PRODUCT INFORMATION

PI−34.51

Page 

1

BDL−F.01U.066.178

A2.en/ 11.04.2007

ST−FIR/PRM1/sib

GLT − Non−Automatic Fire Detector Series 120

FMC−120−DKM−G−R / FMC−120−DKM−H−R

FMC−120−DKM−G−B / FMC−120−DKM−H−B /

 FMC−120−DKM−G−Y

FMC−120−EST−G−B

Summary of Contents for 120 Series

Page 1: ...RMATION PI 34 51 Page 1 BDL F 01U 066 178 A2 en 11 04 2007 ST FIR PRM1 sib GLT Non Automatic Fire Detector Series 120 FMC 120 DKM G R FMC 120 DKM H R FMC 120 DKM G B FMC 120 DKM H B FMC 120 DKM G Y FMC 120 EST G B ...

Page 2: ...Page 2 of 18 BDL F 01U 066 178 A2 en 11 04 2007 ST FIR PRM1 sib ...

Page 3: ...ants 5 4 Order contents 6 4 1 Basic model 6 4 2 Labelling foils 6 4 3 Accessories Spare parts 6 5 Device structure 7 6 Functional description 8 6 1 Manual call point 8 6 2 Functional test 8 6 3 Test detector 8 7 Installation 9 7 1 Installation dimensions view housing rear wall interior 9 7 2 Cable duct 9 7 3 Installation variants for fire hose cabinets 10 7 4 Connection 11 8 Notes on maintenance a...

Page 4: ...xterior areas Form H blue D FMC 120 DKM G Y Manual call point for interior areas Form G yellow Stop device D FMC 120 EST G B Stop device for interior areas Form G blue 2 Features D Manual call point and stop device Trigger alarm by pushing the button After alarm triggering the push button is adjusted D Detector query routines with evaluation and multiple transmission D Display LED for triggered al...

Page 5: ...ing to VdS D In high risk areas non automatic fire detectors should be installed at intervals of max 40 m VDE 0833 Part 2 Point 7 2 6 3 1 Maximum number of detectors that may be connected In accordance with VdS guidelines a maximum of 10 non automatic fire detectors may be connected to a primary line The test detector can be used for primary lines with automatic fire detectors It is con nected to ...

Page 6: ...h fire panels BMZ D The line voltage Umax must not exceed 33 V D The maximum current Imax must be limited to 130 mA Fire detector cable D Only fire detector cables that conform to DIN VDE 0814 may be used D The total cable capacity Cmax must not exceed 1 F D The total cable inductivity Lmax must not exceed 0 01 H The cable type J Y ST Y08 in accordance with DIN VDE 0815 table 10 has a capacity of ...

Page 7: ...areas Form G yellow F01U012763 Pc FMC 120 EST G B Stop device for interior areas Form G blue 4 2 Labelling foils Product ID DU Designation F 01U 012 951 PAK FMC FST DE Pre cut and labelled foil sets for the top labelling field 1 PACK 5 sheets with 12 labelling variants F 01U 033 170 PAK FMX FSO GLT Pre cut foil sets for the top labelling field 1 PAK 10 sheets with 6 labelling variants Appropriate ...

Page 8: ...ts interchangeable for cable inlet and outlet The cable can also be ducted through openings in the rear wall of the housing 3 Connection terminal strip 4 Detector door with replaceable glass pane hidden lock and seal for Form H 5 Glass pane 6 Display LED 7 PC board with protective coating for Form H The PC board is clipped onto the floor of the housing 8 Trigger mechanism clipped onto the PC board...

Page 9: ...pressed push button is reset by manually activating the reset lever 5 or by opening the detector door 1 The alarm is reset and the display LED goes out 4 2 4 1 5 2 3 3 1 6 2 Functional test Manual call point and stop device To trigger the alarm press the manual call point 3 hard The display LED 4 flashes Use the reset lever 5 to return the manual call point to the starting status 6 3 Test detector...

Page 10: ...urface or flush mounted The cable ducting should be carried out using the intended openings in the housing see 7 2 Cable duct d The installation location is to be selected so that approximately 35 mm space remains free on the right hand side for opening the door 7 1 Installation dimensions view housing rear wall interior ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ÎÎÎÎÎÎ ...

Page 11: ...ib 7 3 Installation variants for fire hose cabinets 135 140 2 5 mm 1 10 2 147 139 2 3 Pos Description 1 Installation depth version 1 min 36 mm 2 Installation depth version 2 14 mm 3 Installation depth version 3 approx 30 mm With this version it is not necessary to open the door of the hose box e g for maintenance ...

Page 12: ...0 R4 R3 R5 R1 A B E G H K J C D F R1 A B 820 Ω R3 G H 0 Ω R4 E F 150 Ω R5 J K 0 Ω R2 E R6 R6 A B 2k21 Endmelder Last detector Laatste melder R2 C D RE 3k92 In order to reach an alarm resistance of 820 Ohm in current gain operation resistor R6 must be removed For other operating modes voltage reduc tion see the wiring diagram manual for the corresponding fire panel b 3 2 A B J K H G F E D C 10 8 9 ...

Page 13: ...in Germany these regulations refer to the maintenance intervals as per the manufac turer s instructions D Bosch ST recommends a functional and visual inspection at least once a year D Maintenance and inspection work should be carried out regularly and by trained personnel 8 1 Repair In the event of a defect the entire unit is exchanged 8 2 Disposal Unusable units should be disposed of in accordanc...

Page 14: ...n category as per EN 60529 Form H exterior Form G interior IP 54 IP 52 Permissible ambient temperature Form H exterior Form G interior 25_C to 70_C 13_F to 158_F 10_C to 55_C 14_F to 131_F Standard except FMC 120 DKM G Y EN 54 11 Standard for FMC 120 DKM G Y EN 12094 3 Colours RAL 5005 signal blue RAL 1003 signal yellow RAL 3001 signal red Housing material Plastic ASA Acrylonitrile Styrene Acrylat...

Page 15: ... BM Fire detector DIN German Institute for Standardisation DKM Manual call point EMZ Intrusion control panel EN European standard GMZ Danger detection system KI Customer service information LED Light Emitting Diode LSN Local Security Network SM Single action call point UGM Universal danger detection system VDE Association of German Electrical Engineers VdS VdS Schadenverhütung GmbH ...

Page 16: ...PI 34 51 en Produktinformation FMC 120 DKM EST GLT Page 16 of 18 BDL F 01U 066 178 A2 en 11 04 2007 ST FIR PRM1 sib 11 Notes ...

Page 17: ...Page 18 of 18 Bosch Sicherheitssysteme GmbH Robert Koch Straße 100 D 85521 Ottobrunn Germany www bosch sicherheitssysteme de info service de bosch com ...