background image

----------

l�-'

un 

Jet 

_________

__

ИБП ABB Powervalue 11 RT (

6-1

0 кВА) - руководство по эксплуатации. Юниджет

Постоянная ссылка на страницу:

 

https://www.uni-jet.com/catalog/istochniki-

besperebojnogo-pitaniya/on-line-ibp-1-kva-10kva/abb-powervalue-11-rt.html

Summary of Contents for PowerValue 11 RT

Page 1: ...l un I Jet _________ __ ABB Powervalue 11 RT 6 10 https www uni jet com catalog istochniki besperebojnogo pitaniya on line ibp 1 kva 10kva abb powervalue 11 rt html...

Page 2: ...PowerValue 11 RT 6 10 kVA User manual...

Page 3: ...RESULT IN MINOR INJURY AND OR DAMAGE TO THE PRODUCT NOTE NOTE INDICATES THE PRESENCE OF A HAZARD WHICH COULD LEAD TO PROPERTY DAMAGE SAFETY WARNING THE SYMBOL IS USED TO ALERT THE USER TO WARNINGS CAU...

Page 4: ...characteristics 12 3 4 Electrical installation 14 3 5 Initial startup 20 3 6 Emergency power off EPO 20 3 7 Paralleling the units 21 3 8 Installation Checklist 24 4 Operation 25 4 1 Control Panel 25...

Page 5: ...4 PowerValue 11 RT 6 10kVA User manual...

Page 6: ...AREA TO WARN ELECTRICAL MAINTENANCE PERSONNELS THAT THE CIRCUIT FEEDS A UPS MAKE SURE THAT WARNING LABEL CONTAINS THE FOLLOWING TEXT OR EQUIVALENT ISOLATE THE UPS UNINTERRUPTIBLE POWER SUPPLY BEFORE...

Page 7: ...FIRE AS THEY MAY EXPLODE WARNING DO NOT OPEN OR MUTILATE THE BATTERIES WARNING RELEASED ELECTROLYTE IS HARMFUL TO THE SKIN AND EYES 1 3 Declaration of Safety conformity and CE marking PowerValue 11 RT...

Page 8: ...ISCONNECT THE BATTERIES BEFORE CARRYING OUT ANY KIND OF SERVICE AND OR MAINTENANCE VERIFY THAT NO CURRENT IS PRESENT AND NO HAZARDOUS VOLTAGE EXISTS IN THE CAPACITOR OR BUS CAPACITOR TERMINALS WARNING...

Page 9: ...or supplier immediately in case of any damage 3 1 3 Storage of UPS If you plan to store the UPS prior to use keep the UPS in a dry clean and cool storage room with an ambient temperature between 15 C...

Page 10: ...de the cabinet into the rack as shown in Figure 1 Figure 1 Rack mount installation If installing additional UPS units repeat the steps above for each cabinet 3 2 2 1 Connecting the external battery mo...

Page 11: ...owerValue 11 RT 10kVA To connect the external battery modules 1 Plug the battery module cable into the UPS battery connector in the rear panel of the UPS as shown in Figure 3 3 2 2 2 Standalone Tower...

Page 12: ...al tower position 1 Carefully rotate the LCD control panel 90 to the right in the top and bottom front panels as shown in Figure 6 Figure 6 Display rotation 2 Place the units to a vertical position 3...

Page 13: ...tton Scroll Button Down or Forward 3 3 2 Rear panel Table 2 and Figures 9 and Table 3 and Figure 10 show the connectors and ports in the UPS rear panel 1 GND contact 2 EPO 3 Parallel port 4 Output cir...

Page 14: ...werValue 11 RT 10 kVA rear view 1 SNMP AS400 slot 2 EPO 3 USB 4 Parallel port 5 Battery connector 6 GND contact 7 Output sockets 8 Output circuit breaker 9 AC output 10 Bypass 11 AC input Table 3 Powe...

Page 15: ...ontactor 208 240V 35A PowerValue 11 RT 6 kVA 208 240V 50A PowerValue 11 RT 10 kVA Line input Neutral Input main breaker AC Contactor Mains Input Coil Remote Switch 3 4 2 Recommended cable sections and...

Page 16: ...0kVA 15 3 4 3 Connections To access the terminal blocks remove the 2 screws from the terminal block cover as shown in Figures 12 and 13 Figure 12 PowerValue 11 RT 6 kVA Terminal block Figure 13 PowerV...

Page 17: ...d Main low voltage switchboard MLVS CAUTION MAKE SURE THAT THE EARTH WIRE IS CONNECTED To connect the UPS cables 1 Connect a jumper between terminals JP and L 2 Connect the input and output cables Use...

Page 18: ...erent a transformer should be connected to the inputs Figure 18 Figure 19 and Figure 20 show the alternative ways of connecting the inputs to the transformers Figure 17 UPS Diagram with Dual Input Fee...

Page 19: ...THAT THE EARTH WIRE IS CONNECTED To connect the UPS cables 1 Ensure that the jumper JP is disconnected 2 Connect the input output and bypass cables Use appropriate tools and terminal splices to ensure...

Page 20: ...verter Main low voltage switchboard MLVS Normal AC Load Figure 24 Frequency converter connections for 6kVA units Figure 25 Frequency converter connections for 10kVA units CAUTION INDUCTIVE LOADS FOR E...

Page 21: ...ABLED BY DEFAULT AFTER INITIAL STARTUP AUTO SENSING IS DISABLED UNTIL MANUALLY RE ENABLED THROUGH THE OUTPUT FREQUENCY SETTINGS NOTE AT INITIAL STARTUP THE INPUT VOLTAGE AUTO SENSING IS DISABLED BY DE...

Page 22: ...eaker panel is lower than 10 meters the length difference between input and output cables of the UPS must be lower than 20 When the distance between the UPS in parallel and the breaker panel is more t...

Page 23: ...between the two UPS units is lower than 0 5V If the output voltage difference is higher than 0 5V the UPS voltage needs to be regulated If the output voltage difference is lower than 0 5V switch on t...

Page 24: ...PS output breaker 9 Transfer the main maintenance switch or static switch from BPS to UPS 10 Press the power on button of one UPS and each UPS will turn on Both UPS will then work in parallel in onlin...

Page 25: ...nated A ground conductor is properly installed Battery enclosure is installed Air conditioning equipment is installed and operating correctly The area around the installed UPS system is clean and dust...

Page 26: ...software 4 1 Control Panel The user friendly control panel has two parts selection keys power management LCD display PMD 4 Operation Figure 29 Control panel Selection keys LCD display 4 1 1 Selection...

Page 27: ...nutes Overload Beep twice every second Table 5 Definition of alarms Figure 30 The default LCD display Operating mode Battery information Mains input information UPS output information Load information...

Page 28: ...ut from ECO mode to battery mode is 10ms and not recommended for sensitive loads Converter mode In converter mode the UPS runs with fixed output frequency 50Hz or 60Hz In case of a mains failure the U...

Page 29: ...1 second and the UPS starts up 4 After a few seconds the UPS transfers to battery mode When the UPS is supplied with power from the mains the UPS transfers to online mode without interruption in the o...

Page 30: ...Navigation Use the scroll buttons to navigate through the UPS screens From the main screen UPS status screen press or for information on alarm parallel system and battery From the main screen keep pre...

Page 31: ...ent log Reset all the events from the log file No Yes No Restore factory settings Recover all settings in the LCD menu and the EPO polarity and locks the DC start up can be executed only when UPS is i...

Page 32: ...lel system 1 UPS system Parallel system 4 4 2 4 Identification The identification menu shows the UPS serial number firmware serial number and model type Press to navigate through the Identification me...

Page 33: ...s cut off enabled disabled disabled Redundancy lost in parallel UPS systems One of the parallel units has been disconnected from the system enable disabled enabled Bypass voltage low limit When the vo...

Page 34: ...mode voltage low limit 5 218 5 5V ECO mode voltage high limit 5 241 5V ECO mode frequency low limit 5 47 5Hz ECO mode frequency high limit 5 52 5Hz External battery modules 0 Set running time LCD con...

Page 35: ...34 PowerValue 11 RT 6 10kVA User manual...

Page 36: ...ing control and firmware updates To establish communication between the UPS and a computer connect one end of the serial communication cable to the RS 232 port on the UPS and the other end to the RS 2...

Page 37: ...NOT HAVE TO BE SHUTDOWN BEFORE INSTALLING A COMMUNICATION CARD To install a network management card 1 Remove the two screws that protect the communication slot of the UPS 2 Insert the SNMP card into...

Page 38: ...sing the UPS status menu screen 1 Press for longer than 1 second to go to the UPS status menu screen 2 Press to access the UPS Status main screen 3 Press to access the notice and alarm screens 4 The U...

Page 39: ...oft start successfully Contact your service representative Output Short Circuit Alarm Code 31 Indicates that the UPS has detected abnormally low impedance placed on its output considered as a short ci...

Page 40: ...system is in redundant mode only the UPS with the failure will transfer to fault mode without output Other UPS will still support the load If the parallel system is not redundant and the load cannot...

Page 41: ...40 PowerValue 11 RT 6 10kVA User manual...

Page 42: ...Webserver Modbus 97 Output Load Percentage Output Webserver Modbus 100 Battery Voltage V Battery Webserver Modbus 110 Battery Capacity Battery Webserver Modbus 103 Temperature C Environmental Webserve...

Page 43: ...toring UPS Status Battery Status Battery status UPS Monitoring UPS Status Capacity Battery measurement UPS Monitoring UPS Status Voltage Battery measurement UPS Monitoring UPS Status Time on Battery B...

Page 44: ...or PowerValue 11 RT 10 kVA 1 x 20 x 9 0Ah Standard EBM value setting through LCD display and RS232 M is the total nr of standard EBM connected M 1 UPS Model LCD display path Settings Password USER Ext...

Page 45: ...614 00798 03 Contact us Copyright ABB All rights reserved Specification subjects to change without notice www abb com ups ups sales ch abb com...

Reviews: