Relion

®

 650 series

Bay control REC650

Product Guide

Summary of Contents for REC650 ANSI

Page 1: ...Relion 650 series Bay control REC650 Product Guide...

Page 2: ...17 Technical data 40 18 Ordering 75 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB ABB AB assumes no responsibil...

Page 3: ...t control configurations can be used and one control IED per bay is recommended Interlocking modules are available for common types of switchgear arrangements The control is based on the select before...

Page 4: ...C2 QC1 EF4 PTOC 51N 67N IN Q CBAY Control WA1 S CILO Control S CILO Control S CILO Control S CILO Control S CILO Control S CILO Control SEL GGIO Control C MSQI Meter V MSQI Meter CV MMXN Meter CC RPLD...

Page 5: ...1 EF4 PTOC 51N 67N IN Q CBAY Control WA1 WA2 S CILO Control S CILO Control S CILO Control S CILO Control S CILO Control S CILO Control S CILO Control SEL GGIO Control C MSQI Meter V MSQI Meter CV MMXN...

Page 6: ...ontrol S CILO Control S CILO Control S CILO Control S CILO Control SEL GGIO Control DRP RDRE Mont QA1 QB1 QB2 QC2 QC1 WA1 WA2 QC11 QC21 CC RBRF 50BF 3I BF PH PIOC 50 3I CC RPLD 52PD PD C MMXU Meter C...

Page 7: ...3 Available functions Bay control REC650 1MRK 511 249 BEN Product version 1 1 Issued February 2011 ABB 7...

Page 8: ...r bus coupler bay 1 1 1 BH_CONN 3 Interlocking for 1 1 2 breaker diameter 1 1 1 BH_LINE_A 3 Interlocking for 1 1 2 breaker diameter 1 1 1 BH_LINE_B 3 Interlocking for 1 1 2 breaker diameter 1 1 1 DB_B...

Page 9: ...s 5 5 5 AUTOBITS AutomationBits command function for DNP3 0 3 3 3 I103CMD Function commands for IEC60870 5 103 1 1 1 I103IEDCMD IED commands for IEC60870 5 103 1 1 1 I103USRCMD Function commands user...

Page 10: ...80 280 280 SRMEMORY Configurable logic blocks set reset memory flip flop gate 40 40 40 RSMEMORY Configurable logic blocks reset set memory flip flop gate 40 40 40 ANDQT Configurable logic Q T AND gate...

Page 11: ...signal gate extracting value with quality and time 20 20 20 FXDSIGN Fixed signal function block 1 1 1 B16I Boolean 16 to Integer conversion 16 16 16 B16IFCVI Boolean 16 to Integer conversion with log...

Page 12: ...3 Insulation gas monitoring function 1 1 1 SSIML 71 Insulation liquid monitoring function 1 1 1 SSCBR Circuit breaker condition monitoring 1 1 1 I103MEAS Measurands for IEC60870 5 103 1 1 1 I103MEASUS...

Page 13: ...ion Bay REC650 A01 1CBA REC650 A02 1CBAB REC650 A07 BCAB Metering PCGGIO Pulse counter logic 16 16 16 ETPMMTR Function for energy calculation and demand handling 3 3 3 Bay control REC650 1MRK 511 249...

Page 14: ...n 1 1 1 LPTTR 26 Thermal overload protection one time constant 1 1 1 CCRBRF 50BF Breaker failure protection 1 1 1 STBPTOC 50STB Stub protection 1 1 1 CCRPLD 52PD Pole discordance protection 1 1 1 BRCP...

Page 15: ...CBA REC650 A02 1CBAB REC650 A07 BCAB Frequency protection SAPTUF 81 Underfrequency function 2 2 2 SAPTOF 81 Overfrequency function 2 2 2 SAPFRC 81 Rate of change frequency protection 2 2 2 Bay control...

Page 16: ...on via ST 1 1 1 GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59 59 59 GOOSEBINRCV GOOSE binary receive 4 4 4 GOOSEDPRCV GOOSE function block to receive a double point value 32 32...

Page 17: ...etting groups 1 TESTMODE Test mode functionality 1 CHNGLCK Change lock function 1 TERMINALID IED identifiers 1 PRODINF Product information 1 PRIMVAL Primary system values 1 SMAI_20_1 12 Signal matrix...

Page 18: ...e configured to co operate with a synchrocheck function Apparatus control APC The apparatus control functions are used for control and supervision of circuit breakers disconnectors and earthing switch...

Page 19: ...t switchyard arrangements each handling the interlocking of one bay The interlocking functionality in each IED is not dependent on any central function For the station wide interlocking the IEDs commu...

Page 20: ...3 are always definite time delayed All IEC and ANSI time delayed characteristics are available The directional function is voltage polarized with memory The function can be set to be directional or n...

Page 21: ...principles A current check with extremely short reset time is used as check criterion to achieve a high security against unnecessary operation A contact check criteria can be used where the fault curr...

Page 22: ...nt return paths but the cable negative sequence impedance is practically constant The directional function is current and voltage polarized The function can be set to forward reverse or non directiona...

Page 23: ...initiating load restoring SAPTOF is provided with an undervoltage blocking Rate of change frequency protection SAPFRC Rate of change frequency protection function SAPFRC gives an early indication of a...

Page 24: ...ker close trip circuit monitoring TCSSCBR The trip circuit supervision function TCSSCBR is designed to supervise the control circuit of the circuit breaker The invalidity of a control circuit is detec...

Page 25: ...estamp and quality of input signals TIMERSETQT function has pick up and drop out delayed outputs related to the input signal The timer has a settable time delay The function also propagates timestamp...

Page 26: ...or position input PSTO 10 Monitoring Measurements CVMMXN CMMXU VNMMXU VMMXU CMSQI VMSQI The measurement functions are used to get on line information from the IED These service values make it possible...

Page 27: ...tagged events logged during disturbances This information is used for different purposes in the short term for example corrective actions and in the long term for example functional analysis The event...

Page 28: ...DT mode SPVNZBAT operates after a predefined operate time and resets when the battery undervoltage or overvoltage condition disappears Insulation gas monitoring function SSIMG Insulation gas monitorin...

Page 29: ...f five meters from the main unit The units are connected with the Ethernet cable included in the delivery The LHMI is simple and easy to understand The whole front plate is divided into zones each wit...

Page 30: ...ated functions to check functionality and to check parts of the configuration and so on Change lock function CHNGLCK Change lock function CHNGLCK is used to block further changes to the IED configurat...

Page 31: ...P and DNP3 With time synchronization wiring IRIG B The IED supports IEC 60870 5 103 time synchronization methods with a time stamping resolution of 5 ms Table 1 Supported communication interface and p...

Page 32: ...IEC09000672 ai IEC09000672 V1 EN Figure 7 Flush mounting the IED into a panel cut out A 240 mm G 21 55 mm B 21 55 mm H 220 mm C 227 mm I 265 9 mm D 228 9 mm J 300 mm E 272 mm K 254 mm F 6 mm A B C IEC...

Page 33: ...C F G B A E D IEC09000678 ai IEC09000678 V1 EN Figure 11 Wall mounting the IED A 270 mm E 190 5 mm B 252 5 mm F 296 mm C 6 8 mm G 13 mm D 268 9 mm GUID 5C185EAC 13D0 40BD 8511 58CA53EFF7DE V1 EN Figu...

Page 34: ...for 6U 1 2x19 casing with 1 TRM Module Slot Rear Position COM pCOM X0 X1 X4 X9 X304 PSM pPSM X307 X309 X410 TRM p2 X101 X102 BIO p3 X321 X324 BIO p4 X326 X329 BIO p5 X331 X334 BIO p6 X336 X339 Bay co...

Page 35: ...RK006501 DB 4 PG 1 1 IEC V1 EN Figure 15 Power supply module PSM 48 125V DC 1MRK006501 DB 5 PG 1 1 IEC V1 EN Figure 16 Power supply module PSM 110 250V DC 1MRK006501 DB 6 PG 1 1 IEC V1 EN Figure 17 Tr...

Page 36: ...19 Binary input output BIO option Terminal X326 329 1MRK006501 DB 9 PG 1 1 IEC V1 EN Figure 20 Binary input output BIO option Terminal X331 334 Connection diagrams for REC650 A02 1MRK006501 CB 3 PG 1...

Page 37: ...IEC V1 EN Figure 23 Power supply module PSM 110 250V DC 1MRK006501 CB 6 PG 1 1 IEC V1 EN Figure 24 Transformer module TRM 1MRK006501 CB 7 PG 1 1 IEC V1 EN Figure 25 Binary input output BIO option Ter...

Page 38: ...ure 27 Binary input output BIO option Terminal X331 X334 1MRK006501 CB 10 PG 1 1 IEC V1 EN Figure 28 Binary input output BIO option X336 X339 Connection diagrams for REC650 A07 1MRK006501 BB 3 PG 1 1...

Page 39: ...IEC V1 EN Figure 31 Power supply module PSM 110 250V DC 1MRK006501 BB 6 PG 1 1 IEC V1 EN Figure 32 Transformer module TRM 1MRK006501 BB 7 PG 1 1 IEC V1 EN Figure 33 Binary input output BIO option Ter...

Page 40: ...X326 X329 1MRK006501 BB 9 PG 1 1 IEC V1 EN Figure 35 Binary input output BIO option Terminal X331 X334 1MRK006501 BB 10 PG 1 1 IEC V1 EN Figure 36 Binary input output BIO option Terminal X336 X339 Ba...

Page 41: ...ctor within which under specified conditions the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment under specified c...

Page 42: ...For 1 s 100 A 500 A For 10 s 20 A 100 A Dynamic current withstand Half wave value 250 A 1250 A Input impedance 100 m 20 m Voltage inputs Rated voltage Un 100 V AC 110 V AC 115 V AC 120 V AC Voltage w...

Page 43: ...y voltage Max 15 of the DC value at frequency of 100 Hz Maximum interruption time in the auxiliary DC voltage without resetting the IED 50 ms at Uaux Binary inputs and outputs Table 4 Binary inputs De...

Page 44: ...carry for 3 0 s 15 A Make and carry for 0 5 s 30 A Breaking capacity when the control circuit time constant L R 40 ms at U 48 110 220 V DC 1 A 0 3 A 0 1 A Table 7 Power output relays with TCS function...

Page 45: ...d by connectors and cable together Table 10 X4 IRIG B interface Type Protocol Cable Screw terminal pin row header IRIG B Shielded twisted pair cable Recommended CAT 5 Belden RS 485 9841 9844 or Alpha...

Page 46: ...titude up to 2000 m Transport and storage temperature range 40 85 C Table 15 Environmental tests Description Type test value Reference Cold tests operation storage 96 h at 25 C 16 h at 40 C 96 h at 40...

Page 47: ...de 10 V emf f 150 kHz 80 MHz IEC 61000 4 6 IEC 60255 22 6 level 3 Radiated amplitude modulated 20 V m rms f 80 1000 MHz and f 1 4 2 7 GHz IEC 61000 4 3 IEC 60255 22 3 level 3 Fast transient disturbanc...

Page 48: ...s No restart 0 s Correct behaviour at power down IEC 60255 11 IEC 61000 4 11 Electromagnetic emission tests EN 55011 class A IEC 60255 25 Conducted RF emission mains terminal 0 15 0 50 MHz 79 dB V qua...

Page 49: ...ance 100 M 500 V DC Protective bonding resistance IEC 60255 27 Resistance 0 1 60 s Table 18 Mechanical tests Description Reference Requirement Vibration response tests sinusoidal IEC 60255 21 1 Class...

Page 50: ...lBase 1 0 of Ir at I Ir 1 0 of I at I Ir Reset ratio 95 Operate time 20 ms typically at 0 to 2 x Iset Reset time 35 ms typically at 2 to 0 x Iset Critical impulse time 10 ms typically at 0 to 2 x Iset...

Page 51: ...e characteristics see table 65 table 66 and table 67 17 curve types See table 65 table 66 and table 67 Operate time nondirectional start function 20 ms typically at 0 to 2 x Iset Reset time nondirecti...

Page 52: ...ms typically at 0 to 2 x Iset Reset time 30 ms typically at 2 to 0 x Iset Critical impulse time 10 ms typically at 0 to 2 x Iset Operate time 10 ms typically at 0 to 10 x Iset Reset time 40 ms typica...

Page 53: ...urve types See table 65 table 66 and table 67 Minimum polarizing voltage 1 100 of UBase 0 5 of Ur Minimum polarizing current 2 100 of IBase 1 0 of Ir Real part of source Z used for current polarizatio...

Page 54: ...current 1 00 400 00 of lBase At low setting 10 50 mA 1 0 of Ir at I Ir 1 0 of I at I Ir 1 0 mA Operate level for non directional residual overvoltage 1 00 200 00 of UBase 0 5 of Ur at U Ur 0 5 of U at...

Page 55: ...ly at 0 8 to 1 5 x Uset Reset time non directional residual overvoltage 120 ms typically at 1 2 to 0 8 x Uset Operate time directional residual over current 260 ms typically at 0 5 to 2 x Iset Reset t...

Page 56: ...nt trip Reset level temperature 0 600 C 2 0 of heat content trip Table 27 Breaker failure protection CCRBRF Function Range or value Accuracy Operate phase current 5 200 of lBase 1 0 of Ir at I Ir 1 0...

Page 57: ...value Accuracy Operate value current asymmetry level 0 100 1 0 of Ir Reset ratio 95 Time delay 0 000 60 000 s 0 5 25 ms Table 30 Broken conductor check BRCPTOC Function Range or value Accuracy Minimum...

Page 58: ...2 0 5000 0 of IBase 1 0 of Ir at I Ir 1 0 of I at I Ir Reset ratio 95 Low voltage level for memory 0 0 5 0 of UBase 0 5 of Ur Relay characteristic angle 180 180 degrees 2 0 degrees Relay operate angl...

Page 59: ...ally at 2 to 0 x Uset Impulse margin time 15 ms typically Table 34 Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage low and high step 1 200 of UBase 0 5 of Ur a...

Page 60: ...step 2 0 000 60 000 s 0 5 25 ms Minimum operate time for step 1 inverse characteristic 0 000 60 000 s 0 5 25 ms Operate time start function 30 ms typically at 0 to 2 x Uset Reset time start function...

Page 61: ...0 Hz 50 ms typically at fset 0 5 Hz to fset 0 5 Hz Operate time delay 0 000 60 000 s 250 ms Restore time delay 0 000 60 000 s 150 ms Table 38 Overfrequency protection SAPTOF Function Range or value Ac...

Page 62: ...Ir 5 0 of I at I Ir Table 41 Fuse failure supervision SDDRFUF Function Range or value Accuracy Operate voltage zero sequence 1 100 of UBase 1 0 of Ur Operate current zero sequence 1 100 of IBase 1 0...

Page 63: ...io Ubus Uline 0 2 to 5 0 Frequency difference limit between bus and line 0 003 1 000 Hz 2 0 mHz Phase angle difference limit between bus and line 5 0 90 0 degrees 2 0 degrees Voltage difference limit...

Page 64: ...s Inhibit reset time 0 000 60 000 s Reclaim time 0 00 6000 00 s Minimum time CB must be closed before AR becomes ready for autoreclosing cycle 0 00 6000 00 s CB check time before unsuccessful 0 00 60...

Page 65: ...T 10 10 20 0 000 90000 000 s 0 5 25 ms LOOPDELAY 10 10 20 Table 47 Configurable logic Q T Logic block Quantity with cycle time Range or value Accuracy 20 ms 100 ms ANDQT 20 100 ORQT 20 100 XORQT 10 30...

Page 66: ...at S Sr 1 Apparent power S 0 1 x Ur U 1 5 x Ur 0 2 x Ir I 4 0 x Ir 1 0 of Sr at S Sr 1 0 of S at S Sr Apparent power S Three phase settings cos phi 1 0 5 of S at S Sr 0 5 of Sr at S Sr Power factor co...

Page 67: ...derived Maximum number of binary inputs 96 Maximum number of phasors in the Trip Value recorder per recording 30 Maximum number of indications in a disturbance report 96 Maximum number of events in t...

Page 68: ...aximum number of recorded disturbances 100 Table 53 Event recorder DRPRDRE Function Value Buffer capacity Maximum number of events in disturbance report 150 Maximum number of disturbance reports 100 R...

Page 69: ...io lower limit 105 Upper limit for the battery terminal voltage 60 140 of Ubat 1 0 of set battery voltage Reset ratio upper limit 95 Timers 0 000 60 000 s 0 5 110 ms Table 57 Insulation gas monitoring...

Page 70: ...counter PCGGIO Function Setting range Accuracy Cycle time for report of counter value 1 3600 s Table 61 Function for energy calculation and demand handling ETPMMTR Function Range or value Accuracy Ene...

Page 71: ...5 999 in steps of 0 01 unless otherwise stated ANSI Extremely Inverse A 28 2 B 0 1217 P 2 0 ANSI IEEE C37 112 class 5 40 ms ANSI Very inverse A 19 61 B 0 491 P 2 0 ANSI Normal Inverse A 0 0086 B 0 018...

Page 72: ...rt time inverse A 0 05 P 0 04 IEC Long time inverse A 120 P 1 0 Table 67 RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic 1 0 236 0 339 t k I...

Page 73: ...steps of 0 01 unless otherwise stated Class 5 40 ms Type B curve 2 0 480 32 0 5 0 035 t k U U U EQUATION1437 SMALL V1 EN k 0 05 1 10 in steps of 0 01 unless otherwise stated Type C curve 3 0 480 32 0...

Page 74: ...N1431 SMALL V1 EN U Uset U UVmeasured k 0 05 1 10 in steps of 0 01 unless otherwise stated Class 5 40 ms Type B curve 2 0 480 0 055 32 0 5 k t U U U EQUATION1432 SMALL V1 EN U Uset U Umeasured k 0 05...

Page 75: ...V1 EN U Uset U Umeasured k 0 05 1 10 in steps of 0 01 Class 5 40 ms Type B curve 2 0 480 32 0 5 0 035 t k U U U EQUATION1437 SMALL V1 EN k 0 05 1 10 in steps of 0 01 Type C curve 3 0 480 32 0 5 0 035...

Page 76: ...REC650 Position SOFTWARE 1 Notes and Rules Version number Version no 1 1 Selection for position 1 1 1 Configuration alternatives 2 Notes and Rules Single breaker for single busbar IEC A01 Single break...

Page 77: ...erminals S Ringlug terminals R Power supply Slot position pPSM 100 240V AC 110 250V DC 9BO A 48 125V DC 9BO B Selection for position 7 Human machine interface 8 Notes and Rules Local human machine int...

Page 78: ...3 NO Trip 5 NO Signal 1 CO Signal A A A A p6 optional for A01 p6 A for A02 A07 Selection for position 10 A A A Communication and processing module 11 Notes and Rules Slot position rear view pCOM 14BI...

Page 79: ...IEC Quantity 1MRK 500 093 UEN Technical manual IEC Quantity 1MRK 511 247 UEN Commissioning manual IEC Quantity 1MRK 511 248 UEN Application manual IEC Quantity 1MRK 511 246 UEN Communication protocol...

Page 80: ...650 series manuals Identity number Communication protocol manual DNP3 1MRK 511 241 UEN Communication protocol manual IEC 61850 1MRK 511 242 UEN Communication protocol manual IEC 60870 5 103 1MRK 511...

Page 81: ...81...

Page 82: ...act us ABB AB Substation Automation Products SE 721 59 V ster s Sweden Phone 46 0 21 32 50 00 Fax 46 0 21 14 69 18 www abb com substationautomation 1MRK 511 249 BEN Copyright 2011 ABB All rights reser...