background image

CP410

Installation and Operation Manual

ABB, 1SBC159101M0201 2007-05

English

Cover_MAEN857.fm  Page 1  Monday, April 2, 2007  11:17 AM

Summary of Contents for CP410

Page 1: ...CP410 Installation and Operation Manual ABB 1SBC159101M0201 2007 05 English ...

Page 2: ...ead the entire installation manual prior to installing and using this equipment Only qualified personnel may install operate or repair this equipment ABB is not responsible for modified altered or renovated equipment Because the equipment has a wide range of applications users must acquire the appropriate knowledge to use the equipment properly in their specific applications Only parts and accesso...

Page 3: ...ons 10 3 3 Mounting Procedure 10 3 4 Grounding 12 3 5 Power Supply and Wiring 12 4 Dip Switches 13 5 Communication Port 14 6 LCD Contrast Adjustment 14 7 Operation 15 7 1 Self Test 15 7 2 System Menu 16 7 3 Key Pad 17 7 4 Bench and Function Tests 18 7 5 Setting Parameters 18 7 6 Downloading an Application 19 7 7 Uploading an Application 20 7 8 Copying an Application 21 7 9 Passwords 22 ...

Page 4: ...Contents ABB 1SBC159101M0201 ...

Page 5: ...C Storing the operator terminal where the temperature is lower higher than recommended in this manual can cause the LCD display liquid to congeal become isotopic The LCD display liquid contains a powerful irritant In case of skin contact wash immediately with plenty of water In case of eye contact hold the eye open flush with plenty of water and get medical attention The supplier is not responsibl...

Page 6: ... the power circuit Installation Communication cables must be separated from power cables for operational circuits Only use shielded cables to avoid unpredictable problems During Use Emergency stop and other safety functions may not be controlled from the operator terminal Do not use too much force or sharp objects when touching the keys display etc Service and Maintenance Only qualified personnel ...

Page 7: ...Installation 2 1 Package Contents The following parts are found in the box Operator terminal CP410 4 installation fasteners Power connector connected to the 24 V DC power outlet This installation and operation manual 1SBC159101M0201 CP410 ...

Page 8: ...ash ROM 4 MB RAM 128 KB CPU 32 bit RISC Battery backed memory No Real time clock Yes Display Mono STN LCD 160 x 80 pixels black white with 16 gray levels Yellow green LED backlight lifetime approximately 75 000 h Active area of display W x H 65 x 35 mm 20 x 10 characters of 8 x 8 size can be displayed Contrast adjustment Contrast adjustable by potentiometer on the back Power supply 24 V DC 15 or 2...

Page 9: ...ctrostatic Discharge IEC61000 4 2 RF Susceptibility IEC61000 4 3 High Frequency Transients IEC61000 4 4 Cooling Natural cooling Parameter CP410 CP410 Fixture mounting holes Power lamp Communication lamp Function and numerical keys Display DIP switches 1 10 Contrast adjustment COM2 RS232 RS422 RS485 DC power outlet ...

Page 10: ...ifications 10 ABB 1SBC159101M0201 3 2 External and Cut out Dimensions 3 3 Mounting Procedure 1 Cut out the control front panel to match the dimensions mm below CP410 CUTOUT DIMENSION UNIT mm CP410 CUTOUT DIMENSION ...

Page 11: ...xtures to the holes on the unit and fasten the screws into the front panel Do not tighten the screws with too much force or it may cause the deformation of the oper ator terminal 3 The operator terminal is to be installed within the angle of 0 to 135 as shown below STEP 1 STEP 2 STEP 3 Maximum torgue 0 3 Nm ...

Page 12: ...eps to wire the power connector 1 Unplug the power connector and unscrew the screws 2 Strip approximately 1 cm of insulation Insert the wire all the way into the power connector and then turn the screws tight 3 Plug in the connector to the power outlet of the operator terminal Warning To avoid an electrical shock be sure to switch off the power before connecting the communication download cable to...

Page 13: ...tion SW6 Password ON The operator terminal asks the operator to enter a password after power on self test OFF No password is required to start the operator terminal SW7 System Menu ON The operator terminal displays the system menu OFF The operator terminal runs user application without displaying the system menu SW8 Default User Level ON The default user level is set to 1 if the operator terminal ...

Page 14: ...t Adjustment The potentiometer on the back of the operator terminal is used to adjust LCD Contrast STN LCD Use a small screwdriver to turn the potentiometer clock wise contrast down counter clockwise contrast up Note Make sure that the connection is in accordance with the setting of the dip switch es for example RS485 corresponds to SW10 ON See section 4 Dip Switches Pin Function 1 RS422 TX RS485 ...

Page 15: ...layed on the screen for about two seconds and then disappear If the power to the operator terminal or the PC was interrupted while download ing Firmware check or Application check will not pass the self test indicated by an x mark in the self test results after power is restored If this happens the user can simply follow the download procedure to re download the application or data After downloadi...

Page 16: ...rminal Commands with gray background e g F7 F8 can be executed if the associated function keys are pressed The func tions of the commands are briefly explained below System menu command Function Link The operator terminal is connected F7 Confg Sets up the internal time clock and communication parameters in the operator terminal Use and to move to desired field and and to set the value of the field...

Page 17: ... CP400Soft They can for example be used to set a controller bit or register to change a screen or to display a password table Please see the CP400Soft User s Manual for details When a key is pressed the operator terminal will make a beep sound to signal that a command is pressed The default setting a 200 ms beep can be config ured in CP400Soft CP410 Functional keys F1 F10 Numerical keys Navigation...

Page 18: ... set parameters in the operator terminal select F7 Confg in the system menu To set parameters in CP400Soft select Application Workstation Setup Select the Connection tab to set communication parameters CP410 Description F9 Bench test Keyboard Test 16 keys BIOS System RAM Flash memory Buzzer LED BIOS Battery Status RTC COM port Flash ROM F6 Function Test F1 LED F2 Buzzer F3 DIP SW F4 LCD F5 RS232 F...

Page 19: ...rs are correctly configured Also remember to compile the file before downloading it The file has to be compiled every time a change has been made in the file before downloading it Then select Application Download Firmware Application in CP400Soft if it is the first time to download the application to the operator terminal otherwise select Application Download Application The following appears on t...

Page 20: ...will prompt for a password enter the password set in CP400Soft from Application Workstation Setup Once the correct password is entered the operator terminal starts to upload the application to the PC For information about setting a password please see section 7 9 Passwords While the operator terminal is uploading the following is displayed After uploading select File Reconstruct Source in CP400Sof...

Page 21: ...system menu from the operator terminal with the appli cation to be copied The operator terminal will prompt for a password enter the password set in CP400Soft from Application Workstation Setup Once the cor rect password is entered the CP410 starts to copy the application to the other CP410 For information about setting a password please see section 7 9 Passwords The following appears on the scree...

Page 22: ... levels in the table shown below Use the arrow keys and to move and the key to highlight an area for entering a value In the illustration below the button is an action button used to display the password table When the button is selected the password table is displayed on the screen for a user with the right to access the table How to configure an Action Button is described in the CP400Soft User s...

Page 23: ...rd which has been entered There fore this button can be applied to raise or drop one s privileges while the oper ator terminal is in operation How to configure an Action Button is described in the CP400Soft User s Manual Scenario 3 Password protecting a button in the operator terminal The designer can create a button which is protected by a password for execution For example a Goto Screen button c...

Page 24: ...00Soft the operator terminal will prompt for a password The user will need to enter the correct password to copy an application from one CP410 to another Note that setting this password is different from the passwords set in Scenario 1 3 To set this password select Application Workstation Setup in CP400Soft Under the Password tab the designer is able to set the password ...

Page 25: ...port Department 10 rue Ampère 69685 Chassieu France Tel 33 0 4 72 22 17 22 Fax 33 0 4 72 22 17 00 ABB STOTZ KONTAKT GmbH Po Box 10 16 80 69006 Heidelberg Germany Tel 49 0 6221 701 1190 Fax 49 0 6221 701 1333 www abb fr www abb de stotz kontakt ...

Reviews: