background image

Montage Einspeiseblock, Einspeise element 

 

Fig. 1

Demontage Einspeiseblock, Einspeise element

Fig. 2

Montage der Hilfsklemmen LA und LB 
 Einspeiseblock

Fig. 3

Einspeisebeispiele

Fig. 4–10

Der IP Schutz muss durch den Errichter erstellt 
werden.

Montage sur les socles, Bloc d’alimen- 

F

 

tation, Elément d’alimentation

Fig. 1

Démontage, Bloc d’alimen tation, Elément 
 d’alimentation

Fig. 2

Montage des bornes auxiliaires LA et LB Bloc 
d’alimen tation

Fig. 3

Exemples d’alimentation

Fig. 4–10

La protection de la propriété intellectuelle doit 
être créé par l'installateur.

Assembly to plug-in socket system, 

G

 

Incoming Terminal Block standard,  
Incoming Terminal Block oversize

Fig. 1

Disconnection, Incoming Terminal Block 
 standard, Incoming Terminal Block oversize

Fig. 2

Assemble auxiliary terminals LA and LB Incoming 
Terminal Block  standard

Fig. 3

Supply variants

Fig. 4–10

La protection de la propriété intellectuelle doit 
être créé par l'installateur.

ABB Switzerland Ltd

Low Voltage Products

Fulachstrasse 150

CH-8201 Schaffhausen

Phone:  +41 58 586 41 11 

Fax: 

+41 58 586 42 22

www.abb.com

ABB Inc. 

8155 T&B Blvd. 

Memphis, TN 38125 

Technical Support: 

E-Mail: [email protected] 

Phone: 1-888-385-1221 Option 1

U L   d a t a

For all types: 
Feeder Blocks cat. nos. ZLS250 – ZLS253,   ZLS954UL, ZLS959UL are suitable for use in feeder circuits up to 600 V

Wire required to be fixed 2 inches (50.0 mm) below entry point of component housing by suitable cable ties
Rated Voltage:

600 V AC

Rated Current (side feed, left or right):

125 A

Rated Current (center feed):

250 A max. when used with two feeder blocks

Short Circuit Rating:

50 kA, max. 480 VAC and 480 Y/277 V and 240 VAC

Short Circuit Protection:

150 A Fuse or Circuit-Breaker (DIVQ/7) with maximum rating 
of 250 A, located at Line Side

Torque: 

2.0 Nm

Stripping length:

21 mm

Wire size:

2 AWG - 1/0 AWG

Wire rated min. 600 V and 75 °C (AVLV2/8)

For all types: 
Feeder Blocks cat. nos. ZLS224, ZLS224R, ZLS225 and ZLS225R are suitable for use in feeder circuits up to 250 V

Rated Voltage:

250 V AC

Rated Current (side feed, left or right):

125 A

Rated Current (center feed):

250 A max. when used with two feeder blocks

Short Circuit Rating:

50 kA, max. 240 VAC

Short Circuit Protection:

150 A Fuse or Circuit-Breaker (DIVQ/7) with maximum rating 
of 250 A, located at Line Side

Torque: 

4.0 Nm

Stripping length:

18 mm

Wire size:

10 AWG - 1/0 AWG

Wire rated min. 600 V and 75 °C (AVLV2/8)

1

max. 125 A (UL+IEC)

max. 125 A

max. 125 A

max. 150 A (UL)

max. 160 A (IEC)

1

2

> 30°

max. 125 A

max. 125 A

max. 150 A (UL)

max. 200 A (IEC)

max. 125 A

max. 125 A

max. 250 A (UL+IEC), same cable length

max. 125 A

max. 125 A

max. 250 A (UL+IEC)

max. 125 A

max. 125 A

1

2

4

5

3

max. 125 A (UL)

7

max. 125 A

max. 125 A

max. 250 A (UL+IEC)

max. 125 A

max. 125 A

10

6

9

8

Reviews: