background image

73 - 1 - 6124

25124

Flush-mounted
Room Temperature Controller UP
6134 - 24 - 102 - 500
GJ B000 6134 A0142

for ABB Powernet

®

 EIB

and ABB i-bus

® 

EIB

Operating instructions

only for authorized, skilled electricians
with EIB training

Summary of Contents for 6134-24-102-500

Page 1: ...4 25124 Flush mounted Room T emperature Controller UP 6134 24 102 500 GJ B000 6134 A0142 for ABB Powernet EIB and ABB i bus EIB Operating instructions only for authorized skilled electricians with EIB training ...

Page 2: ...el Fig 1 Pos 4 For labeling you may use perforated sheets item No 1799 03 The manufacturer database of ABB is continuously updated It stores the latest applications For relevant descriptions see the Technical Manual of the ABB i bus EIB or ABB Powernet EIB and the respective device windows in the EIBATool Software Package ETS2 version 1 1 or higher In case you do not have the data base orTechnical...

Page 3: ...by an authorized electrician Laying and connection of the bus line as well as application devices must be in conformity with applicable guidelines specified in the EIB Manual of the European Installation Bus Association EIBA The devices are to be programmed using ETS2 version 1 1 or higher or via the ABB Powernet EIB Controller 6910 500 operating system version 2 0 or higher When mounting the room...

Page 4: ...in conjunction with a Powernet mains coupler 6920 U 500 requires a temperature balance to be performed For this purpose proceed as described under Temperature Balancing In multiple device units the room temperature controller must always be mounted at the bottom ...

Page 5: ...onnector strip on the rear side for UP bus coupler or UP mains coupler Control and Indicating Elements Operation Temperature Range Operation 5 C 45 C Measuring range 0 C 40 C Setpoint range 5 C 30 C Type of Protection IP 20 acc to DIN EN 60 529 in built in state Dimensions 56 x 71 mm H xW Weight 0 05 kg ...

Page 6: ...Fig 1 OverallView 1 UP Coupler here eg 6120 U 500 with programming key item 9 and programming LED item 10 4 Covering frame 1721 2x 7 Flush mounted room temperature controller 6134 24 102 500 ...

Page 7: ...10 C 12 Occupancy button to select Stand by Comfort 13 yellow indicating LED dew point alarm 14 red indicating LED freezing heat protection operation 15 green indicating LED convenience operation 16 green indicating LED standby operation 17 green indicating LED night operation ...

Page 8: ...M control with ON OFF telegrams pulse width modulation The control algorithm has a proportional and an integral characteristic PI controller The respective parameters are preset and should not be changed The room temperature controller has the following modes of operation Convenience operation normal operation Standby operation in case of unoccupied rooms with a parameter related temperature lower...

Page 9: ...Dew point alarm the room temperature controller switches off if an appropriate signal is received from an EIB humidity sensor LEDs on the room temperature controller indicate the currently active operating mode Use the rotary knob on the controller to vary the applicable setpoint temperatures within an adjustable range 1 C to 10 C or 0 C no local adjustment The current switching and operating stat...

Page 10: ... temperature mounting For this purpose proceed as described under Start up Subsequent changes can be made For this purpose you must first disassemble the room temperature controller Mounting Before carrying out mounting work on the UP mains coupler make sure the 230V power system is disconnected Position the room temperature controller as required for mounting Fix the covering frame fig 1 item 4 i...

Page 11: ...ng of the UP coupler Secure the controller in position via the screw fig 1 item 5 on the carrier ring of theUP coupler as follows Pull off the rotary knob fig 1 item 6 Tighten screw connecting controller with the carrier ring of the UP coupler Replace the rotary knob fig 1 item 6 Dismantling Pull off the rotary knob fig 1 item 6 Remove the screw located underneath Hold the covering frame and pull ...

Page 12: ...g LED fig 1 item 10 will become illuminated After the physical address has been programmed the red LED will go out Write the number of the physical address on the device using a smudge proof pencil Select and parameterize the application For the required temperature balancing when operating the room temperature controller via the Powernet EIB use a balancing value of 8 C and select lower measuring...

Page 13: ...e has been attained Connect a PC with loaded room temperature software package see ETS product data base or a Powernet EIB controller to the bus line View the temperature indication TRTC determined by the room temperature controller and the parameterized balancing value BVold Determine the room temperature TRoom using a thermometer Determine the new balancing value BVnew as follows BVnew TRoom TRT...

Page 14: ...ht lowering item 17 green The respective LED lights up to signal the active operating mode Control Elements Convenience Standby Operation button item 12 This button enables manual change over from any operating mode to convenience operation normal operation and vice versa Rotary knob item 1 1 Via the rotary knob adjust any desired deviations eg 3 C to 3 C from the preset temperature setpoints ...

Reviews: