background image

RTU560 

Connections and Settings  
Communication Unit 560CMD11 

 

Doc.-No.: 1KGT 150 765 V005 1 

 

 

Application,  characteristics  and  technical  data 
have to be taken from the hardware data sheet: 

 

560CMD11 R0001 

1KGT 150 764 V0011 

560CMD11 R0011 

1KGT 150 764 V0011 

Operation 

The Communication Unit 560CMD11 is one of the 
CMU  boards  (CMU  =  communication  unit)  of  the 
remote  terminal  unit  RTU560.  The  560CMD11 
controls process events and communications with 
control  centers  and  local  MMI  systems  via  up  to 
four serial Interfaces (CP1, CP2, CPA, CPB), two 
Ethernet  10BaseT/100BaseT  LAN  Interfaces  (E1, 
E2) and an integrated GPRS modem. 

 

Fig. 1:  Block diagram 560CMD11 

To force the IP-Address to a default value at start-
up, the “Def. IP-Addr” switch on the front side (see 
Fig. 

8) 

has 

to 

be 

switched 

“ON”.  

The 560CMD11 starts with the factory settings for 
the  Ethernet  Interface  (see  Fig.  2)  which  are 
192.168.0.1 for the IP-address with the network 

setting  255.255.255.0  for  the  subnet  mask  and 
192.168.0.20 for the gateway. 

Switch

„Def. IP- Address“

position

?

OFF

E

Read IP address

from confi-

guration file

ON

Set Switch

„Def. IP-Address“

to 

„OFF“

Send Configuration

to RTU 192.168.0.1

Switch

„Def. IP- Address“

position

?

OFF

E

Read IP address

from confi-

guration file

ON

Set Switch

„Def. IP-Address“

to 

„OFF“

Send Configuration

to RTU 192.168.0.1

 

        

Fig. 2: Use Switch „Def. IP-Addr“ 

Serial Interface 

The  serial  interfaces  (CP1,  CP2,  CPA  and  CPB) 
are  available  on  the  RJ45  connector  on  the  front 
plate. It can interface RS485 (Tab. 1) or RS232C 
(Tab. 2) signals.  

 

Serial Interfaces RS485 Mode 

Pin 

Signal 

 

 

 

 

 

RJ45

1

8

Rx

Tx

RJ45

1

8

RJ45

1

8

Rx

Tx

 

 Jack 

Not used 

TA 

Data - 

TB 

Data + 

Not used 

GND 

Signal Ground 

Not used 

Table 1: Serial Interfaces RS485 Mode 

Summary of Contents for RTU560

Page 1: ...8 has to be switched ON The 560CMD11 starts with the factory settings for the Ethernet Interface see Fig 2 which are 192 168 0 1 for the IP address with the network setting 255 255 255 0 for the subnet mask and 192 168 0 20 for the gateway Switch Def IP Address position OFF E Read IP address from confi guration file ON Set Switch Def IP Address to OFF Send Configuration to RTU 192 168 0 1 Switch D...

Page 2: ...er based protocols GPRS Modem Interface Both functions are mutually exclusive GPRS Modem only R0011 The settings have to be done by the RTUtil560 configuration tool The 560CMD11 R0011 provides a radio interface via an integrated Quad Band GSM GPRS mo dem For communication via the GSM GPRS mo dem a pluggable SIM Card is necessary The SIM Card socket is placed below the Com pactFlash socket The Quad...

Page 3: ...is 24VDC The connector consists of a 3 pole pluggable screw terminal 5 08mm see Tab 4 and Fig 8 or Fig 11 The max input power is 67 Watt In some cases an external potential isolation for the DC Input is neces sary This can be done e g by a power supply unit 560PSU40 41 Power Supply DC Out The 560CMD11 provides 24VDC output power for max 0 5A The connector consists of a 3 pole pluggable screw termi...

Page 4: ...onal galvanic isolated RS232 interface see Fig 5 if the entire system is grounded positively Signaling The red LED of the 560CMD11 is controlled by the RTU560 firmware For the definition and oper ation of the LED ERR please refer to the release specific function description The connector em bedded LEDs Tx and Rx are directly connected to the receiver transmitter of the communication line The LEDs ...

Page 5: ...on Unit 560CMD11 Doc No 1KGT 150 765 V005 1 5 Fig 4 Negative System Earthing Fig 5 Positive System Earthing power supply System 560CMD11 GPRS Chip RS232 560PSU40 41 RS232 galvanic isolated power supply System 560CMD11 GPRS Chip RS232 560PSU40 41 ...

Page 6: ... see Fig 8 and Fig 11 4 Pull or plug only the CF card Don t touch other components 5 Close the housing before the power supply is connected to the 560CMD11 SIM Card only R0011 For communication via the GSM GPRS modem a pluggable SIM Card ID 000 is necessary For changing the SIM Card the right side of the housing has to be opened see Fig 11 1 Disconnect the power supply of the 560CMD11 2 Take care ...

Page 7: ... with collision avoidance TxD RxD DCD without handshake DNP 3 0 only The settings of the Ethernet Interface are Node name IP address Subnet mask Default gateway Routing information The number of the host Interface Fig 6 560ANA02 For the configuration procedure of the GPRS Modem only R0011 please refer to the function description part 6 The settings of the GPRS Modem are Local IP address Remote net...

Page 8: ...and Settings Communication Unit 560CMD11 Doc No 1KGT 150 765 V005 1 8 Fig 7 Top side of 560CMD11 R0001 housing screws screws Fig 8 Front and right side of 560CMD11 R0001 housing Fig 9 Bottom side of 560CMD11 R0001 housing ...

Page 9: ...ttings Communication Unit 560CMD11 Doc No 1KGT 150 765 V005 1 9 Ethernet Fig 10 Top side of 560CMD11 R0011 housing Fig 11 Front and right side of 560CMD11 R0011 housing screws screws Fig 12 Bottom side of 560CMD11 R0011 housing ...

Page 10: ...eed particulars shall prevail ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB...

Reviews: