ...ssing when disarming 48 7 3 Alarm processing 48 7 4 Software 49 7 4 1 Remote Connect 49 7 4 2 Remote Connect with Customer Control 49 7 4 3 Remote Connect with Callback Verification 49 7 4 4 Remotely Arm Disarm System by Programming Softwares 50 7 5 Domestic Dialing 50 7 5 1 Domestic Dialing Function 50 7 6 Reporting Formats 50 7 6 1 Transmission Formats 50 7 6 2 Contact ID Format 50 7 6 3 CFSK Fo...

Page 8: ...me 72 8 5 2 Exit Time 73 8 5 3 Keypad Lockout Time 73 8 5 4 System Power Up Wait Time 73 8 5 5 AC MAINS Fail Wait Time 73 8 6 Optional Equipment 73 8 6 1 RE012 E 2 Channel Hand Held Keyfob 433 MHz 73 8 6 2 WE800E 433 MHz RF Receiver 73 8 6 3 ICP EZPK Programming Key 73 8 6 4 A Link Plus Software 73 8 6 5 DX3010 8 Relay Module 73 8 6 6 B420 DX4020 ITS DX4020G GSM GPRS Communication Module 74 8 6 7 ...

Page 9: ...1 Quick Emergency Alarm 81 10 3 12 Event Recall 81 10 3 13 OC1 Warning Device 1 Monitor 81 10 3 14 OC2 Warning Device 2 Monitor 81 10 3 15 Phone line Monitor 81 10 3 16 AC Fault Detect time 82 10 3 17 Battery Detect time 82 10 3 18 Event Record Count Per Set Unset Period 82 10 3 19 Beep for Warning Devices 82 10 4 Zone Programming 82 10 5 Output Programming 85 10 5 1 Keypad Buzzer 85 10 5 2 Warnin...

Page 10: ...ming simplicity and speed are our major considerations we believe that our objectives have been attained This installation guide explains all aspects of programming the AMAX panel 2000 AMAX panel 2000 EN from factory default to final commissioning All system parameters and options are dealt with in detail but adaptability differs with individuals Each control panel can be tailored to meet your req...

Page 11: ...BOSCH DX4020 IP and DX4020G GPRS modules Telephone line monitor function Keypad duress panic fire and medical alarms Keypad Code STAY AWAY Arming One Button Code STAY AWAY Arming Keyfob AWAY Arming Disarming Telefone AWAY Arming RPS remote program upload download RPS remote control Quick programming key Dynamic battery testing Entry Exit warning beeper AC Fail and system fault indicators Fault inq...

Page 12: ...ller s access 4 Enter Date and Time Refer to Section 3 1 1 Setting date and time page 13 5 Enter the default Installer Code 1234 958 and press Two beeps sound and the STAY and AWAY indicators flash simultaneously to indicate that you have entered into installer s programming mode Once you enter the installer s programming mode you are automatically positioned at location 000 the first digit of IP ...

Page 13: ... indicates an erroneous entry of date and time 3 If operation is not carried out within 240 seconds after entering the date and time setting interface the system will automatically exit from the setting ICP AMAX P ICP AMAX P EN 5 5 7 7 3671 3RUW 7DPSHU 6ZLWFK 3RUW QVWDOODWLRQ RGH 5HVWRUH 3 3 3URJUDP H 3RUW Z8 COM Z7 Z6 COM Z5 Z4 COM Z3 Z2 COM Z1 Y G B R GND 12V OC2 OC1 RQH RVFK XV X 3RZHU 2XWSXW 3...

Page 14: ...he data retention time is quite long without power reprogramming is not required after powering up the control panel You can change data as many times as required without any additional specialized equipment The memory is organized in locations each of which holds the data for a specific function In general the entire programming sequence consists of selecting the required location and entering or...

Page 15: ...he beginning of the subscriber ID number 17 for receiver 1 The data stored in the new location appears To move to the next location Press For example if you are currently positioned at location 017 press to move to location 018 To move to the previous location Press For example if you are positioned at location 018 press to move back to Location 017 To change data in the current location Enter the...

Page 16: ...l memory to the programming key page 46 3 Enter 9 6 0 to exit from installer s programming mode 4 The system resets and returns to the disarmed state And the programming key becomes your standard data pattern for future control panel programming 3 3 3 Installer s Programming Command There are six commands that you can use in installer s programming mode To issue the command enter the command numbe...

Page 17: ...e connected to a Central Monitoring Station A 12V 7AH Battery must be connected to the System The Maximum Current of all Components together PCB lOOmA lCP KP8L 18mA ICPKP8 24mA should not exceed 550mA The lock can only be used in an non EN setup The panel must be programmed with the EN settings indicated on the programming sheet When the panel is set without EN parameters the EN Indication Label m...

Page 18: ... en Installation AMAX panel 2000 AMAX panel 2000 EN F 01U 241 127 V4 2011 12 Installation Manual Bosch Sicherheitssysteme GmbH Figure 3 4 5 Reassemble the Keypad it s now ready for use in you re EN setup ...

Page 19: ... quick arming Disarming Disarm code Other Commands Fault and Tamper Analysis code 2 Walk test code 4 Event recall code 5 System Reset code 6 Bypassing zones code 9 zone Bypassing Faults and Tamper conditions code 97 Enable Disable Installer code Enable code 98 Disable code 98 Change individual code code 99 newcode Alarm Commands Duress alarm code 0 Emergency alarm Simultaneously press and hold 1 a...

Page 20: ...nd lights on 1 second lights off Exit time Fast flash 0 25 seconds lights on 0 25 seconds lights off Programming mode or Code function mode STAY indicator flashes simultaneously STAY on System is armed in STAY mode off System not armed in STAY mode Slow flash 1 second lights on 1 second lights off Exit time Fast flash 0 25 seconds lights on 0 25 seconds lights off Programming mode or Code function...

Page 21: ...eep The requested operation is refused Incorrect operation signal Two short beeps The system accepted the code The system executed the requested function One short beep per second In walk test mode One short beep every two seconds Exit time started Continued sound Last 10s on exit time Keypad fault tamper sound fault tamper to be acknowledged Keypad alarm sound Continuous 0 5 second beep stops 0 5...

Page 22: ... _____________________________________________________ Code 9 _______________________________________________________Keyfob 1 Code 10 _____________________________________________________ Keyfob 2 Code 11 _____________________________________________________ Keyfob 3 Code 12 _____________________________________________________ Keyfob 4 Code 13 _____________________________________________________...

Page 23: ...ts After exit time the AWAY indicator is lit When the Key switch is deactivated the system is disarmed and Away indicator is off 4 1 2 Arming in STAY mode STAY Mode is used when you need to arm the perimeter and unused areas of the premises to detect a would be intruder while at the same time being able to move freely within an area that is automatically isolated There are two methods to arm your ...

Page 24: ...ed the system is disarmed and the AWAY or STAY indicator is extinguished 4 3 Faults or Tamper conditions Whenever a system fault or tamper condition occurs the FAULT or MAINS indicator flashes and the keypad beeps 4 3 1 System fault or tamper analysis Mode To enter fault or tamper analysis mode for determining a system fault or tamper condition 1 Enter your Code and 2 and press Two beeps sound The...

Page 25: ...call mode This function allows you to playback the last 254 system events that occurred Event Memory recall mode reports all alarms and each arming or disarming of the system and helps in troubleshooting system faults The events are shown using the keypad indicators Defined events are shown using keypad indicators To enter Event memory Recall mode Enter your code 5 and press Two beeps sound The ev...

Page 26: ... bypassing Zones one or more zones are disabled for one arming cycle After bypassing a zone you can arm the system even when a zone is in alarm state How to bypass a zone 1 Enter your code and press 9 The STAY indicator flashes fast 2 Enter the zone number you wish to bypass then press the key If you wish to bypass multiple zones please repeat step 2 3 If you wish to cancel bypassed zone enter the...

Page 27: ...ur user number is shown on the keypad 2 Enter the new code and press Two beeps sound and the STAY and AWAY indicators are extinguished 4 10 Keypad alarm operation commands 4 10 1 Duress alarm A keypad duress alarm is used as a silent holdup alarm when 0 is added to the end of a valid Code used to disarm the system code 0 A duress alarm is useful only if your system reports to a monitoring station ...

Page 28: ...elephone number of a family member friend A maximum of one telephone number can be called through the control panel during an alarm Contact your installer to enable disable the Domestic dialing functionality 4 11 2 Confirming the Domestic call All alarm events need acknowledgement The transmission sequence is repeated until the control panel recieves an acknowledgement tome The control panel autom...

Page 29: ...d press two beeps sound The FAULT indicator remains lit and the STAY and AWAY indicators flash The lit zone indicators indicate the type of fault or tamper condition that occurred 2 For multi level menu enter the corresponding number to enter the submenu press 0 key to return to the main menu 3 To exit from Fault and Tamper Analysis Mode press The STAY and AWAY indicators are extinguished and the ...

Page 30: ...r to 5 2 1 AC Fault Refer to 5 2 1 2 Fault Battery Refer to 5 2 2 3 Aux Power Supply Fault Refer to 5 2 3 4 Bosch Option Bus Power Fault Refer to 5 2 4 5 RF Power Fault Refer to 5 2 5 3 Warning Device Failure List Refer to 5 3 1 Warning Device 1 Disconnected Refer to 5 3 1 2 Warning Device 1 Short Refer to 5 3 2 3 Warning Device 2 Disconnected Refer to 5 3 3 4 Warning Device 2 Short Refer to 5 3 4...

Page 31: ...2 Flash FAULT indicator on the other keypad in normal operation refer to the detailed description in chapter keypad indicators 3 Keypad missing communication with the panel performance as below Stop detection on the keypad button Flash FAULT indicator The disconnected keypad does not sound FAULT beeping per min 4 When the fault is reset send the restore report to the configured destinations of the...

Page 32: ...e fault occured report the fault to configured destination on location 140 3 Slow flash FAULT indicator refer to the detailed description in chapter keypad indicators 4 As the AC supply is reconnected the MAINS indicator is back to light except in Programming Mode or Code Functions Mode 5 When the fault is reset send the restored report to the configured destinations 5 2 2 Battery Failure Conditio...

Page 33: ...ault is reset send the restored report to the configured destinations The FAULT indicator is turned off when there is no other system fault 5 2 5 RF Power Supply Fail Condition Voltage is lower than 4V 5 Restore Voltage is raised to 5 5V 5 and fault is reset Supervise 1 Monitor the voltage by MPU 2 Report the RF power fault to the configured destination programmed on location 140 3 Slow flash FAUL...

Page 34: ...e siren fault to the configured destination programmed on location 140 3 Slow flash FAULT indicator refer to the detailed description in chapter keypad indicators 4 When the fault is reset send the restored report to the configured destinations The FAULT indicator is turned off when there is no other system fault 5 3 4 Warning Device 2 Short Condition Warning Device output is shorted Restore Warni...

Page 35: ...o step to Communication failure list for more information 5 6 1 Communication Failure 1 Condition Panel can not send the report to the Destination 1 after 4 attempts Restore The fault is reset when the first kissoff tone is received and fault is reset Supervise 1 Report the fault to configured destination on location 140 when the fault is detected 2 Slow flash FAULT indicator refer the detailed de...

Page 36: ...n The zone indicator 7 lights to indicate Tamper conditions Enter 7 to step to Tamper conditions list for more information 5 7 1 On Board Tamper Onboard Tamper Condition is registered when the Onboard Tamper input P8 is open Condition Onboard Panel Tamper input P8 is open Restore The Tamper condition is reset when the Input is shorted and Tamper condition is reset Supervise 1 Report the Tamper con...

Page 37: ...rned off when there is no other system fault 5 7 5 Sensor Tamper Condition Tamper contact is triggered Zone is programmed as Dual End of Line Restore Tamper contact is restored and Tamper condition is reset Supervise 1 Report the Sensor Tamper to configured destination on Location 140 when the Sensor Tamper is detected 2 Slow flash FAULT indicator refer the detailed description in chapter keypad i...

Page 38: ...ult Restore Fault contact is restored and Fault condition is reset Supervise 1 Report the Fault condition to configured destination on Location 140 when the Fault condition is detected 2 Slow flash FAULT indicator refer the detailed description in chapter keypad indicators 3 When the Fault is reset send the restored report to the configured destinations The FAULT indicator is turned off when there...

Page 39: ...w Zone type Refer to 6 11 97 Bypass all faults Refer to 6 12 98 Enable Disable installer code user s access Refer to 6 13 99 Change individual code Refer to 6 14 955 Change View date and time Refer to 6 15 956 Add delete a level 2 user Refer to 6 16 956 Add delete Remote Radio User Codes Refer to 6 17 957 Change domestic phone numbers Refer to 6 18 958 Enter Programming Mode Refer to 6 19 959 Exit...

Page 40: ...press two beeps sound The STAY AWAY and FAULT indicators flash One or more zone indicators 1 8 light to indicate the type of fault that occurred 6 4 View date and time This function allows user code holder to view the date and time 1 Enter your code 3 and press Two beeps sound the STAY and AWAY indicators flash and date time is shown in the format YYMMDD HHMM 2 If operation is not carried out with...

Page 41: ...ence The alarm memory is played back in this order Table 6 2 Event Memory Playback Sequnece indication Event 1 All indicators off System disarmed 2 Zone 4 and AWAY indicators light Alarm in Zone 4 3 Zone 3 and AWAY indicators light Alarm in Zone 3 4 AWAY indicator lights System armed in AWAY Mode Each event is indicated by a beep and a lit indicator Resetting a disarmed 24 Hour Alarm is indicated ...

Page 42: ...ne is not programmed as bypass zone then it cannot be bypassed manually as bypass zone For example you might want to isolate a zone before arming the system because a zone passive infrared PIR detector is activating false alarms or because you need to leave a pet inside a particular zone while you are away Key switch zone can t be bypassed The non used zone can t be bypassed Alarm Zone bypass 1 Zo...

Page 43: ...idual codes 1 Enter your Code 99 and press Two beeps sound and the STAY and AWAY indicators flash 2 Enter the new code and press Two beeps sound and the STAY and AWAY indicators are extinguished 6 15 Setting date and time This function allows installer code holder to set or view the date and time 1 Enter your installer code 955 and press Two beeps sound the STAY and AWAY indicators flash and date ...

Page 44: ...Y and AWAY indicators are extinguished 4 Repeat this procedure to delete other User Code 6 17 Add delete Radio User Codes This function allows Installer Code holder to add or delete a Remote Radio User Code if enabeled in location 182 To add or change a Remote Radio User Code 1 Enter your Installer Code 956 and press Two beeps sound and the STAY and AWAY indicators flash 2 Enter the number of the ...

Page 45: ...o program telephone number 9672 1777 enter Installer CODE 9 5 7 9 6 7 2 1 7 7 7 You can cancel the domestic dialing function at any time Such as you moved to other placesand do not want the system to dial your working phone number or mobile number any more To disable domestic dialing Enter the installer Code and press 957 then set the first number as 15 6 19 Enter Programming Mode This function al...

Page 46: ...eypad displays the data stored in Location 000 2 Enter 9 6 1 Two beeps and the system is reset to the factory default values 6 23 Command 962 Copy the control panel memory to the programming key This command copies the control panel memory to the programming key To copy the control panel memory to the programming key 1 Enter the installer code the default is 1234 958 and press to enter into Instal...

Page 47: ...and displays the panel software version 1 Enter 9 9 9 under installer s programming mode The keypad will display the first number 2 Press to display the next number Display example For the version 3 17 Enter 9 9 9 under the programming mode The keypad displays 1st number 3 and press to display the 2nd number 1 then press to display the 3rd number 7 Continue to press and no version number will be d...

Page 48: ...icate the ARM status Send the Battery Low report to the configured destinations of the control panel system if it occurred by the setting of location 140 Record the event in history AWAY ARM will monitor all zones except bypassed zones STAY ARM will only monitor the unsealed non interior zones Refer to Section 8 1 2 Zone programming page 57 for different processes with different zone types 7 2 Zon...

Page 49: ...our clients 7 4 2 Remote Connect with Customer Control If you want to configure the control panel to establish a remote connection it is possible only when the client initiates it through the remote keypad Program the following information Program the Call Back Telephone Number in Location 154 169 Start using remote program in Location 153 The control panel is now set ready for the client to contr...

Page 50: ... alarming The acknowledgement tone is the DTMF signal sent by the remote user with the If the control panel got the acknowledgement from the user it will send 2 seconds long beep as acknowledge tone and hang up the line 7 6 Reporting Formats 7 6 1 Transmission Formats The AMAX panel 2000 AMAX panel 2000 EN provides two kinds of transmission formats Contact ID and CFSK format for its dialing and co...

Page 51: ...r on board dialers The dialers report to Receiver 1 to Receiver 4 by programming You can program each dialer with 4 separate telephone numbers IP addresses and ports reporting format type and subscriber ID number and internet communication options if necessary Example You can set up Dialer 1 to report to receiver 1 in CFSK Format and set up Dialer 2 Dialer 3 and Dialer 4 to report to a base statio...

Page 52: ...tact the monitoring station If the call is successful the relevant information is transmitted and the dialer returns to Standby Mode Contact your monitoring station for the correct telephone number IP Address before you program these locations 7 7 2 Other Network Programming Option Refer to Section 10 1 1 Receiver Parameters page 78 When the control panel tansmits a report in network the following...

Page 53: ...me between two retries is 15 seconds for the 1st retry to 4th retry and the retry interval time between two retries is 10 minutes for the 5th retry to 8th retry after the 8th retry the retry interval time between two retries is 60 minutes For all enabled destinations except domestic destinations the waiting time for next retry would be cleared to zero as long as there is a new report 2 Attempt Pri...

Page 54: ...g this count to an acceptable level has an effect only if Remote Arming and the Remote Upload Download are enabled Programming this location to 0 prevents the control panel from answering incoming calls regardless of any other programmed options 7 8 Access Codes This section describes the access codes used to assign privileges and access functions for User Code holders of the system There are two ...

Page 55: ...ns page 39 User Codes 1 to 8 can be one to four digits long Only User Codes 9 to 16 can be used as remote radio user codes Use User Code 17 to send report when arming disarming the system by key switch Use User Code 18 to send report when arming the system in AWAY Mode or STAY Mode by keypad single button Use User Code 19 to send report when remotely arming the system by telephone call Use User Co...

Page 56: ...On board Zone EOL 1 Single EOL If 24 zone tamper function is not detected each zone uses a single 2 2k ohm EOL The panel can detect the zone as short normal or open The detectors sensors will be connected between zone and COM terminal through EOL series connection open triggered or EOL parallel connection short triggered Figure 8 1 Open Triggered Figure 8 2 Short Triggered The panel sets the short...

Page 57: ...w the zone operates the zone options and the reporting information for the zone Zone Operating Information These three locations store the Zone Type for example Enter Exit of Delay Instant or 24 Hour Zone Zone Options These two locations allow you to select from a number of options Refer to Section 8 1 4 Zone Bypass page 62 for more information Zone Reporting Information This information includes ...

Page 58: ... Zone disarm status 2 AWAY Arm same as the Instant Zone AWAY Arm status 3 STAY Arm This Zone will be Ignored and performed as disarm Refer to Section Keypad Indicators page 20 to see how the zone is displayed during exit time When Zone is triggered not bypassed and system is forced to arm a Zone fault report is send When System is disarmed and zone is not restored before a Zone fault restore repor...

Page 59: ... two or more zones programmed as delay zones and both are triggered thefollower zone will follow the first triggered delay zone 3 STAY ARM same as the delay zone When System is disarmed and zone is not restored before a Zone restore report is sent 6 Interior follower The interior follower zone will perform as below 1 Disarm same as the Instant Zone disarm status 2 AWAY Arm same as the Follower Zon...

Page 60: ...arm report Zone triggered during entry time Alarm report 3 STAY Arm Same as AWAY Arm performance A Fire zone does not send a restore report until the zone is restored 10 External Fault Zone The Fault Zone Input will perform as below 1 Disarm Zone normal no Alarm no report Zone triggered Alarm report 2 AWAY Arm Zone normal no Alarm no report Zone triggered Alarm report Zone triggered during exit ti...

Page 61: ...eport sent is by User Code 17 13 Key switch on off If a zone is programmed as key switch On Off it will ignore all other programming items such as bypass forcing arm If the Zone Tamper function is enabled the zone will process as a zone tamper When a zone is programmed for key switch arming then that zone is the input for a On Off keyswitch input In On Off mode the control will arm when the zone i...

Page 62: ...ully if the zone is still triggered after the exit time is up a trouble event will be sent 3 The zone restore report will be sent when the trouble zone is restored Exception case for force arming Telephone and RPS remote arming If using telephone and RPS remote arming as arm operation the system will ignore the force arm programming It will ARM without checking the characters of force arming 8 1 6...

Page 63: ...operates when the zone fails The fault is reset when the zone is restored The zone fault occurs on any below condition 1 24 hour and instant zone if force arm enabled and not ready at arm operation generate a zone trouble event 2 When the zone is locked out 3 Delay and follower zone if force arm enabled and not ready at exit delay timer expired generate a zone trouble event 4 24 hour zone if it is...

Page 64: ...s starting it will follow the Arm disarm status before the last time the panel power was down reset Quick arming starts AC MAINS Fault Report is followed with other report or one hour delayed to send out When AC MAINS is lost and battery is lower than 9VDC or Aux power keypad power and battery voltage are lower than 9V 5 the system will not send out the report to a remote receiver When one of the ...

Page 65: ...pad Tamper restore 137 3 1 2 02 System status Enclosure Tamper 137 1 17 01 System status Enclosure Tamper restore 137 3 17 02 System status Zone Bypass 570 1 Zone1 8 03 System status Zone Bypass restore 570 3 Zone1 8 04 Zone Restore Zone External Fault 150 1 Zone1 8 01 System status Zone External Fault restore 150 3 Zone1 8 02 System status Disarm AWAY 401 1 User0 20 06 Arm Disarm Arm AWAY 401 3 U...

Page 66: ...30 1 4 0E System status DX4020 G restore 330 3 4 0F System status Code Retry Limit exceeded 421 1 0 0EF7 System status Communication fail 350 1 Destination 1 4 0EF7 System status Communication restore 350 3 Destination 1 4 0FF7 System status Telephone IP test report 602 1 0 0900 CFG Test Config changed 306 1 0 050C System status Warning Device short 324 1 1 2 0112 System status Warning Device disc...

Page 67: ...AY Mode If a non 24 Hour zone is not restored when the system is disarmed the system automatically sends a Zone Restore Report for that zone All 24 Hour zones send a Zone Restore Report only when the zone is restored Zone Status Arm Disarm Report A Disarm Report is sent to the base station destination when the system is disarmed from STAY AWAY Mode An Arm Report is sent at the end of Exit Time whe...

Page 68: ...ttery Restore Report A Low battery restore report is sent when the Battery comes to normal and fault is reset System Status Access Denied Code Retry An Access Denied Report is sent to the base station destination when the number of incorrect code attempts equals the number programmed Restore reports are sent when fault is reset The Code Retries feature restricts the number of times an invalid User...

Page 69: ... Back Mode at anytime 8 4 Output Process The AMAX panel 2000 AMAX panel 2000 EN Control Panel has three outputs on the main board and 8 outputs on the DX3010 relay module The Output 1 is used as Siren alarm During the alarm duration the system can reset the alarm by command reset The other outputs can be programmed to follow up different events 8 4 1 Output Events Option 0 No output activate for t...

Page 70: ...y Warning This output operates during Exit Time when the control panel is armed The output is reset 1 When the system is disarmed 2 When Exit Time expires 3 When the output programmed duration is up If this duration is programmed as 000 the output will continue till the delay warning duration is up 5 Telephone Line Fail This output operates when a telephone line fault occurs The output is reset 1 ...

Page 71: ...the Tamper condition is Restored and Tamper is reset 10 External Fault This output operates when an External Fault occurs The output is reset 1 When the output programmed duration is up lf this duration is programmed as 000 the output will continue till the External Fault is Restored and the fault is reset 11 All Faults This output operates when a Fault occurs The output is reset 1 When the output...

Page 72: ...s used to activate the alarming When the keypad buzzer is default then there is no output in an alarm 8 4 5 Optional Relay Output There is one optional relay output controlled connector The programming character is the same as on board OC 2 output The default programming data is DISABLED 8 4 6 On board LED Indicator The red LED indicator on the main printed circuit board indicate the system status...

Page 73: ... pieces of equipment enhance certain features to make the system extremely flexible 8 6 1 RE012 E 2 Channel Hand Held Keyfob 433 MHz This hand held radio keyfob RE012 E operates the system remotely Cooperating with WE800E the keyfob can remotely arm and disarm the system 8 6 2 WE800E 433 MHz RF Receiver This interface allolws the use of up to eight radio User Codes 9 16 This is useful if you want ...

Page 74: ...S DX4020G as below Figure 8 5 DX4020 Location Setting ITS DX4020G is configured by connecting with the PC Refer to ITS DX4020G manual for more information 8 6 7 IUI AMAX LED8 8 Zone LED Keypad This keypad operates with the AMAX panel 2000 AMAX panel 2000 EN control panel It provides indications for up to eight zones The AMAX panel 2000 AMAX panel 2000 EN support a maxmium of two keypad To use the ...

Page 75: ...utputs PO Onboard OC 1 supervised output max 500mA OC 2 supervised output max 500mA OC 3 max 100mA Auxiliary module DX3010 Relay 1 8 Contacts rated 5A at 28VDC Cable requirements Unshielded and shielded 0 6 0 8mm Number of Users 16 8 8Keyfob Key Fobs 8 Events 254 history events stamped with time and date 254 EN history events stamped with time and date Pin Code variations 10000 DX 3010 1 B 420 or ...

Page 76: ...geable Low battery condition is below 11 8 VDC Minimum battery condition is 10 8VDC Maximum auxiliary current to recharge standby battery to 80 within 72h 12 V 7 Ah Battery 550mA Certification EN 50131 3 GRADE 2 ENV II ENVIRONMENTAL GRADE II Keypads IUI AMAX LED8 8Zone LED Keypad Relative Humidity 10 95 Operating Temperature 10 C 55 C Input Voltage range 10VDC 14VDC Current Consumption standby 24m...

Page 77: ...13 5 VDC 3 5 at AC power 10 VDC 13 7 VDC only battery power the Maximum rated current is 500 mA with overload and short circuit protection function R B G Y The group of terminals is OPTION bus interface terminals connect with the external option bus module such as IUI AMAX LED LCD keypad DX3010 module R is power and B is power G is data out and Y is data in R and B can be regarded as another indep...

Page 78: ... Receiver 1 001 999 Minutes 027 029 001 Telephone Number IP Address and Port for Receiver 2 030 046 15 Subscriber ID Number for Receiver 2 047 052 000000 Transmission Format for Receiver 2 0 Not used 1 Contact ID 2 CFSK 3 Bosch Network 053 1 Anti replay for Receiver 2 0 Disable 1 Enable 054 1 Acknowledge Wait Time for Receiver 2 05 99 seconds 055 056 05 Pulse Interval Time for Receiver 2 001 999 M...

Page 79: ...cation 120 135 Default 15 Enter 15 as the first digit is to disable the function EN 15 Digit Programming Key Digit Programming Key 0 0 8 8 1 1 9 9 2 2 11 3 3 12 4 4 4 Sec Pause 13 5 5 15 15 6 6 7 7 Location 137 144 Location Default Zone Restore Report Options Alarm restore fault restore bypass restore 137 0 Arm Disarm report option in AWAY Mode 138 6 Arm Disarm report option in STAY Mode 139 6 Sys...

Page 80: ...NOTICE The system sends no report when programmed to report to the receiver as Option 0 Location 145 150 Default 145 146 timer test report 1 99 hours 0 don t send timer test report 24 EN 1 24 147 148 Report time Hours 0 23 else don t send real time test report 99 149 150 Report time minutes 0 59 else don t send real time test report 99 Location 152 Location Default 0 Panel does not answer 1 15 Num...

Page 81: ...nitor 10 3 14 OC2 Warning Device 2 Monitor 10 3 15 Phone line Monitor Location 179 Location Default 1 15 attempt times 0 no lockout 179 6 EN 10 Location 180 Location Default 0 Disable 1 Enable 180 1 EN 0 Location 181 Location Default 0 Disable 1 Enable 181 1 EN 0 Location 182 Location Default 0 Disable 1 Enable 182 1 EN 0 Location 183 Location Default 0 Disable 1 Enable 183 1 EN 0 Location 184 Loc...

Page 82: ... Bypass Disable 0 Enable 1 211 1 Forced Arming Disable 0 Enable 1 212 1 EN 0 Silent Alarm Enable 1 Disable 0 213 0 EN 0 Zone alarm lock out time Disable 0 1 times 1 3 times 2 6 times 3 alarm duration 4 214 0 Support Detector Tamper Disable 0 Enable 1 215 1 Zone alarm report Refer to zone report option 216 6 EN 1 5 6 7 Zone Chime Mode Enable 1 Disable 0 217 0 Reserved 218 219 0 Zone 02 Zone Type Re...

Page 83: ...isable 0 Enable 1 242 1 EN 0 Silent Alarm Enable 1 Disable 0 243 0 EN 0 Zone alarm lock out time disable 0 1 times 1 3 times 2 6 times 3 alarm duration 4 244 0 Support Detector Tamper Disable 0 Enable 1 245 1 Zone alarm report Refer to zone report option 246 6 EN 1 5 6 7 Zone Chime Mode Enable 1 Disable 0 247 0 Reserved 248 249 0 Zone 05 Zone Type Refer to zone type option 250 1 Zone Bypass Disabl...

Page 84: ...N 0 Zone alarm lock out time disable 0 1 times 1 3 times 2 6 times 3 alarm duration 4 274 0 Support Detector Tamper Disable 0 Enable 1 275 1 Zone alarm report Refer to zone report option 276 6 EN 1 5 6 7 Zone Chime Mode Enable 1 Disable 0 277 0 Reserved 278 279 0 Zone 08 Zone Type Refer to zone type option 280 1 Zone Bypass Disable 0 Enable 1 281 1 Forced Arming Disable 0 Enable 1 282 1 EN 0 Silen...

Page 85: ...le 370 0 Output 1 Location Default Event type fixed value 3 EN Polarity Mode 0 Steady 1 Pulse 371 0 EN 0 Output Duration 001 999sec 000 on 372 374 000 EN 180 NOTICE When the triggered zone is programmed as silent zone keypad output and OC1 output do not response Other outputs are as normal Output 2 Location Default Event type Refer to output events option 375 3 EN 3 Polarity Mode 0 Steady 1 Pulse ...

Page 86: ...01 999sec 000 on 397 399 030 Relay Output 4 Event Type Refer to output events option 400 0 Polarity Mode 0 Steady 1 Pulse 401 0 Output Duration 001 999sec 000 on 402 404 030 Relay Output 5 Event Type Refer to output events option 405 0 Polarity Mode 0 Steady 1 Pulse 406 0 Output Duration 001 999sec 000 on 407 409 030 Relay Output 6 Event Type Refer to output events option 410 0 Polarity Mode 0 Ste...

Page 87: ...ller Code is used to program the system 10 6 2 User Codes Event Type Description 0 No output activate for the events 1 System Disarmed 2 System Armed 3 System Alarm 4 Entry Exit Delay Warning 5 Telephone Line Fail 6 AC Lost 7 Battery Low 8 RF Power Fault 9 TAMPER 10 External Fault 11 All Faults 12 Away armed 13 Stay armed 14 Reset 15 24h Alarm Location 425 428 Location Default Installer code 0 425...

Page 88: ... Manual Bosch Sicherheitssysteme GmbH User 07 460 464 15 User 08 465 469 15 RF User 09 470 474 15 EN 15 RF User 10 475 479 15 EN 15 RF User 11 480 484 15 EN 15 RF User 12 485 489 15 EN 15 RF User 13 490 494 15 EN 15 RF User 14 495 499 15 EN 15 RF User 15 500 504 15 EN 15 RF User 16 505 509 15 EN 15 ...

Page 89: ... be operated in disarming state Installer is not enabled from User No indication on on board LED AC Mains power or the battery is failed Restore the power The board is damaged Change a new one Zone Leds are always on Check that the zones are correctly connected Check that the sensors work normally Check that the EOL resistor is correctly connected with the sensor Fault Led is always on flashing Ti...

Page 90: ...oes not dial Check if the dialing function is switched off in communication programming Telephone number and transmission format need to be programmed No remote arming function Check if the function is switched off Do not set Location 152 and 153 as 0 No RPS software function Check if the function is switched off Do not set Location 152 and 153 as 0 Abnormal in PSTN Domestic dialling communicaiton...

Page 91: ......

Page 92: ...Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany www boschsecurity com Bosch Sicherheitssysteme GmbH 2011 ...