BIO-Tester Relion® REX640

Quick operation guide 

Summary of Contents for RELION REX640

Page 1: ...BIO Tester Relion REX640 Quick operation guide...

Page 2: ...onal requirements are complied with In particular any risks in applications where a system failure and or product failure would create a risk for harm to property or persons including but not limited...

Page 3: ...lways be followed The necessary and required earthing connections must be made according to the product guidelines and regulations When the withdrawable module has been detached from the case do not t...

Page 4: ...O1002 BIO1004 connector 4 LHMI 48 V DC connector 5 PSM1001 PSM1002 PSM1003 test switches and indication LEDs 6 BIO1001 BIO1003 test switches and indication LEDs 7 BIO1002 BIO1004 test switches and ind...

Page 5: ...protection relay and the LHMI need to be switched off before the preparations After the auxiliary supply voltage of the protection relay has been switched off it is possible to start the preparations...

Page 6: ...connector cables between the BIO Tester and the protection relay Connect the separate earth protection lead of BIO Tester to the protective earth pin of the protection relay Connect the connector cab...

Page 7: ...and the protection relay BIO1001 and BIO1002 have their own connector cables The different power supply modules PSM1001 PSM1002 PSM1003 have the same connector cable Double check that the auxiliary v...

Page 8: ...protective earth screw T20 on the LHMI but DO NOT remove the existing LHMI s earth lead Connect the separate earth protection lead of BIO Tester Tighten the protective earth screw to 1 5 Nm 10 Follow...

Page 9: ...Tester to the main s wall plug connector Push the cable connector in place and secure it by turning it clockwise Power up BIO Tester using the mains connection Select the protection relay s operating...

Page 10: ...IED test mode The test mode can be activated via REX640 LHMI Testing binary inputs Select the correct rated voltage by adjusting the potentiometer Set the input supply voltage level above the set val...

Page 11: ...640 LHMI Testing and Commissioning page select Force Outputs On the REX640 LHMI module specific page select state On or Off for the selected output channel and tap Force Monitor the status of binary o...

Page 12: ...ctor cables and put them back inside the BIO Tester case Connect all secondary wiring connector terminals back to the protection relay Ensure the correctness and tightness of connectors Switch on the...

Page 13: ...lo sure to third parties or utilization of its contents in whole or in parts is forbidden without prior writ ten consent of ABB OY 4 Ordering data Item Order number BIO Tester Relion REX640 in a water...

Page 14: ...14 BIO TESTER REX640 QUICK OPER ATION GUIDE This page is intentionally left blank...

Page 15: ...BIO TESTER REX640 QUICK OPER ATION GUIDE 15 This page is intentionally left blank...

Page 16: ...BB Distribution Solutions Electrification Service P O Box 503 FI 65101 VAASA Finland Phone 358 10 22 11 www abb com service www abb com mediumvoltage Copyright 2019 ABB All rights reserved 2NGA000133...