Disturbance recording and  

fault locating device DRL6600U

Product guide

Summary of Contents for DRL6600U

Page 1: ... Disturbance recording and fault locating device DRL6600U Product guide ...

Page 2: ...of change frequency recording 9 8 Binary signal recording 9 9 Fault Locating 9 10 Data analysis 9 11 Operation 10 Manual recording 10 Remote recording 10 Local remote reset 10 12 Monitoring 10 Analog signal sampling monitoring 10 Binary signal monitoring 10 Disturbance report 10 13 Basic IED functions 10 Self supervision with internal event list 10 Self supervision function 10 Time Synchronization...

Page 3: ...is necessary It truthfully records electric variables during such events as power oscillation frequency collapse or voltage fluctuation providing indispensable data support for incident analysis and operation maintenance DRL6600U consist of a recording unit with CPU and hard disk and a separate HMI It uses the CPU and hard disk for recording and data transfer to the system data manager or other ta...

Page 4: ...50N IN U over Phase overvoltage recording 59 U U1 over Positive sequence overvoltage recording U1 U2 over Negative sequence overvoltage recording U2 3U0 over Residual overvoltage recording 59N 3U0 U under Phase undervoltage recording 27 U U1 under Positive sequence undervoltage recording U1 U sudden change Delta phase voltage recording U 3U0 sudden change Delta residual voltage recording 3U0 I sud...

Page 5: ...IEC61850 Over frequency Over frequency recording 81 f Low frequency Low frequency recording 81 f DF div dt Rate of change frequency recording 81R Df dt U3 over Third harmonic overvoltage recording U3 U5 over Fifth harmonic overvoltage recording U5 U7 over Seventh harmonic overvoltage recording U7 DI Binary signal recording Fault locating Fault locating ...

Page 6: ...g U2 3U0 over Residual overvoltage recording 59N 3U0 U under Phase undervoltage recording 27 U U1 under Positive sequence undervoltage recording U1 U sudden change Delta phase voltage recording U 3U0 sudden change Delta residual voltage recording 3U0 I sudden change Delta phase current recording I 3I0 sudden change Delta residual current recording IN Current variation Variation current recording C...

Page 7: ...ggering generates a recording file Remote recording Remote control triggering generates a recording file Local reset Locally reset the LEDs Remote reset Remotely reset the LEDs Table 3 Communication function Name Description ANSI IEC60617 IEC61850 IEC61850 MMS communication IEC61850 communication protocol function HMI RJ 45 IEC 61850 8 1 Double point GOOSE Receiving Receive a double point GOOSE va...

Page 8: ...ring the middle and late periods of system disturbance PostTrigger The disturbance recorder applies the principle of extendable recording that switches from the A to B and C periods ensuring a high resolution during the PreTrigger and Trigger periods and adjusting to a lower sampling rate during the PostTrigger period in order to reduce the long term storage requirements When a new disturbance occ...

Page 9: ...ase voltage recording Overvoltage recording When supplying power over an underground cable or a network with high capacitance the phase to ground capacitance of the line may contribute to a voltage rise Ferranti effect Long term operation may pose a threat to the safety of energized equipment Thus it s necessary to monitor the voltage in the power system Delta voltage recording Large scale electri...

Page 10: ... corresponding parameters like line length and line impedance have been entered once a phase to ground or phase to phase short circuit happens a recording will be started Based on the impedance at the time the short circuit happens the DRL6600U automatically calculates and determines the distance between the device and the fault point 10 Data analysis DRL6600U provides a cross platform waveform an...

Page 11: ...ite name triggering name triggering file name fault line fault distance fault phase tripping phase and current and voltage RMS of one cyclic wave both before and after the disturbance 13 Basic IED functions Self supervision with internal event list The self supervision INTERRSIG and SELFSUPEVLST will respond to internal system events generated by the different internal self supervision functions I...

Page 12: ...ns the following an industrial PC a display LCD a keyboard and a mouse The HMI is used for setting monitoring and controlling of DRL6600U 15 Communication Station level communication The DRL6600U disturbance recorder supports the IEC 61850 8 1 communication protocol The device provides 8 Ethernet ports on the DRL6600U HMI so that several independent networks can be connected simultaneously It also...

Page 13: ...T Figure 2 Device module Table 4 Module description Name SN Location Function POWER X100 No 1 Power supply module SIGNAL X200 No 2 Signal panel module providing binary output and time synchronization CPU X300 No 3 Recording CPU AD X400 No 5 No 8 Analog signal sampling DI X500 No 9 No 10 Binary signal sampling AC X600 No 14 No 16 No 18 No 20 VT CT connection DC X610 No 17 DC connection DRL6600U HMI...

Page 14: ...age channels is 180V and largest current for current channels is 40In In is 1A or 5A please note clearly in the order form Primary and secondary side rated values can be configured in the analog input channel settings of the device Up to 192 binary input connections are supported Figure 3 Analog input module sketch diagram 1 No 17 is a DC input module with 8 DC input channels applicable to for exa...

Page 15: ...000359 Disturbance Recording and Fault Locating Device DRL6600U Product version V8 30 Issued May 2017 Revision 14 ABB Figure 4 Binary input terminal diagram up to 192 binary input connections are supported ...

Page 16: ...Device DRL6600U Product version V8 30 Issued May 2017 Revision 15 ABB 18 Mounting method This device commonly adopts panel mode mounting Figure 5 IED mounting cut out dimension diagram E 190 6mm F 133 3mm A 465mm B 450mm C 532 2mm D 133 3mm G Φ8 M5 Or M6 ...

Page 17: ...ABB Figure 7 Display hanging bar cut out dimension diagram Figure 6 Keyboard and mouse carrier cut out dimension diagram E Φ9 mm 4 9x9 B 450mm A 465mm C 89 5mm D 76 2mm I Φ8 6 8x10 3mm H 37 7mm G 101 6mm F 76 2mm E 101 6mm B 350mm D 354 8 0 15 mm C 300mm Figure 8 Display mounting cut out dimension diagram A 482 6 0 2mm ...

Page 18: ...ED device dimensions and weights Description Reference value Width 465mm Height 531 8mm Depth 249 5mm Case weight 40kg DRL6600U HMI weight 1 3kg Table 6 Power supply Description Reference value Rated value 110 220V DC Permissible deviation 15 10 Maximum burden 80W Maximum allowable ripple 5 Maximum de energized time for direct current without IED restart 100ms ...

Page 19: ...inuous 1s 10s 4 times the rated value 100 times the rated value 10 times the rated value Dynamic current tolerance Half wave value 1250A Input impedance 20mΩ U Rated voltage Un 57 74V AC Rated voltage Udn 300V Voltage tolerance Continuous RMS 2 times the rated value Rated voltage overload 0 5VA phase Table 8 binary input Description Reference value Operating range Maximum input voltage 300V DC Rat...

Page 20: ...1 TCP IP RJ 45 100MBits s Table 11 IRIG B port Type Protocol Cable Screw terminal pin row header IRIG B Shielded twisted pair Recommendation CAT 5 Belden RS 485 9841 9844 or Alpha electric wire Alpha 6222 6230 Table 12 IP classification flush mounting Description Value IED front panel IP 40 IED back panel connecting terminal IP 20 DRL6600U HMI front panel and side IP 40 Table 13 Ambient conditions...

Page 21: ... IEC 60068 2 78 IEC 60068 2 30 Table 15 Electro magnetic compatibility test Description Type test value Reference standard 100kHz and 1MHz burst disturbance test Common mode Differential mode 2 5kV 1kV IEC 60255 4 18 IEC 60255 22 1 level 3 Electrostatic discharge test Contact discharge Air discharge 8kV 15kV IEC61000 4 2 2008 IEC 60255 22 2 level 4 Radio frequency interference tests Transmission c...

Page 22: ... 4 Power frequency immunity test Common mode Differential mode RMS 300V RMS 150V IEC 60255 22 7 level A Voltage sag and short interruption Sag Interruption 40 200ms 70 500ms 0 100ms No restart 0 s Behave normally at power off IEC 60255 11 IEC 61000 4 17 Electromagnetic launch test Transmission radio frequency launch main terminal 0 15 0 50MHz 0 5 30MHz Radiation radio frequency launch 30 230MHz 23...

Page 23: ...0255 5 Insulation resistance measurements Isolation resistance 100MΩ 500V DC IEC 60255 5 Table 17 Machinery test Description Reference standard Requirement Vibration response test sine IEC 60255 21 1 Type 2 Vibration durability test IEC 60255 21 1 level 1 Impulse response test IEC 60255 21 2 level 1 Impulse resistance test IEC 60255 21 2 level 1 Crash test IEC 60255 21 2 level 1 Table 18 Product s...

Page 24: ...tage 0 5 30V Settings 3 Un accuracy 5 Residual overvoltage 0 5 200V Settings 3 Un accuracy 5 Phase undervoltage 10 120V 5 Positive sequence undervoltage 10 120V 5 Delta phase voltage 0 5 30V Settings 5 Un accuracy 10 Delta residual voltage 0 5 30V Settings 5 Un accuracy 10 Delta phase current 0 05 10A Settings 10 In accuracy 20 Delta residual current 0 05 10A Settings 10 In accuracy 20 Variation c...

Page 25: ...DRL6600U DC110V 5A UAAEAH102000000A24AAAA DRL6600U DC220V 5A UAAEAL220000000A24AAAA DRL6600U 64 AI 32I 32U 192 BI GOOSE DC110V 1A UAAEAH220000000A24AAAA DRL6600U DC220V 1A UAAEAL202000000A24AAAA DRL6600U DC110V 5A UAAEAH202000000A24AAAA DRL6600U DC220V 5A UAAEAL220100000A24AAAA DRL6600U 80 40I 40U AI 192 BI GOOSE DC110V 1A UAAEAH220100000A24AAAA DRL6600U DC220V 1A UAAEAL202010000A24AAAA DRL6600U D...

Page 26: ...B AB Grid Automation Products 721 59 Västerås Sweden Phone 46 0 21 32 50 00 abb com protection control 4CAE000359 Rev Copyright 2017 ABB All rights reserved Specifications subject to change without notice ...