PRODUCT INFORMATION

PI−34.53

Page 

1

BDL−F.01U.066.176

A2.en/ 11.04.2007

ST−FIR/PRM1/sib

LSN − Non−Automatic Fire Detector Series 210

FMC−210−DM−G−R / FMC−210−DM−H−R

FMC−210−DM−G−B / FMC−210−DM−H−B / FMC−210−DM−G−Y

FMC−210−EST−G−B

FMC−210−SM−G−B / FMC−210−SM−G−R

Summary of Contents for 210 Series

Page 1: ...4 53 Page 1 BDL F 01U 066 176 A2 en 11 04 2007 ST FIR PRM1 sib LSN Non Automatic Fire Detector Series 210 FMC 210 DM G R FMC 210 DM H R FMC 210 DM G B FMC 210 DM H B FMC 210 DM G Y FMC 210 EST G B FMC 210 SM G B FMC 210 SM G R ...

Page 2: ...Page 2 of 17 BDL F 01U 066 176 A2 en 11 04 2007 ST FIR PRM1 sib ...

Page 3: ...contents 7 4 1 Basic model 7 4 2 Labelling foils 7 4 3 Accessories Spare parts 7 5 Device structure 8 6 Functional description 9 6 1 Manual call point 9 6 2 Single action call point 9 6 3 Functional test 9 7 Installation 9 7 1 Installation dimensions view housing rear wall interior 10 7 2 Cable duct 10 7 3 Installation variants for fire hose cabinets 11 7 4 Connection 12 7 5 Addressing 13 8 Notes ...

Page 4: ...ll point for interior areas Form G blue FMC 210 SM G R Single action call point for interior areas Form G red 2 Features Manual call point and stop device Trigger alarm by pushing the button After alarm triggering the push button is adjusted Single action call point Trigger alarm by breaking the glass pane Automatic or manual addressing is possible via the rotary switch Detector query routines wit...

Page 5: ...s e g exits passageways stairwells and be easily accessible An installation height of 1400 mm 200 mm measured from the middle of the push button to the floor must be maintained Non automatic fire detectors must be sufficiently lit with sunlight or another light source including emergency lighting if present The distance between non automatic fire detectors should not exceed 100 m according to DIN ...

Page 6: ...els The line voltage Umax must not exceed 33 V The maximum current Imax must be limited to 130 mA Fire detector cable Only fire detector cables that conform to DIN VDE 0814 may be used The total cable capacity Cmax must not exceed 1 mF The total cable inductivity Lmax must not exceed 0 01 H The cable type J Y ST Y08 in accordance with DIN VDE 0815 table 10 has a capacity of 120 hF at a length of 1...

Page 7: ...G blue F01U027317 Pc FMC 210 SM G B Single action call point for interior areas Form G blue F01U011962 Pc FMC 210 SM G R Single action call point for interior areas Form G red 4 2 Labelling foils Product ID DU Designation F 01U 012 951 PAK FMC FST DE Pre cut and labelled foil sets for the top labelling field 1 PACK 5 sheets with 12 labelling variants F 01U 033 169 PAK FMX FSO LSN Pre cut foil sets...

Page 8: ...cts interchangeable for cable inlet and outlet The cable can also be ducted through openings in the rear wall of the housing 3 Connection terminal strip 4 Detector door with replaceable glass pane hidden lock and seal for Form H 5 Glass pane 6 Display LED 7 PC board with protective coating for Form H The PC board is clipped onto the floor of the housing 8 Trigger mechanism clipped onto the PC boar...

Page 9: ...d the display LED 4 flashes After a new glass pane 2 has been inserted the call point 3 is reset by opening the detector doors 1 6 3 Functional test Manual call point and stop device To trigger the alarm press the manual call point 3 hard The display LED 4 flashes Use the reset lever 5 to return the manual call point to the starting status Single action call point To trigger the alarm open the det...

Page 10: ... ST FIR PRM1 sib 7 1 Installation dimensions view housing rear wall interior ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ 60 mm 135 mm 37 mm 135 mm approx 38 mm 17 mm 13 mm 7 2 Cable duct Surface mounted cable duct Flush mounted cable duct via concealed box ...

Page 11: ...b 7 3 Installation variants for fire hose cabinets 135 140 2 5 mm 1 12 5 2 149 5 139 2 3 Pos Description 1 Installation depth version 1 min 39 mm 2 Installation depth version 2 14 mm 3 Installation depth version 3 approx 30 mm With this version it is not necessary to open the door of the hose box e g for maintenance ...

Page 12: ...f 17 BDL F 01U 066 176 A2 en 11 04 2007 ST FIR PRM1 sib 7 4 Connection U 0 V a b a b LSN1 LSN2 3 E 2 1 4 Pos Description Connector 1 U 0 V For execution of the external power supply 2 a b LSN1 LSN in 3 a b LSN2 LSN out 4 E Earth connection for the cable shielding ...

Page 13: ...g modes at the same time Address Mode 0 0 0 Loop stub in LSN improved mode with automatic addressing T branches not possible 001 254 Loop stub T branches in LSN improved mode with manual addressing CL 0 0 Loop stub in Classic LSN mode Mode XXX XXX XXX FPA 5000 BZ 500LSN UEZ 2000 LSN UGM 2020 CL 00 000 255 299 001 254 If LSN improved version elements are used in conjunction with the FPA 5000 unshie...

Page 14: ...cations Technische gegevens Operating voltage 24 V DC 15 V DC to 33 V DC Current consumption 0 4 mA Protection category as per EN 60529 Form H exterior Form G interior IP 54 IP 52 Permissible ambient temperature Form H exterior Form G interior 25 C to 70 C 13 F to 158 F 10 C to 55 C 14 F to 131 F Standard except FMC 210 DM G Y EN 54 11 Standard for FMC 210 DM G Y EN 12094 3 Colours RAL 5005 signal...

Page 15: ...l BM Fire detector DIN German Institute for Standardization DM Manual call point EMZ Intrusion control panel EN European standard GMZ Danger detection system KI Customer service information LED Light Emitting Diode LSN Local Security Network SM Single action call point UGM Universal danger detection system VDE Association of German Electrical Engineers VdS VdS Schadenverhütung GmbH ...

Page 16: ...PI 34 53 en Produktinformation FMC 210 DM SM EST LSN Page 16 of 17 BDL F 01U 066 176 A2 en 11 04 2007 ST FIR PRM1 sib 11 Notes ...

Page 17: ...Page 17 of 17 Bosch Sicherheitssysteme GmbH Robert Koch Straße 100 D 85521 Ottobrunn Germany www bosch sicherheitssysteme de info service de bosch com ...