background image

 

I N S TA LL ATI O N  M A N UA L 

Stanilite®

Platinum Spitfire® LED recessed

Nexus® RF

Doc no. 29-WSIS001_A

This document covers

What’s inside the box

Safety warning

Lamp head assembly

Installation instructions

Battery and control pack

Removal instructions

Accessory kit

Testing precautions

Installation manual

Troubleshooting guide

Warranty information

Troubleshooting guide

If you have installed and connected the fitting as per the instructions listed earlier and it does 
not function correctly, use the following table as a guide to fixing the problem. Look up the 
type of fault in the left column and check the possible causes from the right column.  

If the fitting still does not work after checking these possible causes, contact ABB customer 
service in Australia on 1800 60 20 20.


ABB Australia Pty Limited

For enquiries
ABB contact centre: 1800 60 20 20
E-mail: [email protected] 

www.stanilite.com.au

© Copyright 2019 ABB. All rights reserved. 

9

A

K

K

10

74

9

20

28

0 - A - M

ay 2

0

19

Thank you for choosing ABB product

Please read this document thoroughly before 
commencing installation and retain for future 
reference. Contact ABB customer service in 
Australia on 1800 60 20 20 if you need any 
assistance. The installation instructions were 
correct at the time of print. To reflect changes in 
technology and Australian standards; ABB 
reserves the right to amend the instructions 
without notice. Updated document can be found 
on the Stanilite website.

Safety warning

In Australia and New Zealand, only licensed 
electricians are permitted by law to work with 
240 volt electrical installations.
Do not attempt to install or connect this product 
unless you are a licensed electrician.
Turn off and isolate the electrical supply before 
connecting this fitting to the building wires.
Do not touch the terminals of the terminal block 
when the light fitting is energised.
The only user-serviceable parts are the lamp head 
assembly and battery pack. LED light source is 
not user-serviceable.
Do not attempt to service other parts of the 

No. Fault

Possible causes

1

LED light source and indicating LED not lit

AC supply not connected; 

or

AC supply turned off; 

or

Test switch damaged

2

LED light source is lit but indicating LED not lit

Test switch damaged; 

or

Battery not connected or faulty

3

LED light source does not switch to emergency 
mode when the test button is pressed

Test switch damaged; 

or

Battery not connected or faulty

4

LED light source works momentarily on emergency 
when the test button is pressed

Battery not yet charged (allow up to 24 hours)

fitting as this will void the warranty.
As the installer, it is your responsibility to ensure 
compliance with all relevant building and safety 

codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to 

the applicable standards for data and mains 
cabling installation procedures and 
requirements.
As per AS 60598.2.2:2016 the recessed luminaire 
classification is CA90.  

Note: Not suitable for use with loose-fill 
insulation.

The control pack and battery pack must be 
installed above the insulation. No fire rated box is 
required for the product.

Important to note:

•  This product is designed for indoor use only.

Nexus RF (wireless system)

The Nexus RF range of light fittings are designed to 
communicate via a proprietary RF network, however 
the electrical installation of the fittings is identical 
to that of a standard non-monitored fitting.

Reviews: