Relion

®

 615 series

Voltage Protection and Control

REU615

DNP3 Point List Manual

Summary of Contents for REU615

Page 1: ...Relion 615 series Voltage Protection and Control REU615 DNP3 Point List Manual...

Page 2: ......

Page 3: ...Document ID 1MRS757056 Issued 2013 02 21 Revision C Product version 4 0 FP1 Copyright 2013 ABB All rights reserved...

Page 4: ...s document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All o...

Page 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Page 6: ...rning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN...

Page 7: ...xxx1 Controllable disconnector 1 16 CTRL Dxxxxx2 Controllable disconnector 2 17 CTRL Exxxxx1 Controllable earth switch 1 17 Sensors and monitoring functions 17 LD0 ARCSARC1 Fault arc protection stage...

Page 8: ...IPTOC1 Phase overcurrent protection instantaneous stage 1 25 LD0 PHLPTOC1 Phase overcurrent protection low stage 1 25 LD0 PHPTOV1 Phase overvoltage protection stage 1 25 LD0 PHPTOV2 Phase overvoltage...

Page 9: ...O 32 LD0 XGGIO110 Physical I O 32 LD0 XGGIO130 Physical I O 32 Binary outputs 33 System functions 33 LD0 LLN0 LPHD1 Reset indications and LEDs reset device 33 LD0 DNPGGIO1 Parameter setting group con...

Page 10: ...DCXSWI1 Controllable disconnector 1 4 pole 2 bit position values 41 CTRL DCXSWI2 Controllable disconnector 2 4 pole 2 bit position values 41 CTRL ESSXSWI1 Earth switch 1 4 pole 2 bit position values 4...

Page 11: ...45 DR RDRE1 Disturbance recorder values 45 LD0 SECRSYN1 Synchrocheck line and bus state 45 Generic functions 46 LD0 XRGGIO130 RTD inputs 46 Section 3 DNP3 protocol implementation 47 DNP3 device profil...

Page 12: ...6...

Page 13: ...be used to find out when and for what purpose a typical protection function can be used The manual can also be used when calculating settings The communication protocol manual describes a communicatio...

Page 14: ...the data points specific to the IED The manual should be used in conjunction with the corresponding communication protocol manual The technical manual contains application and functionality descripti...

Page 15: ...ution notices 1 4 2 Document conventions A particular convention may not be used in this manual Abbreviations and acronyms in this manual are spelled out in the glossary The glossary also contains def...

Page 16: ...phase overvoltage protection PHPTOV1 3U 1 59 1 PHPTOV2 3U 2 59 2 PHPTOV3 3U 3 59 3 Positive sequence undervoltage protection PSPTUV1 U1 1 47U 1 PSPTUV2 U1 2 47U 2 Negative sequence overvoltage protec...

Page 17: ...SWI1 I O ES 1 I O ES 1 ESSXSWI2 I O ES 2 I O ES 2 Tap changer position indication TPOSSLTC1 TPOSM 84M Tap changer control with voltage regulator OLATCC1 COLTC 90V Synchronism and energizing check SECR...

Page 18: ...12...

Page 19: ...class assignments are Class 0 and Class 1 for binary inputs and Class 0 and Class 2 for analog inputs These assignments can be modified later Analog values are provided with default scalings The scali...

Page 20: ...o ARCSARC3 o MAPGAPC1 o MAPGAPC2 o MAPGAPC3 o MAPGAPC4 o MAPGAPC5 o MAPGAPC6 o LSHDPFRQ1 LSHDPFRQ2 LSHDPFRQ3 LSHDPFRQ4 LSHDPFRQ5 CBXCBR1 DCXSWI1 DCXSWI2 ESXSWI1 DCSXSWI1 DCSXSWI2 DCSXSWI3 ESSXSWI1 ES...

Page 21: ...Data Object Data Attribute Logical Node is the same as the application function block name SA name The signal may have a defined label that is visible for example in ACT Description Short description...

Page 22: ...CB selected 1 Selected CTRL CBXCBR1 BlkCls stVal BLK_CLOSE Close blocked 1 Blocked BlkOpn stVal BLK_OPEN Open blocked 1 Blocked CTRL CCBRBRF1 OpEx general TRBU Failure ext trip 1 Failure OpIn general...

Page 23: ...earth switch 1 IEC 61850 name SA name Description Values CTRL ESCILO1 EnaCls stVal ENA_CLOSE Close enabled 1 Enabled EnaOpn stVal ENA_OPEN Open enabled 1 Enabled ItlByPss stVal ITL_BYPASS Interlockin...

Page 24: ...ion Values LD0 ARCSARC31 FADet stVal ARC_FLT_DET Arc detected 1 Detected LD0 ARCPTRC31 Op general OPERATE Operate 1 Operate 2 3 3 4 LD0 TCSSCBR1 Trip circuit supervision 1 Table 13 LD0 TCSSCBR1 Trip c...

Page 25: ...Val BLKD_I_CIR High circulating current block 1 Block LTCBlkSt stVal BLKD_LTCBLK External blocking 1 Block ErrParTra stVal PAR_FAIL Parallel failure detected 1 Failure 2 3 5 Metering and measurand fun...

Page 26: ...ARN High warning 1 Warning 2 3 6 Protection functions 2 3 6 1 LD0 LEDPTRC1 Global protection signals Table 20 LD0 LEDPTRC1 Global protection signals IEC 61850 name SA name Description Values LD0 LEDPT...

Page 27: ...uency gradient Op general OPR_FRG Operate 1 Operate 2 3 6 5 LD0 FRPFRQ2 Frequency protection 2 Table 24 LD0 FRPFRQ2 Frequency protection 2 IEC 61850 name SA name Description Values LD0 FRPTRC2 Str gen...

Page 28: ...requency gradient Op general OPR_FRG Operate 1 Operate 2 3 6 8 LD0 FRPFRQ5 Frequency protection 5 Table 27 LD0 FRPFRQ5 Frequency protection 5 IEC 61850 name SA name Description Values LD0 FRPTRC5 Str...

Page 29: ...rt 2 3 6 11 LD0 LSHDPFRQ2 Load shedding instance 2 Table 30 LD0 LSHDPFRQ2 Load shedding instance 2 IEC 61850 name SA name Description Values LD0 LSHDPTRC2 Op general OPERATE Stage operate 1 Operate St...

Page 30: ...RT Stage start 1 Start RestLodOp general RESTORE Restore the load 1 Restore RestLodStr general ST_REST Start of restore 1 Start 2 3 6 15 LD0 NSPTOV1 Negative sequence overvoltage protection stage 1 Ta...

Page 31: ...ection low stage 1 Table 38 LD0 PHLPTOC1 Phase overcurrent protection low stage 1 IEC 61850 name SA name Description Values LD0 PHLPTOC1 Op general OPERATE Stage operate 1 Operate Str general START St...

Page 32: ...PTUV2 Phase undervoltage protection stage 2 IEC 61850 name SA name Description Values LD0 PHPTUV2 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 6 25 LD0 PHPTUV3...

Page 33: ...Table 48 LD0 ROVPTOV2 Residual overvoltage protection 2 IEC 61850 name SA name Description Values LD0 ROVPTOV2 Op general OPERATE Stage 2 operate 1 Operate Str general START Stage 2 start 1 Start 2 3...

Page 34: ...general FUSEF_U General start 1 Start Str3Ph general FUSEF_3PH Three phase start 1 Start 2 3 7 3 DR RDRE1 Disturbance recorder Table 53 DR RDRE1 Disturbance recorder IEC 61850 name SA name Descriptio...

Page 35: ...nction 3 Table 57 LD0 MAPGAPC3 Multipurpose analog protection function 3 IEC 61850 name SA name Description Values LD0 MAPGAPC3 Op general OPERATE Stage operate 1 Operate Str general START Stage start...

Page 36: ...t 3 signal 0 1 Off On Q4 stVal Input 4 signal 0 1 Off On Q5 stVal Input 5 signal 0 1 Off On Q6 stVal Input 6 signal 0 1 Off On Q7 stVal Input 7 signal 0 1 Off On Q8 stVal Input 8 signal 0 1 Off On 2 3...

Page 37: ...state 0 1 Off On SPCS12 stVal Output 12 state 0 1 Off On SPCS13 stVal Output 13 state 0 1 Off On SPCS14 stVal Output 14 state 0 1 Off On SPCS15 stVal Output 15 state 0 1 Off On SPCS16 stVal Output 16...

Page 38: ...Val X110 Input 3 1 0 ON OFF Ind4 stVal X110 Input 4 1 0 ON OFF Ind5 stVal X110 Input 5 1 0 ON OFF Ind6 stVal X110 Input 6 1 0 ON OFF Ind7 stVal X110 Input 7 1 0 ON OFF Ind8 stVal X110 Input 8 1 0 ON O...

Page 39: ...or more details Type Output type Some outputs can only be controlled with value On Writing Off to these points does not affect the function of the output See DNP3 control relay output block parameters...

Page 40: ...SWI1 Controllable disconnector 1 control IEC 61850 name SA name Description Type CTRL DCCSWI1 Pos Oper ctlVal Disconnector control On Off 2 4 2 3 CTRL DCCSWI2 Controllable disconnector 2 control Table...

Page 41: ...al MAN_RESTORE Manual restore On BlkRest Oper ctlVal BLK_REST Cancel restore On 2 4 4 2 LD0 LSHDPFRQ2 Loadshedding controls 2 Table 78 LD0 LSHDPFRQ2 Loadshedding controls 2 IEC 61850 name SA name Desc...

Page 42: ...ecorder IEC 61850 name SA name Description Type DR RDRE1 MemClr Oper ctlVal Clear all records On RcdTrg Oper ctlVal Trig recording On 2 4 6 Generic functions 2 4 6 1 LD0 SPCGGIO1 Multipurpose binary o...

Page 43: ...1 Persistent type outputs can be written with both 1 and 0 values The persistent type is the same as the toggled mode on LHMI and WHMI Table 84 LD0 SPCGGIO2 Multipurpose binary outputs 2 IEC 61850 na...

Page 44: ...ip flop 1 On Rs2 ctlVal Reset flip flop 2 On Rs3 ctlVal Reset flip flop 3 On Rs4 ctlVal Reset flip flop 4 On Rs5 ctlVal Reset flip flop 5 On Rs6 ctlVal Reset flip flop 6 On Rs7 ctlVal Reset flip flop...

Page 45: ...LN0 LocRem stVal Off 0 Loc 1 Rem 2 Station 3 0 3 R 0 3 0 3 2 5 1 2 LD0 LPHD1 System values Table 89 LD0 LPHD1 System values IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 LPHD1 NumCmpChg...

Page 46: ...Alarm R 0 3 0 3 ISCSO9 stVal LED 9 state 0 1 3 Off Ok Alarm R 0 3 0 3 ISCSO10 stVal LED 10 state 0 1 3 Off Ok Alarm R 0 3 0 3 ISCSO11 stVal LED 11 state 0 1 3 Off Ok Alarm R 0 3 0 3 2 5 2 Switchgear...

Page 47: ...DCXSWI1 Controllable disconnector 1 4 pole 2 bit position values IEC 61850 name SA name Description Values S Arg 1 2 3 4 CTRL DCXSWI1 Pos stVal POSITION Intermediate 0 Off 1 On 2 Bad 3 0 3 R 0 3 0 3 2...

Page 48: ...ON Intermediate 0 Off 1 On 2 Bad 3 0 3 R 0 3 0 3 2 5 3 Sensors and monitoring functions 2 5 3 1 LD0 TPOSSLTC1 Tap changer position value Table 101 LD0 TPOSSLTC1 Tap changer position value IEC 61850 na...

Page 49: ...ence of currents Table 105 LD0 CSMSQI1 Sequence of currents IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 CSMSQI1 Sequence of currents SeqA c1 instCVal mag I1_INST Positive magnitude 0 0...

Page 50: ...eqV c2 cVal mag I2_DB Negative magnitude 0 00 4 00 xUn R 0 4 0 400 SeqV c3 cVal mag I3_DB Zero magnitude 0 00 4 00 xUn R 0 4 0 400 2 5 5 7 LD0 PEMMTR1 Power measurement and accumulated power values Ta...

Page 51: ...000 99999 TmpRl mag Relative temperature 0 99 9 R 0 99 9 0 999 2 5 7 Protection related functions 2 5 7 1 DR RDRE1 Disturbance recorder values Table 112 DR RDRE1 Disturbance recorder values IEC 61850...

Page 52: ...E4 1E4 1E4 AnIn3 instMag AI_VAL3 RTD input 3 10000 10000 R 1E4 1E4 1E4 1E4 AnIn4 instMag AI_VAL4 RTD input 4 10000 10000 R 1E4 1E4 1E4 1E4 AnIn5 instMag AI_VAL5 RTD input 5 10000 10000 R 1E4 1E4 1E4 1...

Page 53: ...s supported the complete list is described in the attached table For static non change event object requests request qualifier codes 07 and 08 limited quantity and 17 and 28 index are supported Static...

Page 54: ...ount 1 Count 1 is accepted but ignored Never Always Sometimes Configurable Pulse on Never Always Sometimes Configurable Pulse off Never Always Sometimes Configurable Latch on Never Always Sometimes Co...

Page 55: ...rt Append file mode Yes No Custom status code strings Yes No Permissions field Yes No File events assigned to class Yes No File events send immediately Yes No Multiple blocks in a fragment Yes No Max...

Page 56: ...unsol resp 17 28 index 2 21 Binary input change with time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 2 3 Binary input change with relative time 1 read 06 no r...

Page 57: ...p 17 28 index 32 2 16 bit analog change event without time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 32 3 32 bit analog change event with time 1 read 06 no ra...

Page 58: ...estart 4 No object function code only 23 delay meas No object function code only 24 record current time 1 A default variation refers to the variation responded when variation 0 is requested and or in...

Page 59: ...has the ownership of the protocol and assumes responsibility for its evolution EMC Electromagnetic compatibility HMI Human machine interface IEC International Electrotechnical Commission IEC 61850 Int...